Unarmored, multicore (PN) PVC insulation, PVC sheathed
Unarmored, multicore (PN) PVC insulation, PVC sheathed
0.6 / 1 KV POWER CABLES Conforming to IEC 60502-1
Read moreE(NYY) 2*16+10
Nexans ref. E(NYY) 000010 - Country ref. E(NYY) 2*16+10
- Conductor shape: Circular
- Number of conductors: 3
- Conductor cross-section: 16 mm²
- Nominal insulation thickness: 1.0 mm
- Neutral conductor section (when smaller): 10 mm²
- Insulation thickness of neutral conductor: 1.00 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 17.5 mm
- Approximate weight: 639 kg/km
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Resistance of neutral conductor at 20ºC: 1.83 Ohm/km
- Permissible current rating in open air: 76 A
- Permissible current rating when buried: 100 A
E(NYY) 2*35+16
Nexans ref. E(NYY) 000037 - Country ref. E(NYY) 2*35+16
- Conductor shape: Circular
- Number of conductors: 3
- Conductor cross-section: 35 mm²
- Nominal insulation thickness: 1.2 mm
- Neutral conductor section (when smaller): 16 mm²
- Insulation thickness of neutral conductor: 1.00 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 22.0 mm
- Approximate weight: 1175 kg/km
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Resistance of neutral conductor at 20ºC: 1.15 Ohm/km
- Permissible current rating in open air: 175 A
- Permissible current rating when buried: 195 A
E(NYY) 3*10+6
Nexans ref. E(NYY) 001205 - Country ref. E(NYY) 3*10+6
- Conductor shape: Circular
- Number of conductors: 4
- Conductor cross-section: 10 mm²
- Nominal insulation thickness: 1.0 mm
- Neutral conductor section (when smaller): 6 mm²
- Insulation thickness of neutral conductor: 1.00 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 17.0 mm
- Approximate weight: 579 kg/km
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Resistance of neutral conductor at 20ºC: 3.08 Ohm/km
- Permissible current rating in open air: 57 A
- Permissible current rating when buried: 79 A
E(NYY) 3*120+70 NEW
Nexans ref. E(NYY) 001260 - Country ref. E(NYY) 3*120+70SM
- Conductor shape: Shaped
- Number of conductors: 4
- Conductor cross-section: 120 mm²
- Nominal insulation thickness: 1.4 mm
- Neutral conductor section (when smaller): 70 mm²
- Insulation thickness of neutral conductor: 1.60 mm
- Nominal outer sheath thickness: 2.3 mm
- Nominal outer diameter: 39.0 mm
- Approximate weight: 4547 kg/km
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.268 Ohm/km
- Permissible current rating in open air: 269 A
- Permissible current rating when buried: 311 A
E(NYY) 3*150+70 NEW
Nexans ref. E(NYY) 001270 - Country ref. E(NYY) 3*150+70SM
- Conductor shape: Shaped
- Number of conductors: 4
- Conductor cross-section: 150 mm²
- Nominal insulation thickness: 1.4 mm
- Neutral conductor section (when smaller): 70 mm²
- Insulation thickness of neutral conductor: 1.80 mm
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 42.0 mm
- Approximate weight: 5424 kg/km
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.268 Ohm/km
- Permissible current rating in open air: 309 A
- Permissible current rating when buried: 348 A
E(NYY) 3*150+95
Nexans ref. E(NYY) 001275 - Country ref. E(NYY) 3*150+95SM
- Conductor shape: Circular
- Number of conductors: 4
- Conductor cross-section: 150 mm²
- Nominal insulation thickness: 1.6 mm
- Neutral conductor section (when smaller): 95 mm²
- Insulation thickness of neutral conductor: 1.80 mm
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 44.0 mm
- Approximate weight: 5690 kg/km
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.193 Ohm/km
- Permissible current rating in open air: 309 A
- Permissible current rating when buried: 348 A
E(NYY) 3*16+10
