PVC insulation, PVC sheathed with copper tape screen

Products

EYO 10*1.5RE

Nexans ref. EYO 001406 - Country ref. EYO 10*1.5RE

  • Conductor flexibility: Solid class 1
  • Conductor material: Solid bare copper
  • Number of conductors: 10
  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 17.0 mm
  • Approximate weight: 426 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 20 A
  • Permissible current rating when buried: 30 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 10*1.5RE.

Nexans ref. EYO 000660 - Country ref. EYO 10*1.5RE.

  • Conductor flexibility: Solid class 1
  • Conductor material: Solid bare copper
  • Number of conductors: 10
  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 17.0 mm
  • Approximate weight: 426 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 20 A
  • Permissible current rating when buried: 30 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 19*1.5RE

Nexans ref. EYO 001413 - Country ref. EYO 19*1.5RE

  • Conductor flexibility: Solid class 1
  • Conductor material: Solid bare copper
  • Number of conductors: 10
  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 17.0 mm
  • Approximate weight: 426 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 20 A
  • Permissible current rating when buried: 30 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 2*16

Nexans ref. EYO 000595 - Country ref. EYO 2*16.

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 2
  • Conductor cross-section: 16 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal outer diameter: 18.5 mm
  • Approximate weight: 653 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Permissible current rating in open air: 85 A
  • Permissible current rating when buried: 115 A
  • Rated Voltage Uo/U (Um): 0,6/1 kV
  • Short-circuit max. conductor temperature: 160 °C

 

EYO 27*1.5RE

Nexans ref. EYO 001419 - Country ref. EYO 27*1.5RE

  • Conductor flexibility: Solid class 1
  • Conductor material: Solid bare copper
  • Number of conductors: 27
  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 24.0 mm
  • Approximate weight: 893 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 20 A
  • Permissible current rating when buried: 30 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 10*1.5

Nexans ref. EYO 000822 - Country ref. EYO 10*1.5

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 10
  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 17.5 mm
  • Approximate weight: 439 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 20 A
  • Permissible current rating when buried: 30 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 12*2.5

Nexans ref. EYO 001456 - Country ref. EYO 12*2.5

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 12
  • Conductor cross-section: 2.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 20.0 mm
  • Approximate weight: 638 kg/km
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 26 A
  • Permissible current rating when buried: 41 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 160 °C

 

EYO 19*1.5

Nexans ref. EYO 000852 - Country ref. EYO 19*1.5

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 19
  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 20.5 mm
  • Approximate weight: 687 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 20 A
  • Permissible current rating when buried: 30 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 19*2.5

Nexans ref. EYO 000945 - Country ref. EYO 19*2.5

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 19
  • Conductor cross-section: 2.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 23.0 mm
  • Approximate weight: 910 kg/km
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 26 A
  • Permissible current rating when buried: 41 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 160 °C

 

EYO 2*2.5

Nexans ref. EYO 000212 - Country ref. EYO 2*2.5

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 2
  • Conductor cross-section: 2.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 12.0 mm
  • Approximate weight: 234 kg/km
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 26 A
  • Permissible current rating when buried: 41 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 160 °C

 

EYO 2*2.5RE

Nexans ref. EYO 001106 - Country ref. EYO 2*2.5RE

  • Conductor flexibility: Solid class 1
  • Conductor material: Solid bare copper
  • Number of conductors: 2
  • Conductor cross-section: 2.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 12.0 mm
  • Approximate weight: 218 kg/km
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 26 A
  • Permissible current rating when buried: 41 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 2*2.5RE.

Nexans ref. EYO 000590 - Country ref. EYO 2*2.5RE.

  • Conductor flexibility: Solid class 1
  • Conductor material: Solid bare copper
  • Number of conductors: 2
  • Conductor cross-section: 2.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 12.0 mm
  • Approximate weight: 218 kg/km
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 26 A
  • Permissible current rating when buried: 41 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 2*6

Nexans ref. EYO 001113 - Country ref. EYO 2*6

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 2
  • Conductor cross-section: 6 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal outer diameter: 15.0 mm
  • Approximate weight: 374 kg/km
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Permissible current rating in open air: 46 A
  • Permissible current rating when buried: 67 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 2*6.

Nexans ref. EYO 000593 - Country ref. EYO 2*6.

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 2
  • Conductor cross-section: 6 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal outer diameter: 15.0 mm
  • Approximate weight: 374 kg/km
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Permissible current rating in open air: 46 A
  • Permissible current rating when buried: 67 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 24*2.5

Nexans ref. EYO 002425 - Country ref. EYO 24*2.5

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 24
  • Conductor cross-section: 2.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 26.0 mm
  • Approximate weight: 1123 kg/km
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 26 A
  • Permissible current rating when buried: 41 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 160 °C

 

EYO 27*1.5

Nexans ref. EYO 000865 - Country ref. EYO 27*1.5

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 27
  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 24.0 mm
  • Approximate weight: 919 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 20 A
  • Permissible current rating when buried: 30 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 27*1.5RE.

