YnHKXS 6/10KV up to 18/30 KV IEC 60332-3

Products

YnHKXS 1*120/50 6/10KV

Nexans ref. M3N4 000646 - Country ref. M3N4 1*120/50//POL-2

  • Conductor cross-section: 120 mm²
  • Conductor diameter: 12.9 mm
  • Nominal insulation thickness: 3.4 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 30.0 mm
  • Approximate net weight: 2081 kg/km
  • Test voltage: 21 kV
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV

 

YnHKXS 1*150/50 6/10KV

Nexans ref. M3N4 009521 - Country ref. M3N4 1*150/50//POL-2

  • Conductor cross-section: 150 mm²
  • Conductor diameter: 14.2 mm
  • Nominal insulation thickness: 3.4 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 1.9 mm
  • Nominal outer diameter: 32.0 mm
  • Approximate net weight: 2385 kg/km
  • Test voltage: 21 kV
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV

 

YnHKXS 1*185/50 6/10KV

Nexans ref. M3N4 000162 - Country ref. M3N4 1*185/50//POL-2

  • Conductor cross-section: 185 mm²
  • Conductor diameter: 15.9 mm
  • Nominal insulation thickness: 3.4 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 1.9 mm
  • Nominal outer diameter: 33.0 mm
  • Approximate net weight: 2735 kg/km
  • Test voltage: 21 kV
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV

 

YnHKXS 1*240/50 6/10KV

Nexans ref. M3N4 000647 - Country ref. M3N4 1*240/50//POL-2

  • Conductor cross-section: 240 mm²
  • Conductor diameter: 18.1 mm
  • Nominal insulation thickness: 3.4 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 2.5 mm
  • Nominal outer diameter: 35.0 mm
  • Approximate net weight: 3218 kg/km
  • Test voltage: 21 kV
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV

 

YnHKXS 1*240/50 8.7/15KV

Nexans ref. M4N4 001730 - Country ref. M4N4 1*240/50//POL-2

  • Conductor cross-section: 240 mm²
  • Conductor diameter: 18.1 mm
  • Nominal insulation thickness: 4.5 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal outer diameter: 38.0 mm
  • Approximate net weight: 3444 kg/km
  • Test voltage: 30 kV
  • Rated Voltage Uo/U (Um): 8.7 / 15 (18) kV

 

YnHKXS 1*300/50 6/10KV

Nexans ref. M3N4 020374 - Country ref. M3N4 1*300/50//POL-2

  • Conductor cross-section: 300 mm²
  • Conductor diameter: 20.3 mm
  • Nominal insulation thickness: 3.4 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 3.2 mm
  • Nominal outer diameter: 38.0 mm
  • Approximate net weight: 3944 kg/km
  • Test voltage: 21 kV
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV

 

YnHKXS 1*400/50 6/10KV

Nexans ref. M3N4 001162 - Country ref. M3N4 1*400/50//POL-2

  • Conductor cross-section: 400 mm²
  • Conductor diameter: 23.2 mm
  • Nominal insulation thickness: 3.4 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal outer diameter: 42.0 mm
  • Approximate net weight: 4832 kg/km
  • Test voltage: 21 kV
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV

 

YnHKXS 1*400/95 6/10KV

Nexans ref. M3N4 001164 - Country ref. M3N4 1*400/95//POL-2

  • Conductor cross-section: 400 mm²
  • Conductor diameter: 23.2 mm
  • Nominal insulation thickness: 3.4 mm
  • Screen section: 95 mm²
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal outer diameter: 43.0 mm
  • Approximate net weight: 5270 kg/km
  • Test voltage: 21 kV
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV

 

YnHKXS 1*70/35 6/10KV

Nexans ref. M3N4 001730 - Country ref. M3N4 1*70/35//POL-2

  • Conductor cross-section: 70 mm²
  • Conductor diameter: 9.7 mm
  • Nominal insulation thickness: 3.4 mm
  • Screen section: 35 mm²
  • Nominal outer sheath thickness: 1.7 mm
  • Nominal outer diameter: 26.0 mm
  • Approximate net weight: 1399 kg/km
  • Test voltage: 21 kV
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV

 

YnHKXS 1*70/50 6/10KV

Nexans ref. M3N4 081729 - Country ref. M3N4 1*70/50//POL-2

  • Conductor cross-section: 70 mm²
  • Conductor diameter: 9.7 mm
  • Nominal insulation thickness: 3.4 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 1.7 mm
  • Nominal outer diameter: 27.0 mm
  • Approximate net weight: 1540 kg/km
  • Test voltage: 21 kV
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV

 

YnHKXS 1*95/35 8.7/15KV

Nexans ref. M4N4 001731 - Country ref. M4N4 1*95/35//POL-2

  • Conductor cross-section: 95 mm²
  • Conductor diameter: 11.4 mm
  • Nominal insulation thickness: 4.5 mm
  • Screen section: 35 mm²
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 31.0 mm
  • Approximate net weight: 1798 kg/km
  • Test voltage: 30 kV
  • Rated Voltage Uo/U (Um): 8.7 / 15 (18) kV

 

YnHKXS 1*95/50 6/10KV

Nexans ref. M3N4 009645 - Country ref. M3N4 1*95/50//POL-2

  • Conductor cross-section: 95 mm²
  • Conductor diameter: 11.4 mm
  • Nominal insulation thickness: 3.4 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 29.0 mm
  • Approximate net weight: 1824 kg/km
  • Test voltage: 21 kV
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV

 

Description

Description

Standards

  • International
    IEC 60332-1-2; IEC 60332-3; IEC 60502-2

CU/SC/XLPE/SC/SC TAPE/CU WIRES/ low temp. PVC

APPLICATION

Power use outdoor application, even wet.

Suitable for fixed installations at open air, in tube or canals and underground.

Max. Operation temperature: 90°

Max. Short circuit temperature : 250° (Max 5 s)

 

CONSTRUCTION

1. Conductor:

Compacted Round conductor class 2

2. Insulation:

Extruded inner semi conductive layer, XLPE insulation and  extruded outer semi conductive layer + Semi-conductive tape

3. Metallic screen layer:

Copper wires with open helix copper tape

4. Outer sheath:

Low Temperature PVC, Red or as per customer requirement

5. Marking:

By Inkjet

6. Packing:

Drums can be wooden or steel

TEST AT WORKS according to IEC 60502-2 & IEC 60332-3

Routine Tests
-Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-2 parag. 16.1 & 16.2
-High voltage test acc. to IEC 60502-2 parag. 16.1 & 16.4
-Max. partial discharge test at 1.73 Uo acc. to IEC 60502-2 parag. 16.1 & 16.3

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided 

                                                                       

Sample tests

 -          Check of the build - up and color coding of the cable                                                      

 -          Check of dimensions                                                    

            Insulation          :           according to IEC 60502-2                       Parag.  17.5.2

            Metallic screen  :           according to IEC 60502-2                       Parag.  17.7

            Oversheath       :           according to IEC 60502-2                       Parag.  17.5.3

- Hot Set Test for XLPE insulation according to IEC 60502-2 parag. 17.10

                                                                       

These tests will be carried out on one length of each size during each inspection . 

Tests certificates will be provided by Liban Cables                                                                      

                                                                       

Type tests

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-2. 

Fire retardance test according to IEC 60332-3

These tests will be carried out on one length of the order.

Tests certificates will be provided by Liban Cables

DRAWING YnHKXS

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Circular compacted
Material of the inner semi-conductor
Semi-conducting compound
Insulation
XLPE
Material of the external semi-conductor
Extruded fully bonded
Concentric conductor
Copper wires and helical copper tape
Sheath colour
Red

Electrical characteristics

Electrical characteristics

Frequence
50 Hz

Mechanical characteristics

Mechanical characteristics

Cable flexibility
10xD
Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

U.V resistance
Yes
Fire retardant
IEC 60332-3
Laying depth, center of system
800 mm
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum operating temperature
-35 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close