Nexans ref. E(NYY) 001210 - Country ref. E(NYY) 3*16+10
- Conductor shape: Circular
- Number of conductors: 4
- Conductor cross-section: 16 mm²
- Nominal insulation thickness: 1.0 mm
- Neutral conductor section (when smaller): 10 mm²
- Insulation thickness of neutral conductor: 1.00 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 19.0 mm
- Approximate weight: 831 kg/km
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Resistance of neutral conductor at 20ºC: 1.83 Ohm/km
- Permissible current rating in open air: 76 A
- Permissible current rating when buried: 100 A
E(NYY) 3*185+95 NEW
Nexans ref. E(NYY) 001285 - Country ref. E(NYY) 3*185+95SM
- Conductor shape: Shaped
- Number of conductors: 4
- Conductor cross-section: 185 mm²
- Nominal insulation thickness: 2.0 mm
- Neutral conductor section (when smaller): 95 mm²
- Insulation thickness of neutral conductor: 1.60 mm
- Nominal outer sheath thickness: 2.6 mm
- Nominal outer diameter: 47.0 mm
- Approximate weight: 6848 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.193 Ohm/km
- Permissible current rating in open air: 353 A
- Permissible current rating when buried: 392 A
E(NYY) 3*240+120 NEW
Nexans ref. E(NYY) 001295 - Country ref. E(NYY) 3*240+120SM
- Conductor shape: Shaped
- Number of conductors: 4
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 2.2 mm
- Neutral conductor section (when smaller): 120 mm²
- Insulation thickness of neutral conductor: 1.60 mm
- Nominal outer sheath thickness: 2.8 mm
- Nominal outer diameter: 53.0 mm
- Approximate weight: 8810 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.153 Ohm/km
- Permissible current rating in open air: 415 A
- Permissible current rating when buried: 454 A
E(NYY) 3*25+16
Nexans ref. E(NYY) 001215 - Country ref. E(NYY) 3*25+16
- Conductor shape: Circular
- Number of conductors: 4
- Conductor cross-section: 25 mm²
- Nominal insulation thickness: 1.2 mm
- Neutral conductor section (when smaller): 16 mm²
- Insulation thickness of neutral conductor: 1.00 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 23.0 mm
- Approximate weight: 1215 kg/km
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Resistance of neutral conductor at 20ºC: 1.15 Ohm/km
- Permissible current rating in open air: 101 A
- Permissible current rating when buried: 127 A
E(NYY) 3*300+150
Nexans ref. E(NYY) 001305 - Country ref. E(NYY) 3*300+150SM
- Conductor shape: Shaped
- Number of conductors: 4
- Conductor cross-section: 300 mm²
- Nominal insulation thickness: 2.4 mm
- Neutral conductor section (when smaller): 150 mm²
- Insulation thickness of neutral conductor: 1.80 mm
- Nominal outer sheath thickness: 3.0 mm
- Nominal outer diameter: 59.0 mm
- Approximate weight: 11077 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.124 Ohm/km
- Permissible current rating in open air: 472 A
- Permissible current rating when buried: 516 A
E(NYY) 3*35+16
Nexans ref. E(NYY) 001335 - Country ref. E(NYY) 3*35+16
- Conductor shape: Circular
- Number of conductors: 4
- Conductor cross-section: 35 mm²
- Nominal insulation thickness: 1.2 mm
- Neutral conductor section (when smaller): 16 mm²
- Insulation thickness of neutral conductor: 1.00 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 25.0 mm
- Approximate weight: 1424 kg/km
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Resistance of neutral conductor at 20ºC: 1.15 Ohm/km
- Permissible current rating in open air: 125 A
- Permissible current rating when buried: 153 A
E(NYY) 3*35+2*25
Nexans ref. E(NYY) 001350 - Country ref. E(NYY) 3*35+2*25
- Conductor shape: Circular
- Number of conductors: 5
- Conductor cross-section: 35 mm²
- Nominal insulation thickness: 1.2 mm