Nexans ref. EYO 000662 - Country ref. EYO 27*1.5RE.

  • Conductor flexibility: Solid class 1
  • Conductor material: Solid bare copper
  • Number of conductors: 27
  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 24.0 mm
  • Approximate weight: 893 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 20 A
  • Permissible current rating when buried: 30 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 3*2.5

Nexans ref. EYO 000306 - Country ref. EYO 3*2.5

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 3
  • Conductor cross-section: 2.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 13.0 mm
  • Approximate weight: 269 kg/km
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 24 A
  • Permissible current rating when buried: 36 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 160 °C

 

EYO 3*25

Nexans ref. EYO 000322 - Country ref. EYO 3*25

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 3
  • Conductor cross-section: 25 mm²
  • Nominal insulation thickness: 1.2 mm
  • Nominal outer diameter: 23.0 mm
  • Approximate weight: 1196 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
  • Permissible current rating in open air: 101 A
  • Permissible current rating when buried: 127 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 160 °C

 

EYO 3*6

Nexans ref. EYO 001305 - Country ref. EYO 3*6

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 3
  • Conductor cross-section: 6 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal outer diameter: 16.0 mm
  • Approximate weight: 455 kg/km
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Permissible current rating in open air: 41 A
  • Permissible current rating when buried: 58 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 160 °C

 

EYO 4*1.5

Nexans ref. EYO 000407 - Country ref. EYO 4*1.5

  • Conductor flexibility: Stranded class 2
  • Conductor material: Copper class 2
  • Number of conductors: 4
  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 12.5 mm
  • Approximate weight: 254 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 18 A
  • Permissible current rating when buried: 26 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 160 °C

 

EYO 4*1.5 fire retardant

Nexans ref. EYO 000208 - Country ref. EYO 4*1.5//FR

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 4
  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 12.5 mm
  • Approximate weight: 248 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 18 A
  • Permissible current rating when buried: 26 A
  • Rated Voltage Uo/U (Um): 0,6/1 kV
  • Short-circuit max. conductor temperature: 160 °C

 

EYO 4*1.5RE

Nexans ref. EYO 001304 - Country ref. EYO 4*1.5RE

  • Conductor flexibility: Solid class 1
  • Conductor material: Solid bare copper
  • Number of conductors: 4
  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 12.5 mm
  • Approximate weight: 240 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 18 A
  • Permissible current rating when buried: 26 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 4*1.5RE.

Nexans ref. EYO 000591 - Country ref. EYO 4*1.5RE.

  • Conductor flexibility: Solid class 1
  • Conductor material: Solid bare copper
  • Number of conductors: 4
  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 12.5 mm
  • Approximate weight: 240 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 18 A
  • Permissible current rating when buried: 26 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 4*10

Nexans ref. EYO 000438 - Country ref. EYO 4*10

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 4
  • Conductor cross-section: 10 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal outer diameter: 19.0 mm
  • Approximate weight: 747 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
  • Permissible current rating in open air: 57 A
  • Permissible current rating when buried: 79 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 4*10.

Nexans ref. EYO 000601 - Country ref. EYO 4*10.

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 4
  • Conductor cross-section: 10 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal outer diameter: 19.0 mm
  • Approximate weight: 734 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
  • Permissible current rating in open air: 57 A
  • Permissible current rating when buried: 79 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 4*16

Nexans ref. EYO 001315 - Country ref. EYO 4*16

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 4
  • Conductor cross-section: 16 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal outer diameter: 21.0 mm
  • Approximate weight: 1014 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Permissible current rating in open air: 76 A
  • Permissible current rating when buried: 100 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 4*16.

Nexans ref. EYO 000602 - Country ref. EYO 4*16.

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 4
  • Conductor cross-section: 16 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal outer diameter: 22.0 mm
  • Approximate weight: 999 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Permissible current rating in open air: 76 A
  • Permissible current rating when buried: 100 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 4*2.5

Nexans ref. EYO 000405 - Country ref. EYO 4*2.5

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 4
  • Conductor cross-section: 2.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 13.5 mm
  • Approximate weight: 315 kg/km
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 24 A
  • Permissible current rating when buried: 36 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 4*25.

Nexans ref. EYO 000603 - Country ref. EYO 4*25.

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 4
  • Conductor cross-section: 25 mm²
  • Nominal insulation thickness: 1.2 mm
  • Nominal outer diameter: 25.0 mm
  • Approximate weight: 1466 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
  • Permissible current rating in open air: 101 A
  • Permissible current rating when buried: 127 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 4*6

Nexans ref. EYO 001307 - Country ref. EYO 4*6

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 4
  • Conductor cross-section: 6 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal outer diameter: 17.0 mm
  • Approximate weight: 534 kg/km
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Permissible current rating in open air: 41 A
  • Permissible current rating when buried: 58 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 4*6.

