Description
Standards
International : IEC 60228; IEC 60332-1-2; IEC 60502-2Description
AL/SC/XLPE/SC/SC TAPE/CU WIRES/PE FR
APPLICATION
Power use outdoor application, even wet.
Suitable for fixed installations at open air, in tube or canals and underground.
Max. Operation temperature: 90°
Max. Short circuit temperature : 250° (Max 5 s)
CONSTRUCTION
1. Conductor:
Compacted Round conductor class 2
2. Insulation:
Extruded inner semi conductive layer, XLPE insulation and extruded outer semi conductive layer + semi conductive tape
3. Metallic screen layer:
Copper wires with open helix copper tape
4. Outer sheath:
PE FR, Black or as per customer requirement
7. Marking:
By Inkjet
8. Packing:
Drums can be wooden or steel
Characteristics
Construction characteristics | |
---|---|
Conductor material | Aluminum |
Conductor shape | Round compacted |
Material of the inner semi-conductor | Semi-conducting compound |
Insulation | XLPE |
Material of the external semi-conductor | Extruded fully bonded |
Concentric conductor | Copper wires and helical copper tape |
Mechanical characteristics | |
Cable flexibility | 10xD |
Mechanical resistance to impacts | Good |
Usage characteristics | |
Flame retardant | IEC 60332-1-2 |
Bending factor when laying | 20(xD) |
Laying depth, center of system | 800mm |
Ambient air temperature | 30°C |
Ambient ground temperature | 20°C |
Max. conductor temperature in service | 90°C |
Short-circuit max. conductor temperature | 250°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
-
TEST AT WORKS ACCORDING TO IEC 60502-2 Unarmored
Routine Tests
-Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-2 parag. 16.1 & 16.2
-High voltage test acc. to IEC 60502-2 parag. 16.1 & 16.4
-Max. partial discharge test at 1.73 Uo acc. to IEC 60502-2 parag. 16.1 & 16.3Liban Cables will carry out these tests on all the lengths and tests certificates will be provided
Sample tests
- Check of the build - up and color coding of the cable
- Check of dimensions
Insulation : according to IEC 60502-2 Parag. 17.5.2
Oversheath : according to IEC 60502-2 Parag. 17.5.3
- Hot Set Test for XLPE insulation according to IEC 60502-2 parag. 17.10
These tests will be carried out on one length of each size during each inspection .
Tests certificates will be provided by Liban Cables
Type tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-2.
These tests will be carried out on one length of the order.
Tests certificates will be provided by Liban Cables