A2XS(FL)H 110kV

Products

A2XS(FL)H 1*240/95 64/110kV

Nexans ref. H9A4DU 011118 - Country ref. H9A4DU 1*240/95(FL)//POL

 

Description

Description

Standards

  • International
    IEC 60840

AL/S.C/XLPE/S.C/S.C Swell. tape/Cu wires+OPEN HELIX COPPER TAPE/Swell. tape/Alucopo/LSZH

APPLICATION

Application in ground, outdoors, in tubes, indoors and in cable ducts.

 

All high voltage cables are manufactured on the basis of specifications and can be adapted to the requirements of the customer. Therefore, all technical information are purely for information purposes and the electrical characteristics are calculated for values which are specified in the data sheets. For your specific requirements and laying arrangements please don't hesitate to contact us.

 

DESCRIPTION

Stranded Aluminum conductor according to IEC 60228, semi conducting conductor screen, insulation of cross-linked polyethylene (XLPE), semi conducting insulation screen, semi conducting swellable tape bedding, copper screen, swellable tape bedding, aluminium tape bonded to LSZH sheath.

TEST AT WORKS HV CABLES

Routine Tests

 -          Max. partial discharge test  at 1.5 Uo acc. to IEC 60840  parag.9.2

 -          High voltage test acc. to IEC 60840  parag. 9.3

 

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided

 

Sample tests

 -          Conductor examination  acc. to IEC 60840 parag. 10.4

 -          Max. DC resistance of conductor acc. to IEC 60840 parag. 10.5

 -          Check of thicknesses

                        Insulation          :           according to IEC 60840              Parag.  10.6.2

                        Metallic screen  :           according to IEC 60840              Parag.  10.7

                        Oversheath       :           according to IEC 60840              Parag.  10.6.3

 -          Hot set test for insulation acc. to IEC 60840 parag. 10.9

 -          Measurement of capacitance acc. to IEC 60840 parag. 10.10

 

These tests will be carried out on one length of each size during each inspection .

Tests certificates will be provided by Liban Cables

DRAWING H9A4DU

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Number of conductors
1
Conductor material
Aluminum
Conductor shape
Round compacted
Material of the inner semi-conductor
Semi-conducting compound
Insulation
XLPE
Material of the external semi-conductor
Extruded fully bonded
Material used for longitudinal water tightness
Swellable tape
Concentric conductor
Copper wires and helical copper tape
Outer sheath
LSZH compound
Sheath colour
Black

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
240 mm²
Nominal insulation thickness
15.0 mm
Screen section
95 mm²
Nominal outer sheath thickness
3.2 mm
Nominal outer diameter
67.0 mm
Maximum outer diameter
72.0 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
64/100 (123) kV
Test voltage
160 kV
Frequence
50 Hz

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Bending factor when laying
30 (xD)
Laying depth, center of system
1300 mm
Ambient ground temperature
20 °C
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*