Nexans ref. EYO 000600 - Country ref. EYO 4*6.

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 4
  • Conductor cross-section: 6 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal outer diameter: 17.0 mm
  • Approximate weight: 534 kg/km
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Permissible current rating in open air: 41 A
  • Permissible current rating when buried: 58 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 162 °C

 

EYO 5*2.5

Nexans ref. EYO 001568 - Country ref. EYO 5*2.5

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 5
  • Conductor cross-section: 2.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 15.0 mm
  • Approximate weight: 338 kg/km
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 24 A
  • Permissible current rating when buried: 36 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 160 °C

 

EYO 7*1.5 fire retardant

Nexans ref. EYO 000207 - Country ref. EYO 7*1.5//FR

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 7
  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 14.0 mm
  • Nominal outer diameter: 14.0 mm
  • Approximate weight: 325 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 20 A
  • Permissible current rating when buried: 30 A
  • Rated Voltage Uo/U (Um): 0,6/1 kV
  • Short-circuit max. conductor temperature: 160 °C

 

EYO 7*2.5

Nexans ref. EYO 000918 - Country ref. EYO 7*2.5

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 7
  • Conductor cross-section: 2.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 16.0 mm
  • Approximate weight: 416 kg/km
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 26 A
  • Permissible current rating when buried: 41 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 160 °C

 

EYO 7*4

Nexans ref. EYO 000879 - Country ref. EYO 7*4

  • Conductor flexibility: Class 2 IEC 60228
  • Conductor material: Copper class 2
  • Number of conductors: 7
  • Conductor cross-section: 4 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer diameter: 19.0 mm
  • Approximate weight: 595 kg/km
  • Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
  • Permissible current rating in open air: 35 A
  • Permissible current rating when buried: 53 A
  • Rated Voltage Uo/U (Um): 0.6/ 1 (1.2) kV
  • Short-circuit max. conductor temperature: 160 °C

 

Description

Description

Standards

  • International
    IEC 60228; IEC 60332-1-2; IEC 60502-1

CONSTRUCTION

2.1 Conductor

Plain, annealed electrolytic copper conductors, circular stranded, or sectoral stranded, conforming to the applicable requirements of IEC 60228.

2.2 Insulation

PVC material, conforming to the applicable requirements of IEC 60502-1.

2.3 Assembly

Insulated conductors are laid up, filled where necessary with non-hygroscopic material.

2.4 Screen

Copper tape screen

2.5 Sheath

PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.

2.6 TESTS

Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products.

TEST AT WORKS unarmored multicore

Routine Tests                                                              

 - Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2

 - Voltage test acc. to IEC 60502-1  parag. 15.1 & 15.3                                                   

                                                                       

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided .

                                                                       

Sample Tests                                                              

 - Check of the build - up and color coding of the cable

 - Check of dimensions                                                 

            Insulation          :           according to IEC 60502-1                       Parag.  16.5.2

            Oversheath       :           according to IEC 60502-1                       Parag.  16.5.3

 

These tests will be carried out on one length of each size during each inspection .

Tests certificates will be provided by Liban Cables

                                                                       

Type Tests                                                                  

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-1.

These tests will be carried out on one length of the order .

Tests certificates will be provided by Liban Cables

Cable identification - LV cables ≤ 1KV

INSULATION COLORS:   

 

Neutral

Cond.1

Cond.2

 Cond.3

Cond.4

1 Conductor

 

BLACK

 

 

 

2 Conductors

GREY

BLACK

 

 

 

3 Conductors

 

BLACK

RED

BLUE

 

4 Conductors

GREY

BLACK

RED

BLUE

 

5 Conductors

GREY

BLACK

RED

BLUE

GREEN

 

All numbered control cables (6 conductors and above), are insulated with white color, and numbered with black digits

 

CABLE MARKING OVER THE OUTER JACKET  (by inkjet printing):

LIBAN CABLES     DESCRIPTION     RATED VOLTAGE     SECTION MM2     Year of manufacture     meter marking

 

Other cable identification requirements are available upon request

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor shape
Circular
Insulation
PVC
Screen
Copper tape
Outer sheath
PVC

Dimensional characteristics

Dimensional characteristics

Screen thickness
0.1 µm
Nominal outer sheath thickness
1.8 mm

Electrical characteristics

Electrical characteristics

Thermal soil resistivity wet zone
1 °K.m/W
Test voltage
3500 V

Usage characteristics

Usage characteristics

Laying depth, center of system
600 mm
Operating temperature, range
-15 ... 55 °C
Installation temperature, range
-5 ... 50 °C
Ambient air temperature
30 °C
Max. conductor temperature in service
70 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close