SFC2XU 5*25

Description

Description

Standards

  • International
    IEC 60331; IEC 60502-1

CONSTRUCTION

1- Conductors

stranded-class 2  according to IEC 60228

2 - Mica tape

MICA/GLASS FIRE RESISTANT TAPE

3 - Insulation

XLPE

4 - Outer sheath

Halogen free compound, Color as per customer requirement

5 - Packing

Drums can be wooden or steel

TEST AT WORKS FOR FIRE RESISTANT MULTICORE CABLES

Routine Tests

 - Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2

 - Voltage test acc. to IEC 60502-1  parag.15.1& 15.3

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided.                                                                

 

Sample Tests

 - Check of the build - up and color coding of the cable

 - Check of dimensions

            Insulation          :           according to IEC 60502-1                       Parag.  16.5.2

            Oversheath       :           according to IEC 60502-1                       Parag.  16.5.3

                                                                       

These tests will be carried out on one length of each size during each inspection .

Tests certificates will be provided by Liban Cables

 

Type Tests

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break ) in accordance with IEC 60502-1.

Fire resistance test according to IEC 60331-21 ( 750°C for 90 mins. ) :

            - 500V between conductors

These tests will be carried out on one length of the order .

Tests certificates will be provided by Liban Cables

Cable identification - LV cables ≤ 1KV

INSULATION COLORS:   

 

Neutral

Cond.1

Cond.2

 Cond.3

Cond.4

1 Conductor

 

BLACK

 

 

 

2 Conductors

GREY

BLACK

 

 

 

3 Conductors

 

BLACK

RED

BLUE

 

4 Conductors

GREY

BLACK

RED

BLUE

 

5 Conductors

GREY

BLACK

RED

BLUE

GREEN

 

All numbered control cables (6 conductors and above), are insulated with white color, and numbered with black digits

 

CABLE MARKING OVER THE OUTER JACKET  (by inkjet printing):

LIBAN CABLES     DESCRIPTION     RATED VOLTAGE     SECTION MM2     Year of manufacture     meter marking

 

Other cable identification requirements are available upon request

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Class 2
Conductor material
Copper class 2
Conductor shape
Circular
Number of conductors
5
Insulation
Micatape + XLPE
Outer sheath
Halogen free compound

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
25 mm²
Nominal insulation thickness
0.9 mm
Nominal outer sheath thickness
1.8 mm
Nominal overall diameter
26.0 mm
Approximate weight
1612 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV
Test voltage
3500 V
Max. DC resistance of the conductor at 20°C
0.727 Ohm/km

Usage characteristics

Usage characteristics

U.V resistance
Yes
Fire resistant
IEC 60331-21
Flame retardant
IEC 60332-1-2
Operating temperature, range
-25 ... 55 °C
Short-circuit max. conductor temperature
250 °C
Max. conductor temperature in service
90 °C
Installation temperature, range
-5 ... 50 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close