Single core AWA Armored, XLPE insulated, PVC sheathed UV resistant

Products

EXW 1*300 NEW

Nexans ref. EXW 000530 - Country ref. EXW 1*300//UV

  • Conductor cross-section: 300 mm²
  • Nominal insulation thickness: 1.8 mm
  • Nominal armour wire diameter: 1.7 mm
  • Nominal outer sheath thickness: 2.0 mm
  • Approximate weight: 3322 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
  • Permissible current rating in open air: 665 A
  • Permissible current rating when buried: 600 A

 

EXW 1*630//UV NEW

Nexans ref. EXW 001691 - Country ref. EXW 1*630//UV

  • Conductor cross-section: 630 mm²
  • Nominal insulation thickness: 2.0 mm
  • Nominal armour wire diameter: 2.4 mm
  • Nominal outer sheath thickness: 2.3 mm
  • Approximate weight: 6826 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0283 Ohm/km
  • Permissible current rating in open air: 995 A
  • Permissible current rating when buried: 880 A

 

Description

Description

Standards

  • International
    IEC 60228; IEC 60332-1-2; IEC 60502-1

1. SCOPE

This specification covers PVC, circular, single core armoured cables, rated at 0.6/1 KV according to IEC 60502-1 for use indoors, outdoors, in cable ducts and for direct burial underground, where severe mechanical stresses are present.

2. CONSTRUCTION

2.1 Conductor

Plain, annealed electrolytic copper  conductors, circular stranded, conforming to the applicable requirements of IEC 60228.

2.2 Insulation

XLPE insulation, conforming to the applicable requirements of IEC 60502-1.

2.3 Armour

Aluminum wires armor, complying to the applicable requirements of IEC 60502-1.

2.5 Sheath

PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.

2.6 TESTS

Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products.

TEST AT WORKS according to IEC 60502-1 armored

 Routine Tests                                                              

- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2  

- Voltage test acc. to IEC 60502-1  parag. 15.1 & 15.3 

                                                                       

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided. 

                                                                       

Sample Tests                                                              

            - Check of the build - up and color coding of the cable 

            - Check of dimensions 

                        Insulation:         according to IEC 60502-1                       Parag.  16.5.2

                        Armour:             according to IEC 60502-1                       Parag.  16.7

                        Oversheath:      according to IEC 60502-1                       Parag.  16.5.3

                                                                       

These tests will be carried out on one length of each size during each inspection . 

Tests certificates will be provided by Liban Cables 

                                                                       

Type Tests                                                                  

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-1.  

These tests will be carried out on one length of the order . 

Tests certificates will be provided by Liban Cables

DRAWING SINGLE CORE, AWA ARMORED CABLE

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Stranded class 2
Conductor material
Copper
Conductor shape
Circular
Number of conductors
1
Insulation
XLPE
Armour type
Aluminium Wire
Outer sheath
PVC

Dimensional characteristics

Dimensional characteristics

Nominal overall diameter
32.0 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV
Test voltage
3500 V

Usage characteristics

Usage characteristics

Operating temperature, range
-15 ... 55 °C
Installation temperature, range
-5 ... 50 °C
Ambient air temperature
30 °C
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Flame retardant
IEC 60332-1-2
U.V resistance
Yes

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close