Description
Standards
International : IEC 60228; IEC 60502-2Description
AL/SC/XLPE/SC/SC TAPE/CU WIRES/PE
APPLICATION
Power use outdoor application, even wet.
Suitable for fixed installations at open air, in tube or canals and underground.
Max. Operation temperature: 90°
Max. Short circuit temperature : 250° (Max 5 s)
CONSTRUCTION
1. Conductor:
Compacted Round conductor class 2
2. Insulation:
Extruded inner semi conductive layer, XLPE insulation and extruded outer semi conductive layer + semi conductive tape
3. Metallic screen layer:
Copper wires with open helix copper tape
4. Outer sheath:
PE, Black or as per customer requirement
7. Marking:
By Inkjet
8. Packing:
Drums can be wooden or steel
Characteristics
Construction characteristics | |
---|---|
Conductor material | Aluminum |
Conductor flexibility | Stranded class 2 |
Conductor shape | Round compacted |
Material of the inner semi-conductor | Semi-conducting compound |
Insulation | XLPE |
Material of the external semi-conductor | Extruded fully bonded |
Concentric conductor | Copper wires and helical copper tape |
Outer sheath | PE |
Sheath colour | Black |
Dimensional characteristics | |
Conductor cross-section | 185mm² |
Conductor diameter | 16.2mm |
Nominal insulation thickness | 8.0mm |
Screen section | 50mm² |
Nominal outer sheath thickness | 2.3mm |
Nominal outer diameter | 40.0mm |
Approximate net weight | 1852kg/km |
Electrical characteristics | |
Test voltage | 63kV |
Rated Voltage Uo/U (Um) | 18 / 30 (36) kV |
Frequence | 50Hz |
Perm current rating in air 30°C | 424A |
Permissible current rating when buried | 317A |
Max. DC resistance of the conductor at 20°C | 0.164Ohm/km |
A.C. Conductor resist. 50Hz and at 90 °C | 0.21Ohm/km |
Permissible short circuit current conductor 1s | 17.9kA |
Thermal soil resistivity wet zone | 1.5K*m/W |
Mechanical characteristics | |
Mechanical resistance to impacts | Good |
Cable flexibility | 10xD |
Usage characteristics | |
Bending factor when laying | 20(xD) |
Laying depth, center of system | 800mm |
Ambient air temperature | 30°C |
Ambient ground temperature | 20°C |
Max. conductor temperature in service | 90°C |
Short-circuit max. conductor temperature | 250°C |
Minimum operating temperature | -35°C |