- Neutral conductor section (when smaller): 25 mm²
- Insulation thickness of neutral conductor: 1.20 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 28.0 mm
- Approximate weight: 1792 kg/km
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.727 Ohm/km
- Permissible current rating in open air: 125 A
- Permissible current rating when buried: 153 A
E(NYY) 3*50+25
Nexans ref. E(NYY) 000340 - Country ref. E(NYY) 3*50+25
- Conductor shape: Circular
- Number of conductors: 4
- Conductor cross-section: 50 mm²
- Nominal insulation thickness: 1.4 mm
- Neutral conductor section (when smaller): 25 mm²
- Insulation thickness of neutral conductor: 1.20 mm
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 29.0 mm
- Approximate weight: 1976 kg/km
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.727 Ohm/km
- Permissible current rating in open air: 151 A
- Permissible current rating when buried: 184 A
E(NYY) 3*70+35
Nexans ref. E(NYY) 000339 - Country ref. E(NYY) 3*70+35SM/RM
- Conductor shape: Shaped
- Number of conductors: 4
- Conductor cross-section: 70 mm²
- Nominal insulation thickness: 1.4 mm
- Neutral conductor section (when smaller): 35 mm²
- Insulation thickness of neutral conductor: 1.20 mm
- Nominal outer sheath thickness: 2.0 mm
- Nominal outer diameter: 31.0 mm
- Approximate weight: 2616 kg/km
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.524 Ohm/km
- Permissible current rating in open air: 192 A
- Permissible current rating when buried: 227 A
E(NYY) 3*95+50
Nexans ref. E(NYY) 001251 - Country ref. E(NYY) 3*95+50SM/RM
- Conductor shape: Shaped
- Number of conductors: 4
- Conductor cross-section: 95 mm²
- Nominal insulation thickness: 1.6 mm
- Neutral conductor section (when smaller): 50 mm²
- Insulation thickness of neutral conductor: 1.40 mm
- Nominal outer sheath thickness: 2.2 mm
- Nominal outer diameter: 36.0 mm
- Approximate weight: 3607 kg/km
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.387 Ohm/km
- Permissible current rating in open air: 232 A
- Permissible current rating when buried: 272 A
E(NYY) 4*10+6
Nexans ref. E(NYY) 011418 - Country ref. E(NYY) 4*10+6
- Conductor shape: Circular
- Number of conductors: 5
- Conductor cross-section: 10 mm²
- Nominal insulation thickness: 1.0 mm
- Neutral conductor section (when smaller): 6 mm²
- Insulation thickness of neutral conductor: 1.00 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 18.5 mm
- Approximate weight: 656 kg/km
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Resistance of neutral conductor at 20ºC: 3.08 Ohm/km
- Permissible current rating in open air: 57 A
- Permissible current rating when buried: 79 A
E(NYY) 4*120+70 NEW
Nexans ref. E(NYY) 001428 - Country ref. E(NYY) 4*120+70
- Conductor shape: Circular
- Number of conductors: 5
- Conductor cross-section: 120 mm²
- Nominal insulation thickness: 1.6 mm
- Neutral conductor section (when smaller): 70 mm²
- Insulation thickness of neutral conductor: 1.40 mm
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 46.0 mm
- Approximate weight: 5856 kg/km
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.268 Ohm/km
- Permissible current rating in open air: 269 A
- Permissible current rating when buried: 311 A
E(NYY) 4*150+95
Nexans ref. E(NYY) 001431 - Country ref. E(NYY) 4*150+95
- Conductor shape: Circular
- Number of conductors: 5
- Conductor cross-section: 150 mm²
- Nominal insulation thickness: 1.6 mm
- Neutral conductor section (when smaller): 95 mm²
- Insulation thickness of neutral conductor: 1.80 mm
- Nominal outer sheath thickness: 2.6 mm
- Nominal outer diameter: 51.0 mm
- Approximate weight: 7283 kg/km
