H05V2-K

Products

H05V2K 0.75

Nexans ref. FH05V2K000701 - Country ref. FH05V2K 0.75

  • Conductor cross-section: 0.75 mm²
  • Nominal overall diameter: 2.3 mm
  • Approximate net weight: 11 kg/km
  • Max. DC resistance of the conductor at 20°C: 26 Ohm/km

 

H05V2K 1

Nexans ref. FH05V2K001151 - Country ref. FH05V2K 1

  • Conductor cross-section: 1 mm²
  • Nominal overall diameter: 2.4 mm
  • Approximate net weight: 13 kg/km
  • Max. DC resistance of the conductor at 20°C: 19.5 Ohm/km

 

Description

Description

Standards

  • Product
    BS EN 50525-2-31
  • Test
    IEC 60332-1-2

Construction:

1-Conductor

Plain, annealed, electrolytic copper conductors, stranded class 5

2 - Insulation

Heat resistant PVC based thermoplastic material

TEST AT WORKS TYPE H05V2-K ACCORDING TO BS EN 50525-2-31

Routine Tests

 -          Max. DC conductors resistance at 20°C acc. to EN 60228                                                           

Liban Cables will carry out these tests on all the length and tests certificates will be provided

                                                                       

Sample tests

 -          Check of the build - up and color coding of the cable

 -          Check of dimensions

            Insulation          :           according to BS 50525-2-31       parag. 5.2.1.3                           

                                                                                                   & Table B.4                              

 

These tests will be carried out on one length of each size during each inspection .

Tests certificates will be provided by Liban Cables

                                                                       

Type tests

Mechanical characteristics on insulation  material (tensile strength and elongation at break  ) in accordance with BS EN 50525-2-31

These tests will be carried out on one length of the order

Tests certificates will be provided by Liban Cables

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper class 5
Insulation
PVC

Dimensional characteristics

Dimensional characteristics

Nominal insulation thickness
0.6 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
300/500 V

Usage characteristics

Usage characteristics

Installation temperature, range
-5 ... 50 °C
Maximum operating temperature
90 °C
Operating temperature, range
-15 ... 55 °C
Short-circuit max. conductor temperature
160 °C

Resources

Resources

Find a Distributor

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close