Unarmored, Flexible single core XLPE insulation, PVC sheathed

Products

F5XY 1*120 NEW

Nexans ref. F5XY 000080 - Country ref. F5XY 1*120

  • Conductor cross-section: 120 mm²
  • Nominal insulation thickness: 1.2 mm
  • Nominal outer sheath thickness: 1.5 mm
  • Nominal outer diameter: 21.0 mm
  • Approximate weight: 1169 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.161 Ohm/km
  • Permissible current rating in open air: 379 A
  • Permissible current rating when buried: 363 A

 

F5XY 1*150 NEW

Nexans ref. F5XY 000145 - Country ref. F5XY 1*150

  • Conductor cross-section: 150 mm²
  • Nominal insulation thickness: 1.4 mm
  • Nominal outer sheath thickness: 1.6 mm
  • Nominal outer diameter: 21.0 mm
  • Approximate weight: 1441 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.129 Ohm/km
  • Permissible current rating in open air: 435 A
  • Permissible current rating when buried: 405 A

 

F5XY 1*185 NEW

Nexans ref. F5XY 000089 - Country ref. F5XY 1*185

  • Conductor cross-section: 185 mm²
  • Nominal insulation thickness: 1.6 mm
  • Nominal outer sheath thickness: 1.6 mm
  • Nominal outer diameter: 25.0 mm
  • Approximate weight: 1796 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.106 Ohm/km
  • Permissible current rating in open air: 496 A
  • Permissible current rating when buried: 457 A

 

F5XY 1*240 NEW

Nexans ref. F5XY 000090 - Country ref. F5XY 1*240

  • Conductor cross-section: 240 mm²
  • Nominal insulation thickness: 1.7 mm
  • Nominal outer sheath thickness: 1.7 mm
  • Nominal outer diameter: 27.0 mm
  • Approximate weight: 2314 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0801 Ohm/km
  • Permissible current rating in open air: 584 A
  • Permissible current rating when buried: 529 A

 

F5XY 1*25 NEW

Nexans ref. F5XY 001025 - Country ref. F5XY 1*25

  • Conductor cross-section: 25 mm²
  • Nominal insulation thickness: 0.9 mm
  • Nominal outer sheath thickness: 1.4 mm
  • Nominal outer diameter: 11.0 mm
  • Approximate weight: 283 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.78 Ohm/km
  • Permissible current rating in open air: 142 A
  • Permissible current rating when buried: 148 A

 

F5XY 1*300 NEW

Nexans ref. F5XY 000095 - Country ref. F5XY 1*300

  • Conductor cross-section: 300 mm²
  • Nominal insulation thickness: 1.8 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 32.0 mm
  • Approximate weight: 2959 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0641 Ohm/km
  • Permissible current rating in open air: 665 A
  • Permissible current rating when buried: 600 A

 

F5XY 1*35 NEW

Nexans ref. F5XY 000321 - Country ref. F5XY 1*35

  • Conductor cross-section: 35 mm²
  • Nominal insulation thickness: 0.9 mm
  • Nominal outer sheath thickness: 1.4 mm
  • Nominal outer diameter: 12.5 mm
  • Approximate weight: 374 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.554 Ohm/km
  • Permissible current rating in open air: 175 A
  • Permissible current rating when buried: 179 A

 

F5XY 1*50

Nexans ref. F5XY 001026 - Country ref. F5XY 1*50

  • Conductor cross-section: 50 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal outer sheath thickness: 1.4 mm
  • Nominal outer diameter: 13.5 mm
  • Approximate weight: 523 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.386 Ohm/km
  • Permissible current rating in open air: 212 A
  • Permissible current rating when buried: 214 A

 

F5XY 1*500

Nexans ref. F5XY 005570 - Country ref. F5XY 1*500

  • Conductor cross-section: 500 mm²
  • Nominal insulation thickness: 2.2 mm
  • Nominal outer sheath thickness: 2.0 mm
  • Nominal outer diameter: 41.0 mm
  • Approximate weight: 4874 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0384 Ohm/km
  • Permissible current rating in open air: 870 A
  • Permissible current rating when buried: 780 A

