D(NYA) and E(NYA) FIRE RETARDANT

Products

D(NYA) 10 FR

Nexans ref. DNYA 000710 - Country ref. D(NYA) 10//FR

  • Conductor cross-section: 10 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal overall diameter: 5.7 mm
  • Approximate weight: 110 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km

 

D(NYA) 16 FR

Nexans ref. DNYA 000714 - Country ref. D(NYA) 16 FR

  • Conductor cross-section: 16 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal overall diameter: 6.7 mm
  • Approximate weight: 164 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km

 

D(NYA) 2.5 FR

Nexans ref. DNYA 000904 - Country ref. D(NYA) 2.5//FR

  • Conductor cross-section: 2.5 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal overall diameter: 3.3 mm
  • Approximate weight: 29 kg/km
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km

 

D(NYA) 25 FR

Nexans ref. DNYA 000718 - Country ref. D(NYA) 25//FR

  • Conductor cross-section: 25 mm²
  • Nominal insulation thickness: 1.2 mm
  • Nominal overall diameter: 8.3 mm
  • Approximate weight: 262 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km

 

D(NYA) 4 FR

Nexans ref. DNYA 000704 - Country ref. D(NYA) 4 FR

  • Conductor cross-section: 4 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal overall diameter: 4.0 mm
  • Approximate weight: 46 kg/km
  • Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km

 

E(NYA) 120 FR

Nexans ref. ENYA 000224 - Country ref. E(NYA) 120 FR

  • Conductor cross-section: 120 mm²
  • Nominal insulation thickness: 1.6 mm
  • Nominal overall diameter: 16.0 mm
  • Approximate weight: 1130 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km

 

E(NYA) 150 FR

Nexans ref. ENYA 001759 - Country ref. E(NYA) 150 FR

  • Conductor cross-section: 150 mm²
  • Nominal insulation thickness: 1.8 mm
  • Nominal overall diameter: 17.7 mm
  • Approximate weight: 1394 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km

 

E(NYA) 185 FR

Nexans ref. ENYA 000226 - Country ref. E(NYA) 240 FR

  • Conductor cross-section: 185 mm²
  • Nominal insulation thickness: 2.0 mm
  • Nominal overall diameter: 19.8 mm
  • Approximate weight: 1727 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km

 

E(NYA) 240 FR

Nexans ref. ENYA 000636 - Country ref. E(NYA) 240 FR

  • Conductor cross-section: 240 mm²
  • Nominal insulation thickness: 2.2 mm
  • Nominal overall diameter: 22.5 mm
  • Approximate weight: 2250 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km

 

E(NYA) 300 FR

Nexans ref. ENYA 000228 - Country ref. E(NYA) 300 FR

  • Conductor cross-section: 300 mm²
  • Nominal insulation thickness: 2.4 mm
  • Nominal overall diameter: 25.1 mm
  • Approximate weight: 2827 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km

 

E(NYA) 35 FR

Nexans ref. ENYA 000106 - Country ref. E(NYA) 35 FR

  • Conductor cross-section: 35 mm²
  • Nominal insulation thickness: 1.2 mm
  • Nominal overall diameter: 9.3 mm
  • Approximate weight: 346 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km

 

E(NYA) 50 FR

Nexans ref. ENYA 000200 - Country ref. E(NYA) 50 FR

  • Conductor cross-section: 50 mm²
  • Nominal insulation thickness: 1.4 mm
  • Nominal overall diameter: 11.0 mm
  • Approximate weight: 463 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km

 

E(NYA) 70 FR

Nexans ref. ENYA 000222 - Country ref. ENYA 70//FR

  • Conductor cross-section: 70 mm²
  • Nominal insulation thickness: 1.4 mm
  • Nominal overall diameter: 12.5 mm
  • Approximate weight: 660 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km

 

E(NYA) 95 FR

Nexans ref. ENYA 000223 - Country ref. E(NYA) 95 FR

  • Conductor cross-section: 95 mm²
  • Nominal insulation thickness: 1.6 mm
  • Nominal overall diameter: 14.5 mm
  • Approximate weight: 901 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km

 

Description

Description

Standards

  • International
    EN 50525-3-31; IEC 60227-3; IEC 60228; IEC 60332-1-2; IEC 60332-3
  • National
    DIN VDE 0250

 1-SCOPE

This specification covers single core, PVC insulated cables, intended for internal wiring in dry locations,concealed in conduits.

2.1-Conductor

Plain, annealed, electrolytic copper conductors, solid or stranded, complying with the applicable requirements of IEC 228.

2.2 - Insulation

PVC based thermoplastic material

2.3 - Marking

By ink jet printing on one line over the outer jacket

 

test at works Building wires FR

Routine Tests                                                              

 - Max. DC conductor resistance at 20°C acc. to IEC 60228

 - Spark test during insulation

                                                                       

Liban Cables will carry out these tests on all the length and tests certificates will be provided.                                                                  

                                                                       

Sample Tests

 -          Check of the build - up and color coding of the cable                                                      

 -          Check of dimensions                                                    

            Insulation          :           according to VDE 250  Table 6  Column 2                                  

                                                                       

                                                                       

These tests will be carried out on one length of each size during each inspection .

Tests certificates will be provided by Liban Cables                                                                      

 

Type Tests                                                                  

Mechanical characteristics on insulation  material (tensile strength and elongation at break) in accordance with VDE 250.

Fire retardance test according to IEC 60332-3

These tests will be carried out on one length of the order

Tests certificates will be provided by Liban Cables

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Circular
Number of conductors
1
Conductor flexibility
Stranded class 2
Insulation
PVC

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
1000 V

Usage characteristics

Usage characteristics

Installation temperature, range
-5 ... 50 °C
Maximum operating temperature
70 °C
Operating temperature, range
-15 ... 55 °C
Short-circuit max. conductor temperature
160 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close