Description
Standards
International : IEC 60502-2Description
8.7/15 KV CU/SC/XLPE/SC/SC SWEL/CU WIRES/SWEL/ALLUPE/PE
APPLICATION
Power use outdoor application, even wet.
Suitable for fixed installations at open air, in tube or canals and underground.
Max. Operation temperature: 90°
Max. Short circuit temperature : 250° (Max 5 s)
CONSTRUCTION
1. Conductor:
Compacted Round conductor class 2
2. Insulation:
Extruded inner semi conductive layer, XLPE insulation and extruded outer semi conductive layer
3. Water proof tape:
Semi-conductive swelling tape
4. Metallic screen layer:
Copper wires with open helix copper tape
5. Water proof tape:
Swelling tape
6. Radial water tightness:
Longitudinal PE coated Aluminum Tape
7. Outer sheath:
PE, Black or as per customer requirement
8. Marking:
By Inkjet
9. Packing:
Drums can be wooden or steel
Characteristics
Construction characteristics | |
---|---|
Conductor material | Copper |
Conductor flexibility | Stranded class 2 |
Conductor shape | Round compacted |
Material of the inner semi-conductor | Semi-conducting compound |
Insulation | XLPE |
Material of the external semi-conductor | Extruded fully bonded |
Material used for longitudinal water tightness | Swellable tape |
Concentric conductor | Copper wires and helical copper tape |
Protection | Aluminium tape |
Outer sheath | PE |
Sheath colour | Black |
Dimensional characteristics | |
Conductor cross-section | 300mm² |
Conductor diameter | 20.3mm |
Nominal insulation thickness | 4.5mm |
Screen section | 240mm² |
Nominal outer sheath thickness | 2.3mm |
Nominal outer diameter | 46.0mm |
Approximate net weight | 5683kg/km |
Electrical characteristics | |
Test voltage | 30kV |
Rated Voltage Uo/U (Um) | 8.7 / 15 (17.5) kV |
Frequence | 50Hz |
Perm current rating in air 30°C | 735A |
Permissible current rating when buried | 526A |
Max. DC resistance of the conductor at 20°C | 0.0601Ohm/km |
A.C. Conductor resist. 50Hz and at 90 °C | 0.0791Ohm/km |
Permissible short circuit current conductor 1s | 43.4kA |
Thermal soil resistivity wet zone | 1.5K*m/W |
Mechanical characteristics | |
Mechanical resistance to impacts | Good |
Cable flexibility | 10xD |
Usage characteristics | |
Bending factor when laying | 20(xD) |
Laying depth, center of system | 800mm |
Ambient air temperature | 30°C |
Ambient ground temperature | 20°C |
Max. conductor temperature in service | 90°C |
Short-circuit max. conductor temperature | 250°C |
Minimum operating temperature | -35°C |