Description
Standards
International : IEC 60332-1-2; IEC 60502-2Description
AL/SC/XLPE/SC/CU WIRES/PVC
APPLICATION
Power use outdoor application, even wet.
Suitable for fixed installations at open air, in tube or canals and underground.
Max. Operation temperature: 90°
Max. Short circuit temperature : 250° (Max 5 s)
CONSTRUCTION
1. Conductor:
Compacted Round conductor class 2
2. Insulation:
Extruded inner semi conductive layer, XLPE insulation and extruded outer semi conductive layer
3. Metallic screen layer:
Copper wires with open helix copper tape
4. Outer sheath:
PVC
5. Marking:
By Inkjet
6. Packing:
Drums can be wooden or steel
Characteristics
Mechanical characteristics | |
---|---|
Mechanical resistance to impacts | Good |
Usage characteristics | |
Operating temperature, range | -15 .. 55°C |
Laying depth, center of system | 800mm |
Ambient air temperature | 30°C |
Ambient ground temperature | 20°C |
Max. conductor temperature in service | 90°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
-
TEST AT WORKS ACCORDING TO IEC 60502-2 / PRÓBY FABRYCZNE XnRUHAKXS, XnRUHKXS
Routine Tests / Badania rutynowe:
• Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-2 parag.16.2 / Maks. rezystancja DC żył w temperaturze 20°C zgodnie z IEC 60228 i IEC 60502-2 pkt 16.2
• High voltage test acc. to IEC 60502-2 parag. 16.4 / Próba wysokim napięciem zgodnie z IEC 60502-2 pkt 16.4
• Max. partial discharge test at 1.73 Uo acc. to IEC 60502-2 parag. 16.3 / Badanie maksymalnych wyładowań niezupełnych przy 1,73 Uo zgodnie z IEC 60502-2 pkt 16.3
Liban Cables will carry out these tests on all the lengths and tests certificates will be provided / Firma Liban Cables przeprowadzi te badania dla wszystkich odcinków kabli i dostarczy świadectwa z badań
Sample tests / Badania próbek:
• Check of the build - up and color coding of the cable / Sprawdzenie rozwijania i kolorowych oznaczeń kabla
• Check of dimensions / Sprawdzenie wymiarów
Insulation / Izolacja : according to IEC 60502-2 / zgodnie z IEC 60502-2 Parag. / pkt. 17.5.2
Metallic screen / Ekran metaliczny : according to IEC 60502-2 / zgodnie z IEC 60502-2 Parag. / pkt. 17.7
Oversheath / Powłoka zewnętrzna : according to IEC 60502-2 / zgodnie z IEC 60502-2 Parag. / pkt. 17.5.3
- Hot Set Test for XLPE insulation according to IEC 60502-2 parag. 17.10 /-Badanie stopnia usieciowania izolacji z XLPE zgodnie z IEC 60502-2 pkt 17.10
These tests will be carried out on one length of each size during each inspection . / Badania te – podczas każdej kontroli – zostaną przeprowadzone na jednym odcinku dla każdego rozmiaru kabla.
Tests certificates will be provided by Liban Cables / Świadectwa z badań dostarczy firma Liban Cables
Type tests / Próby typu
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break ) in accordance with IEC 60502-2. / Charakterystyki mechaniczne materiałów izolacji i powłoki zewnętrznej (wytrzymałość na rozciąganie i wydłużenie przy zerwaniu) zgodnie z IEC 60502-2.
These tests will be carried out on one length of the order / Badania te zostaną przeprowadzone na jednym odcinku z zamówienia
Tests certificates will be provided by Liban Cables / Świadectwa z badań dostarczy firma Liban Cables
Declaration of Performance
Declaration of Performance No: 1000845-LBNI
- Certification Date: 20/05/2020
- AVCP (Assessment and Verification of Constancy of Performance): System 4
- Declared performance: Reaction to fire Fca according to EN50575:2014+A1:2016
Nexans ref. | Country ref. | Product Name |
M6A5 000202 | M6A5 1*400/35//ROM | NA2XSY 1*400/35 18/30KV |
M6A5 000203 | M6A5 1*630/35//ROM | NA2XSY 1*630/35 18/30KV |