 

F5XY 1*630 NEW

Nexans ref. F5XY 000099 - Country ref. F5XY 1*630

  • Conductor cross-section: 630 mm²
  • Nominal insulation thickness: 2.4 mm
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal outer diameter: 49.0 mm
  • Approximate weight: 6058 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0287 Ohm/km
  • Permissible current rating in open air: 995 A
  • Permissible current rating when buried: 880 A

 

F5XY 1*70

Nexans ref. F5XY 000070 - Country ref. F5XY 1*70

  • Conductor cross-section: 70 mm²
  • Nominal insulation thickness: 1.1 mm
  • Nominal outer sheath thickness: 1.4 mm
  • Nominal outer diameter: 15.5 mm
  • Approximate weight: 718 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.272 Ohm/km
  • Permissible current rating in open air: 270 A
  • Permissible current rating when buried: 264 A

 

F5XY 1*95 NEW

Nexans ref. F5XY 000075 - Country ref. F5XY 1*95

  • Conductor cross-section: 95 mm²
  • Nominal insulation thickness: 1.1 mm
  • Nominal outer sheath thickness: 1.5 mm
  • Nominal outer diameter: 18.0 mm
  • Approximate weight: 930 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • Permissible current rating in open air: 327 A
  • Permissible current rating when buried: 317 A

 

Description

Description

Standards

  • International
    IEC 60228; IEC 60332-1-2; IEC 60502-1

1. SCOPE

This specification covers XLPE insulated, circular , Single core unarmoured cables, rated at 0.6/1 KV according to IEC 60502-1.

 

2. CONSTRUCTION

2.1 Conductor

Plain, annealed copper conductors, circular flexible conductor, conforming to the applicable requirements of IEC 60228 class 5.

2.2 Insulation

XLPE, conforming to the applicable requirements of IEC 60502-1.

2.3 Sheath

PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.

2.4 TESTS

Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products.

TEST AT WORKS unarmored single core

Routine Tests

 -  Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2

 -  Spark test during insulation                                                       

 Liban Cables will carry out these tests on all the length and tests certificates will be provided.                                                                  

                                                                       

Sample Tests                                                              

 -          Check of the build - up and color coding of the cable                                                      

 -          Check of dimensions                                                    

            Insulation          :           according to IEC 60502-1                       Parag.  16.5.2

            Oversheath       :           according to IEC 60502-1                       Parag.  16.5.3

                                                                       

These tests will be carried out on one length during  of each size during each inspection . 

Tests certificates will be provided by Liban Cables 

                                                                       

Type Tests                                                                  

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-1.

These tests will be carried out on one length of the order.

Tests certificates will be provided by Liban Cables

DRAWING FLEXIBLE 1C

Cable identification - LV cables ≤ 1KV

INSULATION COLORS:   

 

Neutral

Cond.1

Cond.2

 Cond.3

Cond.4

1 Conductor

 

BLACK

 

 

 

2 Conductors

GREY

BLACK

 

 

 

3 Conductors

 

BLACK

RED

BLUE

 

4 Conductors

GREY

BLACK

RED

BLUE

 

5 Conductors

GREY

BLACK

RED

BLUE

GREEN

 

All numbered control cables (6 conductors and above), are insulated with white color, and numbered with black digits

 

CABLE MARKING OVER THE OUTER JACKET  (by inkjet printing):

LIBAN CABLES     DESCRIPTION     RATED VOLTAGE     SECTION MM2     Year of manufacture     meter marking

 

Other cable identification requirements are available upon request

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper class 5
Conductor shape
Circular
Number of conductors
1
Insulation
XLPE
Outer sheath
PVC
Conductor flexibility
Class 5 IEC 60228

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Operating temperature, range
-15 ... 55 °C
Installation temperature, range
-5 ... 50 °C
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Flame retardant
IEC 60332-1-2

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close