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.193 Ohm/km
- Permissible current rating in open air: 309 A
- Permissible current rating when buried: 348 A
E(NYY) 4*185+95
Nexans ref. E(NYY) 001432 - Country ref. E(NYY) 4*185+95
- Conductor shape: Circular
- Number of conductors: 5
- Conductor cross-section: 185 mm²
- Nominal insulation thickness: 2.0 mm
- Neutral conductor section (when smaller): 95 mm²
- Insulation thickness of neutral conductor: 1.60 mm
- Nominal outer sheath thickness: 2.8 mm
- Nominal outer diameter: 56.0 mm
- Approximate weight: 8761 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.193 Ohm/km
- Permissible current rating in open air: 353 A
- Permissible current rating when buried: 392 A
E(NYY) 4*240+120
Nexans ref. E(NYY) 001535 - Country ref. E(NYY) 4*240+120
- Conductor shape: Circular
- Number of conductors: 5
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 2.2 mm
- Neutral conductor section (when smaller): 120 mm²
- Insulation thickness of neutral conductor: 1.60 mm
- Nominal outer sheath thickness: 2.9 mm
- Nominal outer diameter: 63.0 mm
- Approximate weight: 11293 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.153 Ohm/km
- Permissible current rating in open air: 415 A
- Permissible current rating when buried: 454 A
E(NYY) 4*25+16
Nexans ref. E(NYY) 001418 - Country ref. E(NYY) 4*25+16
- Conductor shape: Circular
- Number of conductors: 5
- Conductor cross-section: 25 mm²
- Nominal insulation thickness: 1.2 mm
- Neutral conductor section (when smaller): 16 mm²
- Insulation thickness of neutral conductor: 1.00 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 25.0 mm
- Approximate weight: 1408 kg/km
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Resistance of neutral conductor at 20ºC: 1.15 Ohm/km
- Permissible current rating in open air: 101 A
- Permissible current rating when buried: 127 A
E(NYY) 4*35+16
Nexans ref. E(NYY) 001420 - Country ref. E(NYY) 4*35+16
- Conductor shape: Circular
- Number of conductors: 5
- Conductor cross-section: 35 mm²
- Nominal insulation thickness: 1.2 mm
- Neutral conductor section (when smaller): 16 mm²
- Insulation thickness of neutral conductor: 1.00 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 27.0 mm
- Approximate weight: 1815 kg/km
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Resistance of neutral conductor at 20ºC: 1.15 Ohm/km
- Permissible current rating in open air: 125 A
- Permissible current rating when buried: 153 A
E(NYY) 4*35+25
Nexans ref. E(NYY) 001421 - Country ref. E(NYY) 4*35+25
- Conductor shape: Circular
- Number of conductors: 5
- Conductor cross-section: 35 mm²
- Nominal insulation thickness: 1.2 mm
- Neutral conductor section (when smaller): 25 mm²
- Insulation thickness of neutral conductor: 1.20 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 28.0 mm
- Approximate weight: 1916 kg/km
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.727 Ohm/km
- Permissible current rating in open air: 125 A
- Permissible current rating when buried: 153 A
E(NYY) 4*50+25
Nexans ref. E(NYY) 001422 - Country ref. E(NYY) 4*50+25
- Conductor shape: Circular
- Number of conductors: 5
- Conductor cross-section: 50 mm²
- Nominal insulation thickness: 1.4 mm
- Neutral conductor section (when smaller): 25 mm²
- Insulation thickness of neutral conductor: 1.20 mm
- Nominal outer sheath thickness: 2.0 mm
- Nominal outer diameter: 32.0 mm
- Approximate weight: 2483 kg/km
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.727 Ohm/km
- Permissible current rating in open air: 151 A
- Permissible current rating when buried: 184 A
E(NYY) 4*70+35
Nexans ref. E(NYY) 001424 - Country ref. E(NYY) 4*70+35
