AL, Unarmored, single core XLPE insulation, PVC sheathed

Products

EAX 1*1000

Nexans ref. EAX 000107 - Country ref. EAX 1*1000

  • Conductor cross-section: 1000 mm²
  • Nominal insulation thickness: 2.8 mm
  • Nominal outer sheath thickness: 2.4 mm
  • Nominal outer diameter: 52.0 mm
  • Approximate weight: 3659 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0291 Ohm/km
  • Permissible current rating in open air: 990 A
  • Permissible current rating when buried: 870 A
  • U.V resistance: -

 

EAX 1*120 NEW

Nexans ref. EAX 001074 - Country ref. EAX 1*120//UV

  • Conductor cross-section: 120 mm²
  • Nominal insulation thickness: 1.2 mm
  • Nominal outer sheath thickness: 1.5 mm
  • Nominal outer diameter: 18.0 mm
  • Approximate weight: 460 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
  • Permissible current rating in open air: 299 A
  • Permissible current rating when buried: 283 A
  • U.V resistance: Yes

 

EAX 1*120

Nexans ref. EAX 000074 - Country ref. EAX 1*120

  • Conductor cross-section: 120 mm²
  • Nominal insulation thickness: 1.2 mm
  • Nominal outer sheath thickness: 1.5 mm
  • Nominal outer diameter: 18.0 mm
  • Approximate weight: 460 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
  • Permissible current rating in open air: 299 A
  • Permissible current rating when buried: 283 A
  • U.V resistance:

 

EAX 1*150

Nexans ref. EAX 000080 - Country ref. EAX 1*150

  • Conductor cross-section: 150 mm²
  • Nominal insulation thickness: 1.4 mm
  • Nominal outer sheath thickness: 1.6 mm
  • Nominal outer diameter: 19.5 mm
  • Approximate weight: 556 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • Permissible current rating in open air: 344 A
  • Permissible current rating when buried: 316 A
  • U.V resistance: -

 

EAX 1*150 NEW

Nexans ref. EAX 001080 - Country ref. EAX 1*150//UV

  • Conductor cross-section: 150 mm²
  • Nominal insulation thickness: 1.4 mm
  • Nominal outer sheath thickness: 1.6 mm
  • Nominal outer diameter: 20.0 mm
  • Approximate weight: 552 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • Permissible current rating in open air: 344 A
  • Permissible current rating when buried: 316 A
  • U.V resistance: Yes

 

EAX 1*16

Nexans ref. EAX 000038 - Country ref. EAX 1*16

  • Conductor cross-section: 16 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal outer sheath thickness: 1.4 mm
  • Nominal outer diameter: 8.5 mm
  • Approximate weight: 94 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
  • Permissible current rating in open air: 83 A
  • Permissible current rating when buried: 91 A
  • U.V resistance:

 

EAX 1*185 NEW

Nexans ref. EAX 000185 - Country ref. EAX 1*185//UV

  • Conductor cross-section: 185 mm²
  • Nominal insulation thickness: 1.6 mm
  • Nominal outer sheath thickness: 1.6 mm
  • Nominal outer diameter: 22.0 mm
  • Approximate weight: 705 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • Permissible current rating in open air: 392 A
  • Permissible current rating when buried: 356 A
  • U.V resistance: Yes

 

EAX 1*185

Nexans ref. EAX 000085 - Country ref. EAX 1*185

  • Conductor cross-section: 185 mm²
  • Nominal insulation thickness: 1.6 mm
  • Nominal outer sheath thickness: 1.6 mm
  • Nominal outer diameter: 22.0 mm
  • Approximate weight: 705 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • Permissible current rating in open air: 392 A
  • Permissible current rating when buried: 356 A
  • U.V resistance:

 

EAX 1*240

Nexans ref. EAX 000090 - Country ref. EAX 1*240

  • Conductor cross-section: 240 mm²
  • Nominal insulation thickness: 1.7 mm
  • Nominal outer sheath thickness: 1.7 mm
  • Nominal outer diameter: 25.0 mm
  • Approximate weight: 874 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • Permissible current rating in open air: 461 A
  • Permissible current rating when buried: 413 A
  • U.V resistance: -

 

EAX 1*240 NEW

Nexans ref. EAX 001090 - Country ref. EAX 1*240//UV

  • Conductor cross-section: 240 mm²
  • Nominal insulation thickness: 1.7 mm
  • Nominal outer sheath thickness: 1.7 mm
  • Nominal outer diameter: 25.0 mm
  • Approximate weight: 868 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • Permissible current rating in open air: 461 A
  • Permissible current rating when buried: 413 A
  • U.V resistance: Yes

 

EAX 1*25

Nexans ref. EAX 000036 - Country ref. EAX 1*25

  • Conductor cross-section: 25 mm²
  • Nominal insulation thickness: 0.9 mm
  • Nominal outer sheath thickness: 1.4 mm
  • Nominal outer diameter: 10.0 mm
  • Approximate weight: 134 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.2 Ohm/km
  • Permissible current rating in open air: 111 A
  • Permissible current rating when buried: 115 A
  • U.V resistance:

 

EAX 1*300

Nexans ref. EAX 000093 - Country ref. EAX 1*300

  • Conductor cross-section: 300 mm²
  • Nominal insulation thickness: 1.8 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 27.0 mm
  • Approximate weight: 1079 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
  • Permissible current rating in open air: 525 A
  • Permissible current rating when buried: 468 A
  • U.V resistance: -

 

EAX 1*300

Nexans ref. EAX 000580 - Country ref. EAX 1*300//UV

  • Conductor cross-section: 300 mm²
  • Nominal insulation thickness: 1.8 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 27.0 mm
  • Approximate weight: 1079 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
  • Permissible current rating in open air: 525 A
  • Permissible current rating when buried: 468 A
  • U.V resistance: Yes

 

EAX 1*35

Nexans ref. EAX 000041 - Country ref. EAX 1*35

  • Conductor cross-section: 35 mm²
  • Nominal insulation thickness: 0.9 mm
  • Nominal outer sheath thickness: 1.4 mm
  • Nominal outer diameter: 11.5 mm
  • Approximate weight: 167 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.868 Ohm/km
  • Permissible current rating in open air: 138 A
  • Permissible current rating when buried: 140 A
  • U.V resistance:

 

EAX 1*400

Nexans ref. EAX 000098 - Country ref. EAX 1*400

  • Conductor cross-section: 400 mm²
  • Nominal insulation thickness: 2.0 mm
  • Nominal outer sheath thickness: 1.9 mm
  • Nominal outer diameter: 31.0 mm
  • Approximate weight: 1380 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
  • Permissible current rating in open air: 613 A
  • Permissible current rating when buried: 538 A
  • U.V resistance: -

 

EAX 1*400

Nexans ref. EAX 001098 - Country ref. EAX 1*400//UV

  • Conductor cross-section: 400 mm²
  • Nominal insulation thickness: 2.0 mm
  • Nominal outer sheath thickness: 1.9 mm
  • Nominal outer diameter: 31.0 mm
  • Approximate weight: 1380 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
  • Permissible current rating in open air: 613 A
  • Permissible current rating when buried: 538 A
  • U.V resistance: Yes

 

EAX 1*50

Nexans ref. EAX 000042 - Country ref. EAX 1*50

  • Conductor cross-section: 50 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal outer sheath thickness: 1.4 mm
  • Nominal outer diameter: 12.5 mm
  • Approximate weight: 214 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.641 Ohm/km
  • Permissible current rating in open air: 168 A
  • Permissible current rating when buried: 167 A
  • U.V resistance:

 

EAX 1*500

Nexans ref. EAX 000094 - Country ref. EAX 1*500

  • Conductor cross-section: 500 mm²
  • Nominal insulation thickness: 2.2 mm
  • Nominal outer sheath thickness: 2.0 mm
  • Nominal outer diameter: 34.0 mm
  • Approximate weight: 1719 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0605 Ohm/km
  • Permissible current rating in open air: 687 A
  • Permissible current rating when buried: 608 A
  • U.V resistance:

 

EAX 1*630

Nexans ref. EAX 000105 - Country ref. EAX 1*630

  • Conductor cross-section: 630 mm²
  • Nominal insulation thickness: 2.4 mm
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal outer diameter: 38.0 mm
  • Approximate weight: 2203 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0469 Ohm/km
  • Permissible current rating in open air: 782 A
  • Permissible current rating when buried: 686 A
  • U.V resistance: -

 

EAX 1*70 NEW

Nexans ref. EAX 001055 - Country ref. EAX 1*70//UV

  • Conductor cross-section: 70 mm²
  • Nominal insulation thickness: 1.1 mm
  • Nominal outer sheath thickness: 1.4 mm
  • Nominal outer diameter: 16.5 mm
  • Approximate weight: 284 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
  • Permissible current rating in open air: 213 A
  • Permissible current rating when buried: 206 A
  • U.V resistance: Yes

 

EAX 1*70

Nexans ref. EAX 000055 - Country ref. EAX 1*70

  • Conductor cross-section: 70 mm²
  • Nominal insulation thickness: 1.1 mm
  • Nominal outer sheath thickness: 1.4 mm
  • Nominal outer diameter: 16.5 mm
  • Approximate weight: 284 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
  • Permissible current rating in open air: 213 A
  • Permissible current rating when buried: 206 A
  • U.V resistance:

 

EAX 1*95

Nexans ref. EAX 000045 - Country ref. EAX 1*95

  • Conductor cross-section: 95 mm²
  • Nominal insulation thickness: 1.1 mm
  • Nominal outer sheath thickness: 1.5 mm
  • Nominal outer diameter: 16.5 mm
  • Approximate weight: 385 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
  • Permissible current rating in open air: 258 A
  • Permissible current rating when buried: 247 A
  • U.V resistance: -

 

EAX 1*95

Nexans ref. EAX 001045 - Country ref. EAX 1*95//UV

  • Conductor cross-section: 95 mm²
  • Nominal insulation thickness: 1.1 mm
  • Nominal outer sheath thickness: 1.5 mm
  • Nominal outer diameter: 16.5 mm
  • Approximate weight: 385 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
  • Permissible current rating in open air: 258 A
  • Permissible current rating when buried: 247 A
  • U.V resistance: Yes

 

Description

Description

Standards

  • International
    IEC 60228; IEC 60332-1-2; IEC 60502-1

1. SCOPE

This specification covers XLPE insulated, circular, single core unarmoured cables, rated at 0.6/1 KV according to IEC 60502-1 for use indoors, outdoors, and in cable ducts.

 

2. CONSTRUCTION

2.1 Conductor

Aluminum conductor, circular stranded, conforming to the applicable requirements of IEC 60228.

2.2 Insulation

XLPE material, conforming to the applicable requirements of IEC 60502-1.

2.3 Sheath

PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.

2.4 TESTS

Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products.

TEST AT WORKS unarmored single core

Routine Tests

 -  Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2

 -  Spark test during insulation                                                       

 Liban Cables will carry out these tests on all the length and tests certificates will be provided.                                                                  

                                                                       

Sample Tests                                                              

 -          Check of the build - up and color coding of the cable                                                      

 -          Check of dimensions                                                    

            Insulation          :           according to IEC 60502-1                       Parag.  16.5.2

            Oversheath       :           according to IEC 60502-1                       Parag.  16.5.3

                                                                       

These tests will be carried out on one length during  of each size during each inspection . 

Tests certificates will be provided by Liban Cables 

                                                                       

Type Tests                                                                  

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-1.

These tests will be carried out on one length of the order.

Tests certificates will be provided by Liban Cables

LV AL COND. UNARMORED

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Circular
Insulation
XLPE
Outer sheath
PVC

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Operating temperature, range
-15 ... 55 °C
Installation temperature, range
-5 ... 50 °C
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Flame retardant
IEC 60332-1-2

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close