NA2XS(FL)2Y 87/150kV

Products

A2XS(FL)2Y 1*400/100 87/150kV

Nexans ref. H11A4SP000250 - Country ref. H11A4SP 1*400/100(FL)//NEX1

 

A2XS(FL)2Y 1*400/100 87/150kV

Nexans ref. H11A4SP000251 - Country ref. H11A4SP 1*400/100(FL)//NEX1,

 

Description

Description

Standards

  • Test
    IEC 60840

Application

Application outdoors, indoors, in ground, in tubes, and in cable ducts.

All high voltage cables are manufactured on the basis of specifications and can be adapted to the requirements of the customer. Therefore, all technical information are purely for information purposes and the electrical characteristics are calculated for values which are specified in the data sheets. For your specific requirements and laying arrangements please don't hesitate to contact us.

Description

AL/S.C/XLPE/S.C/S.C Swell. tape/Cu wires+OPEN HELIX COPPER TAPE/Swell. tape/Alucopo/PE

Stranded Aluminum conductor class 2 according to IEC 60228, semi conducting conductor screen, insulation of cross-linked polyethylene (XLPE), semi conducting insulation screen, semi conducting swellable bedding, copper screen, swellable bedding, aluminium tape (longitudinal one side PE coated aluminum tape) bonded to PE sheath.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Number of conductors
-
Conductor material
Aluminum
Conductor shape
Round compacted
Material of the inner semi-conductor
Semi-conducting compound
Insulation
XLPE
Material of the external semi-conductor
Extruded fully bonded
Material used for longitudinal water tightness
Swellable tape
Concentric conductor
Copper wires and helical copper tape
Sheath colour
Black

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
400 mm²
Nominal insulation thickness
20.6 mm
Screen section
100 mm²
Nominal outer sheath thickness
3.6 mm
Nominal outer diameter
85.0 mm
Maximum outer diameter
- mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
-
Test voltage
218 kV
Frequence
50 Hz

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Laying depth, center of system
1300 mm
Ambient temperature
30 °C
Ambient ground temperature
20 °C
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close