1C AL Cond. CTS, AWA and PVC sheath

Products

M3A2W 1*120

Nexans ref. M3A2W 000182 - Country ref. M3A2W 1*120

  • Conductor cross-section: 120 mm²
  • Conductor diameter: 12.8 mm
  • Nominal insulation thickness: 3.4 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer sheath thickness: 2.0 mm
  • Nominal outer diameter: 31.0 mm
  • Approximate net weight: 1249 kg/km
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV
  • Perm current rating in air 30°C: 324 A
  • Permissible current rating when buried: 252 A
  • Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.323 Ohm/km

M3A2W 1*185

Nexans ref. M3A2W 000185 - Country ref. M3A2W 1*185

  • Conductor cross-section: 185 mm²
  • Conductor diameter: 16.2 mm
  • Nominal insulation thickness: 3.4 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal outer diameter: 35.0 mm
  • Approximate net weight: 1588 kg/km
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV
  • Perm current rating in air 30°C: 424 A
  • Permissible current rating when buried: 317 A
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.21 Ohm/km

M3A2W 1*300 NEW

Nexans ref. M3A2W 000205 - Country ref. M3A2W 1*300

  • Conductor cross-section: 300 mm²
  • Conductor diameter: 20.3 mm
  • Nominal insulation thickness: 3.4 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal outer diameter: 39.0 mm
  • Approximate net weight: 2068 kg/km
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV
  • Perm current rating in air 30°C: 577 A
  • Permissible current rating when buried: 474 A
  • Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.129 Ohm/km

M3A2W 1*400

Nexans ref. M3A2W 000210 - Country ref. M3A2W 1*400

  • Conductor cross-section: 400 mm²
  • Conductor diameter: 23.2 mm
  • Nominal insulation thickness: 3.4 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer sheath thickness: 2.4 mm
  • Nominal outer diameter: 32.0 mm
  • Approximate net weight: 2619 kg/km
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV
  • Perm current rating in air 30°C: 673 A
  • Permissible current rating when buried: 470 A
  • Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0997 Ohm/km

M3A2W 1*500

Nexans ref. M3A2W 000220 - Country ref. M3A2W 1*500

  • Conductor cross-section: 500 mm²
  • Conductor diameter: 26.2 mm
  • Nominal insulation thickness: 3.4 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer sheath thickness: 2.5 mm
  • Nominal outer diameter: 48.0 mm
  • Approximate net weight: 3128 kg/km
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV
  • Perm current rating in air 30°C: 789 A
  • Permissible current rating when buried: 537 A
  • Max. DC resistance of the conductor at 20°C: 0.0605 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0794 Ohm/km

M5A2W 1*120

Nexans ref. M5A2W 000200 - Country ref. M5A2W 1*120

  • Conductor cross-section: 120 mm²
  • Conductor diameter: 12.8 mm
  • Nominal insulation thickness: 3.4 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal outer diameter: 35.0 mm
  • Approximate net weight: 1518 kg/km
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 324 A
  • Permissible current rating when buried: 252 A
  • Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.323 Ohm/km

M5A2W 1*500 NEW

Nexans ref. M5A2W 000245 - Country ref. M5A2W 1*500

  • Conductor cross-section: 500 mm²
  • Conductor diameter: 26.2 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer sheath thickness: 2.7 mm
  • Nominal outer diameter: 52.0 mm
  • Approximate net weight: 3522 kg/km
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 789 A
  • Permissible current rating when buried: 537 A
  • Max. DC resistance of the conductor at 20°C: 0.0605 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0794 Ohm/km

M6A2W 1*150

Nexans ref. M6A2W 000121 - Country ref. M6A2W 1*150

  • Conductor cross-section: 150 mm²
  • Conductor diameter: 14.4 mm
  • Nominal insulation thickness: 8.0 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer sheath thickness: 2.4 mm
  • Nominal outer diameter: 43.0 mm
  • Approximate net weight: 2130 kg/km
  • Rated Voltage Uo/U (Um): 18 / 30 (36) kV
  • Perm current rating in air 30°C: 368 A
  • Permissible current rating when buried: 281 A
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.264 Ohm/km

M6A2W 1*240

Nexans ref. M6A2W 000229 - Country ref. M6A2W 1*240

  • Conductor cross-section: 240 mm²
  • Conductor diameter: 17.9 mm
  • Nominal insulation thickness: 8.0 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer sheath thickness: 2.6 mm
  • Nominal outer diameter: 46.0 mm
  • Approximate net weight: 2600 kg/km
  • Rated Voltage Uo/U (Um): 18 / 30 (36) kV
  • Perm current rating in air 30°C: 502 A
  • Permissible current rating when buried: 367 A
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km

M6A2W 1*300

Nexans ref. M6A2W 000231 - Country ref. M6A2W 1*300

  • Conductor cross-section: 300 mm²
  • Conductor diameter: 20.3 mm
  • Nominal insulation thickness: 8.0 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer sheath thickness: 2.6 mm
  • Nominal outer diameter: 49.0 mm
  • Approximate net weight: 2932 kg/km
  • Rated Voltage Uo/U (Um): 18 / 30 (36) kV
  • Perm current rating in air 30°C: 577 A
  • Permissible current rating when buried: 474 A
  • Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.129 Ohm/km

M6A2W 1*400

Nexans ref. M6A2W 000341 - Country ref. M6A2W 1*400

  • Conductor cross-section: 400 mm²
  • Conductor diameter: 23.2 mm
  • Nominal insulation thickness: 8.0 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer sheath thickness: 2.8 mm
  • Nominal outer diameter: 53.0 mm
  • Approximate net weight: 3468 kg/km
  • Rated Voltage Uo/U (Um): 18 / 30 (36) kV
  • Perm current rating in air 30°C: 673 A
  • Permissible current rating when buried: 470 A
  • Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0997 Ohm/km

M6A2W 1*500 NEW

Nexans ref. M6A2W 000236 - Country ref. M6A2W 1*500

  • Conductor cross-section: 500 mm²
  • Conductor diameter: 26.2 mm
  • Nominal insulation thickness: 8.0 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer sheath thickness: 2.9 mm
  • Nominal outer diameter: 57.0 mm
  • Approximate net weight: 4033 kg/km
  • Rated Voltage Uo/U (Um): 18 / 30 (36) kV
  • Perm current rating in air 30°C: 789 A
  • Permissible current rating when buried: 537 A
  • Max. DC resistance of the conductor at 20°C: 0.0605 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0794 Ohm/km

M6A2W 1*630

Nexans ref. M6A2W 000250 - Country ref. M6A2W 1*630

  • Conductor cross-section: 630 mm²
  • Conductor diameter: 29.6 mm
  • Nominal insulation thickness: 8.0 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer sheath thickness: 3.0 mm
  • Nominal outer diameter: 61.0 mm
  • Approximate net weight: 4664 kg/km
  • Rated Voltage Uo/U (Um): 18 / 30 (36) kV
  • Perm current rating in air 30°C: 916 A
  • Permissible current rating when buried: 611 A
  • Max. DC resistance of the conductor at 20°C: 0.0469 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0626 Ohm/km

M6A2W 1*95

Nexans ref. M6A2W 000227 - Country ref. M6A2W 1*95

  • Conductor cross-section: 95 mm²
  • Conductor diameter: 11.7 mm
  • Nominal insulation thickness: 8.0 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal outer diameter: 39.0 mm
  • Approximate net weight: 1720 kg/km
  • Rated Voltage Uo/U (Um): 18 / 30 (36) kV
  • Perm current rating in air 30°C: 280 A
  • Permissible current rating when buried: 221 A
  • Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.41 Ohm/km

Description

Description

Standards

  • International
    IEC 60228; IEC 60332-1-2; IEC 60502-2

1-SCOPE

This specification covers single core armoured cables, conforming to IEC 60502-2 Specifications.
 

2. CONSTRUCTION

2.1 Conductor

Plain, Aluminum conductors, circular stranded, conforming to the applicable requirements of IEC 60228.

2.2 Insulation

Extruded inner semi conductive layer, XLPE insulation and  extruded outer semi conductive layer .

2.3 Metallic Screen Layer

Copper tape

2.4 Separation Sheath

PVC .

2.5 Armour

ALUMINUM WIRES .

2.5 Sheath

PVC .

3. TESTS

All tests required by IEC 60502-2 either on Raw material or on finished products.

TEST AT WORKS according to IEC 60502-2 for armored cables

Routine Tests

 -          Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-2 parag.16.1 & 16.2

 -          High voltage test acc. to IEC 60502-2  parag. 16.1 & 16.4

 -          Max. partial discharge test  at 1.73 Uo acc. to IEC 60502-2  parag.16.1 & 16.3

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided.

 

Sample Tests

 -          Check of the build - up and color coding of the cable                                                      

 -          Check of dimensions                                                    

            Insulation                      :           according to IEC 60502-2           Parag.  17.5.2

            Separation sheath         :           according to IEC 60502-2           Parag.  17.5.3

            Armouring                     :           according to IEC 60502-2          Parag.  17.7

            Oversheath                   :           according to IEC 60502-2           Parag.  17.5.3

-           Hot Set Test                  :           according to IEC 60502-2           Parag.  17.10

These tests will be carried out on one length of each size during each inspection .

Tests certificates will be provided by Liban Cables

                                                                       

Type Tests

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break  ) in accordance with IEC 60502-2.

These tests will be carried out on one length of the order .

Tests certificates will be provided by Liban Cables

DRAWING 1C AL COND AWA ARMORED

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Circular
Material of the inner semi-conductor
Extruded
Armour type
Aluminium Wire
Insulation
XLPE
Screen
Copper tape
Outer sheath
PVC
Colour
Black

Electrical characteristics

Electrical characteristics

Thermal soil resistivity wet zone
1.5 °K.m/W

Mechanical characteristics

Mechanical characteristics

Cable flexibility
8xD

Usage characteristics

Usage characteristics

Laying depth, center of system
800 mm
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Max. conductor temperature in service
90 °C
Operating temperature, range
-15 - 55 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close