SFC2XRU 4*120

Description

Description

Standards

  • International
    IEC 60331-21 ; IEC 60502-1

CONSTRUCTION

1- Conductors

stranded-class 2  according to IEC 60228

2 - Mica tape

MICA/GLASS FIRE RESISTANT TAPE

3 - Insulation

XLPE

4 - Assembly

Insulated conductors are laid up, filled where necessary with non-hygroscopic material and covered with an extruded thickness of thermoplastic material.

5 - Armour

Galvanized round wires completely covering the assembly of cores complying to the applicable requirements of IEC 60502-1.

6 - Outer sheath

Low Smoke Zero Halogen compound, Color as per customer requirement

7 - Packing

Drums can be wooden or steel

TEST AT WORKS FIRE RESISTANT ARMORED

Routine Tests

 -          Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag.15.1&15.2

 -          Voltage test acc. to IEC 60502-1  parag. 15.1&15.3

 

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided

 

Sample Tests

 -          Check of the build - up and color coding of the cable

 -          Check of dimensions

            Insulation          :           according to IEC 60502-1                       Parag.  16.5.2

            Armour              :           according to IEC 60502-1                       Parag.  16.7

            Oversheath       :           according to IEC 60502-1                       Parag.  16.5.3

 - Hot Set Test for XLPE insulation according to IEC 60502-1                 Parag. 16.9

These tests will be carried out on one length of each size during each inspection .

Tests certificates will be provided by Liban Cables.

 

Type Tests

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-1.

Fire Resistance test according to IEC 60331-21 (750۫C for 90 mins) :

            - 500V between conductors

            - 300V between cond. & earth

These tests will be carried out on one length of the order.

Tests certificates will be provided by Liban Cables

DRAWING FIRE RESISTANT ARMORED CABLES

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Class 2
Conductor material
Copper class 2
Conductor shape
Circular
Number of conductors
4
Insulation
Micatape + XLPE
Armour type
Galvanized steel wires
Outer sheath
LSZH compound

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
120 mm²
Nominal insulation thickness
1.2 mm
Nominal armour wire diameter
2.5 mm
Nominal outer sheath thickness
2.5 mm
Nominal overall diameter
52.0 mm
Approximate weight
7857 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV
Test voltage
3500 V
Max. DC resistance of the conductor at 20°C
0.153 Ohm/km

Usage characteristics

Usage characteristics

U.V resistance
Yes
Fire resistant
IEC 60331-21
Flame retardant
IEC 60332-1-2
Operating temperature, range
-25 ... 55 °C
Short-circuit max. conductor temperature
250 °C
Max. conductor temperature in service
90 °C
Installation temperature, range
-5 ... 50 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close