- Conductor shape: Circular
- Number of conductors: 5
- Conductor cross-section: 70 mm²
- Nominal insulation thickness: 1.4 mm
- Neutral conductor section (when smaller): 35 mm²
- Insulation thickness of neutral conductor: 1.20 mm
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 36.0 mm
- Approximate weight: 3408 kg/km
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.524 Ohm/km
- Permissible current rating in open air: 192 A
- Permissible current rating when buried: 227 A
E(NYY) 4*95+50
Nexans ref. E(NYY).001426 - Country ref. E(NYY) 4*95+50
- Conductor shape: Circular
- Number of conductors: 5
- Conductor cross-section: 95 mm²
- Nominal insulation thickness: 1.6 mm
- Neutral conductor section (when smaller): 50 mm²
- Insulation thickness of neutral conductor: 1.40 mm
- Nominal outer sheath thickness: 2.3 mm
- Nominal outer diameter: 42.0 mm
- Approximate weight: 4670 kg/km
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.387 Ohm/km
- Permissible current rating in open air: 232 A
- Permissible current rating when buried: 272 A
Description
Description
Standards
-
InternationalIEC 60228; IEC 60332-1-2; IEC 60502-1
1. SCOPE
This specification covers PVC insulated, circular or shaped, multicore unarmoured cables, rated at 0.6/1 KV according to IEC 60502-1 for use indoors, outdoors, and in cable ducts.
2. CONSTRUCTION
2.1 Phase Conductor
Plain, annealed electrolytic copper conductors, circular stranded, or sectoral stranded only for 3 Cores+Eath: sizes ≥70 to ≤300, conforming to the applicable requirements of IEC 60228.
2.2 Phase Conductor Insulation
PVC material, conforming to the applicable requirements of IEC 60502-1.
2.3 Neutral Conductor
Plain, annealed electrolytic copper conductors, circular stranded, or sectoral stranded only for 3 Cores+Eath: sizes ≥70 to ≤300, conforming to the applicable requirements of IEC 60228.
2.4 Neutral Conductor Insulation
PVC material, conforming to the applicable requirements of IEC 60502-1.
2.5 Assembly
Insulated conductors are laid up, filled where necessary with non-hygroscopic material.
2.6 Sheath
PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.
2.7 TESTS
Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products.
TEST AT WORKS unarmored multicore
Routine Tests
- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2
- Voltage test acc. to IEC 60502-1 parag. 15.1 & 15.3
Liban Cables will carry out these tests on all the lengths and tests certificates will be provided .
Sample Tests
- Check of the build - up and color coding of the cable
- Check of dimensions
Insulation : according to IEC 60502-1 Parag. 16.5.2
Oversheath : according to IEC 60502-1 Parag. 16.5.3
These tests will be carried out on one length of each size during each inspection .
Tests certificates will be provided by Liban Cables
Type Tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-1.
These tests will be carried out on one length of the order .
Tests certificates will be provided by Liban Cables
Cable identification - LV cables ≤ 1KV
INSULATION COLORS:
|
Neutral |
Cond.1 |
Cond.2 |
Cond.3 |
Cond.4 |
1 Conductor |
|
BLACK |
|
|
|
2 Conductors |
GREY |
BLACK |
|
|
|
3 Conductors |
|
BLACK |
RED |
BLUE |
|
4 Conductors |
GREY |
BLACK |
RED |
BLUE |
|
5 Conductors |
GREY |
BLACK |
RED |
BLUE |
GREEN |
All numbered control cables (6 conductors and above), are insulated with white color, and numbered with black digits
CABLE MARKING OVER THE OUTER JACKET (by inkjet printing):
LIBAN CABLES DESCRIPTION RATED VOLTAGE SECTION MM2 Year of manufacture meter marking
Other cable identification requirements are available upon request
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania