Multicore (PN) SWA Armored, XLPE insulated, PVC sheathed

Products

EXR 2*120+50

Nexans ref. EXR 001834 - Country ref. EXR 2*120+50

  • Conductor shape: Circular
  • Number of conductors: 3
  • Conductor cross-section: 120 mm²
  • Nominal insulation thickness: 1.2 mm
  • Earth conductor cross section: 50 mm²
  • Insulation thickness of smaller conductor: 1.0 mm
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer diameter: 41.0 mm
  • Approximate weight: 4731 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.387 Ohm/km
  • Permissible current rating in open air: 339 A
  • Permissible current rating when buried: 345 A

 

EXR 2*120+70

Nexans ref. EXR 001832 - Country ref. EXR 2*120+70

  • Conductor shape: Circular
  • Number of conductors: 3
  • Conductor cross-section: 120 mm²
  • Nominal insulation thickness: 1.2 mm
  • Earth conductor cross section: 70 mm²
  • Insulation thickness of smaller conductor: 1.1 mm
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer diameter: 42.0 mm
  • Approximate weight: 4552 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.268 Ohm/km
  • Permissible current rating in open air: 339 A
  • Permissible current rating when buried: 345 A

 

EXR 2*16+10

Nexans ref. EXR 060100 - Country ref. EXR 2*16+10

  • Conductor shape: Circular
  • Number of conductors: 3
  • Conductor cross-section: 16 mm²
  • Nominal insulation thickness: 0.7 mm
  • Earth conductor cross section: 10 mm²
  • Insulation thickness of smaller conductor: 0.7 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal armour wire diameter: 1.25 mm
  • Nominal outer diameter: 20.0 mm
  • Approximate weight: 992 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Resistance of neutral conductor at 20ºC: 1.83 Ohm/km
  • Permissible current rating in open air: 96 A
  • Permissible current rating when buried: 111 A

 

EXR 2*25+16

Nexans ref. EXR 001971 - Country ref. EXR 2*25+16

  • Conductor shape: Circular
  • Number of conductors: 3
  • Conductor cross-section: 25 mm²
  • Nominal insulation thickness: 0.9 mm
  • Earth conductor cross section: 16 mm²
  • Insulation thickness of smaller conductor: 0.7 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer diameter: 24.0 mm
  • Approximate weight: 1477 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
  • Resistance of neutral conductor at 20ºC: 1.15 Ohm/km
  • Permissible current rating in open air: 127 A
  • Permissible current rating when buried: 141 A

 

EXR 2*35+25

Nexans ref. EXR 001837 - Country ref. EXR 2*35+25

  • Conductor shape: Circular
  • Number of conductors: 3
  • Conductor cross-section: 35 mm²
  • Nominal insulation thickness: 0.9 mm
  • Earth conductor cross section: 25 mm²
  • Insulation thickness of smaller conductor: 0.9 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer diameter: 27.0 mm
  • Approximate weight: 1874 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.727 Ohm/km
  • Permissible current rating in open air: 157 A
  • Permissible current rating when buried: 170 A

 

EXR 2*50+25

Nexans ref. EXR 001830 - Country ref. EXR 2*50+25

  • Conductor shape: Circular
  • Number of conductors: 3
  • Conductor cross-section: 50 mm²
  • Nominal insulation thickness: 1.0 mm
  • Earth conductor cross section: 25 mm²
  • Insulation thickness of smaller conductor: 0.9 mm
  • Nominal outer sheath thickness: 1.9 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer diameter: 29.0 mm
  • Approximate weight: 2052 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.727 Ohm/km
  • Permissible current rating in open air: 190 A
  • Permissible current rating when buried: 204 A

 

EXR 2*50+35

Nexans ref. EXR 060101 - Country ref. EXR 2*50+35

  • Conductor shape: Circular
  • Number of conductors: 3
  • Conductor cross-section: 50 mm²
  • Nominal insulation thickness: 1.0 mm
  • Earth conductor cross section: 35 mm²
  • Insulation thickness of smaller conductor: 0.9 mm
  • Nominal outer sheath thickness: 1.9 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer diameter: 29.5 mm
  • Approximate weight: 2375 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.524 Ohm/km
  • Permissible current rating in open air: 190 A
  • Permissible current rating when buried: 204 A

 

EXR 2*70+35

Nexans ref. EXR 001831 - Country ref. EXR 2*70+35

  • Conductor shape: Circular
  • Number of conductors: 3
  • Conductor cross-section: 70 mm²
  • Nominal insulation thickness: 1.1 mm
  • Earth conductor cross section: 35 mm²
  • Insulation thickness of smaller conductor: 0.9 mm
  • Nominal outer sheath thickness: 2.0 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer diameter: 34.0 mm
  • Approximate weight: 2908 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.524 Ohm/km
  • Permissible current rating in open air: 242 A
  • Permissible current rating when buried: 252 A

 

EXR 3*10+6

Nexans ref. EXR 004300 - Country ref. EXR 3*16+10

  • Conductor shape: Circular
  • Number of conductors: 4
  • Conductor cross-section: 10 mm²
  • Nominal insulation thickness: 0.7 mm
  • Earth conductor cross section: 6 mm²
  • Insulation thickness of smaller conductor: 0.7 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal armour wire diameter: 1.25 mm
  • Nominal outer diameter: 19.5 mm
  • Approximate weight: 899 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
  • Resistance of neutral conductor at 20ºC: 3.08 Ohm/km
  • Permissible current rating in open air: 71 A
  • Permissible current rating when buried: 88 A

 

EXR 3*120+70SM

Nexans ref. EXR 004392 - Country ref. EXR 3*120+70SM

  • Conductor shape: Shaped
  • Number of conductors: 4
  • Conductor cross-section: 120 mm²
  • Nominal insulation thickness: 1.4 mm
  • Earth conductor cross section: 70 mm²
  • Insulation thickness of smaller conductor: 1.2 mm
  • Nominal outer sheath thickness: 2.4 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer diameter: 43.0 mm
  • Approximate weight: 5767 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.268 Ohm/km
  • Permissible current rating in open air: 339 A
  • Permissible current rating when buried: 345 A

 

EXR 3*150+70SM

Nexans ref. EXR 004395 - Country ref. EXR 3*150+70SM

  • Conductor shape: Shaped
  • Number of conductors: 4
  • Conductor cross-section: 150 mm²
  • Nominal insulation thickness: 1.4 mm
  • Earth conductor cross section: 70 mm²
  • Insulation thickness of smaller conductor: 1.1 mm
  • Nominal outer sheath thickness: 2.5 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer diameter: 48.0 mm
  • Approximate weight: 7200 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.268 Ohm/km
  • Permissible current rating in open air: 390 A
  • Permissible current rating when buried: 386 A

 

EXR 3*150+95SM

Nexans ref. EXR 004415 - Country ref. EXR 3*150+95SM

  • Conductor shape: Shaped
  • Number of conductors: 4
  • Conductor cross-section: 150 mm²
  • Nominal insulation thickness: 1.4 mm
  • Earth conductor cross section: 95 mm²
  • Insulation thickness of smaller conductor: 1.1 mm
  • Nominal outer sheath thickness: 2.5 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer diameter: 49.0 mm
  • Approximate weight: 7481 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.193 Ohm/km
  • Permissible current rating in open air: 390 A
  • Permissible current rating when buried: 386 A

 

EXR 3*16+10

Nexans ref. EXR 004315 - Country ref. EXR 3*16+10

  • Conductor shape: Circular
  • Number of conductors: 4
  • Conductor cross-section: 16 mm²
  • Nominal insulation thickness: 0.7 mm
  • Earth conductor cross section: 10 mm²
  • Insulation thickness of smaller conductor: 0.7 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal armour wire diameter: 1.25 mm
  • Nominal outer diameter: 22.0 mm
  • Approximate weight: 1182 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Resistance of neutral conductor at 20ºC: 1.83 Ohm/km
  • Permissible current rating in open air: 96 A
  • Permissible current rating when buried: 111 A

 

EXR 3*185+95SM

Nexans ref. EXR 004445 - Country ref. EXR 3*185+95SM

  • Conductor shape: Shaped
  • Number of conductors: 4
  • Conductor cross-section: 185 mm²
  • Nominal insulation thickness: 1.6 mm
  • Earth conductor cross section: 95 mm²
  • Insulation thickness of smaller conductor: 1.1 mm
  • Nominal outer sheath thickness: 2.7 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer diameter: 53.0 mm
  • Approximate weight: 8784 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.193 Ohm/km
  • Permissible current rating in open air: 444 A
  • Permissible current rating when buried: 435 A

 

EXR 3*240+120 SM

Nexans ref. EXR 004455 - Country ref. EXR 3*240+120SM

  • Conductor shape: Shaped
  • Number of conductors: 4
  • Conductor cross-section: 240 mm²
  • Nominal insulation thickness: 1.7 mm
  • Earth conductor cross section: 120 mm²
  • Insulation thickness of smaller conductor: 1.2 mm
  • Nominal outer sheath thickness: 2.9 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer diameter: 59.0 mm
  • Approximate weight: 10965 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.153 Ohm/km
  • Permissible current rating in open air: 522 A
  • Permissible current rating when buried: 504 A

 

EXR 3*25+16

Nexans ref. EXR 004325 - Country ref. EXR 3*25+16

  • Conductor shape: Circular
  • Number of conductors: 4
  • Conductor cross-section: 25 mm²
  • Nominal insulation thickness: 0.9 mm
  • Earth conductor cross section: 16 mm²
  • Insulation thickness of smaller conductor: 0.7 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer diameter: 26.0 mm
  • Approximate weight: 1776 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
  • Resistance of neutral conductor at 20ºC: 1.15 Ohm/km
  • Permissible current rating in open air: 127 A
  • Permissible current rating when buried: 141 A

 

EXR 3*300+150SM NEW

Nexans ref. EXR 004475 - Country ref. EXR 3*300+150SM

  • Conductor shape: Shaped
  • Number of conductors: 4
  • Conductor cross-section: 300 mm²
  • Nominal insulation thickness: 1.8 mm
  • Earth conductor cross section: 150 mm²
  • Insulation thickness of smaller conductor: 1.4 mm
  • Nominal outer sheath thickness: 3.0 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer diameter: 64.0 mm
  • Approximate weight: 13357 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.124 Ohm/km
  • Permissible current rating in open air: 595 A
  • Permissible current rating when buried: 571 A

 

EXR 3*35+16

Nexans ref. EXR 003016 - Country ref. EXR 3*35+16

  • Conductor shape: Circular
  • Number of conductors: 4
  • Conductor cross-section: 35 mm²
  • Nominal insulation thickness: 0.9 mm
  • Earth conductor cross section: 16 mm²
  • Insulation thickness of smaller conductor: 0.7 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer diameter: 28.0 mm
  • Approximate weight: 2042 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Resistance of neutral conductor at 20ºC: 1.15 Ohm/km
  • Permissible current rating in open air: 157 A
  • Permissible current rating when buried: 170 A

 

EXR 3*50+25 NEW

Nexans ref. EXR 000788 - Country ref. EXR 3*50+25

  • Conductor shape: Circular
  • Number of conductors: 4
  • Conductor cross-section: 50 mm²
  • Nominal insulation thickness: 1.0 mm
  • Earth conductor cross section: 25 mm²
  • Insulation thickness of smaller conductor: 0.9 mm
  • Nominal outer sheath thickness: 1.9 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer diameter: 32.0 mm
  • Approximate weight: 2641 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.727 Ohm/km
  • Permissible current rating in open air: 190 A
  • Permissible current rating when buried: 204 A

 

EXR 3*70+35SM/RM

Nexans ref. EXR 005117 - Country ref. EXR 3*70+35SM/RM

  • Conductor shape: Shaped
  • Number of conductors: 4
  • Conductor cross-section: 70 mm²
  • Nominal insulation thickness: 1.1 mm
  • Earth conductor cross section: 35 mm²
  • Insulation thickness of smaller conductor: 0.9 mm
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer diameter: 35.0 mm
  • Approximate weight: 3623 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.524 Ohm/km
  • Permissible current rating in open air: 242 A
  • Permissible current rating when buried: 252 A

 

EXR 3*70+50SM/RM

Nexans ref. EXR 004368 - Country ref. EXR 3*70+50SM/RM

  • Conductor shape: Shaped
  • Number of conductors: 4
  • Conductor cross-section: 70 mm²
  • Nominal insulation thickness: 1.1 mm
  • Earth conductor cross section: 50 mm²
  • Insulation thickness of smaller conductor: 1.0 mm
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer diameter: 36.0 mm
  • Approximate weight: 3774 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.387 Ohm/km
  • Permissible current rating in open air: 242 A
  • Permissible current rating when buried: 252 A

 

EXR 3*95+50

Nexans ref. EXR 000209 - Country ref. EXR 3*95+50SM/RM

  • Conductor shape: Shaped
  • Number of conductors: 4
  • Conductor cross-section: 95 mm²
  • Nominal insulation thickness: 1.1 mm
  • Earth conductor cross section: 50 mm²
  • Insulation thickness of smaller conductor: 1.0 mm
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer diameter: 39.0 mm
  • Approximate weight: 4652 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.387 Ohm/km
  • Permissible current rating in open air: 293 A
  • Permissible current rating when buried: 302 A

 

EXR 4*120+70

Nexans ref. EXR 001531 - Country ref. EXR 4*120+70

  • Conductor shape: Circular
  • Number of conductors: 5
  • Conductor cross-section: 120 mm²
  • Nominal insulation thickness: 1.2 mm
  • Earth conductor cross section: 70 mm²
  • Insulation thickness of smaller conductor: 1.1 mm
  • Nominal outer sheath thickness: 2.5 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer diameter: 51.5 mm
  • Approximate weight: 7823 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.268 Ohm/km
  • Permissible current rating in open air: 339 A
  • Permissible current rating when buried: 345 A

 

EXR 4*150+70

Nexans ref. EXR 004095 - Country ref. EXR 4*150+70

  • Conductor shape: Circular
  • Number of conductors: 5
  • Conductor cross-section: 150 mm²
  • Nominal insulation thickness: 1.4 mm
  • Earth conductor cross section: 70 mm²
  • Insulation thickness of smaller conductor: 1.1 mm
  • Nominal outer sheath thickness: 2.7 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer diameter: 56.0 mm
  • Approximate weight: 9080 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.268 Ohm/km
  • Permissible current rating in open air: 390 A
  • Permissible current rating when buried: 386 A

 

EXR 4*150+95

Nexans ref. EXR 001135 - Country ref. EXR 4*150+95

  • Conductor shape: Circular
  • Number of conductors: 5
  • Conductor cross-section: 150 mm²
  • Nominal insulation thickness: 1.4 mm
  • Earth conductor cross section: 95 mm²
  • Insulation thickness of smaller conductor: 1.1 mm
  • Nominal outer sheath thickness: 2.7 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer diameter: 56.0 mm
  • Approximate weight: 9406 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.193 Ohm/km
  • Permissible current rating in open air: 390 A
  • Permissible current rating when buried: 386 A

 

EXR 4*16+10

Nexans ref. EXR 000970 - Country ref. EXR 4*16+10

  • Conductor shape: Circular
  • Number of conductors: 5
  • Conductor cross-section: 16 mm²
  • Nominal insulation thickness: 0.7 mm
  • Earth conductor cross section: 10 mm²
  • Insulation thickness of smaller conductor: 0.7 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer diameter: 24.0 mm
  • Approximate weight: 1495 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Resistance of neutral conductor at 20ºC: 1.83 Ohm/km
  • Permissible current rating in open air: 96 A
  • Permissible current rating when buried: 111 A

 

EXR 4*185+95

Nexans ref. EXR 001556 - Country ref. EXR 4*185+95

  • Conductor shape: Shaped
  • Number of conductors: 5
  • Conductor cross-section: 185 mm²
  • Nominal insulation thickness: 1.6 mm
  • Earth conductor cross section: 95 mm²
  • Insulation thickness of smaller conductor: 1.1 mm
  • Nominal outer sheath thickness: 2.9 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer diameter: 62.0 mm
  • Approximate weight: 11106 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.193 Ohm/km
  • Permissible current rating in open air: 444 A
  • Permissible current rating when buried: 435 A

 

EXR 4*240+120

Nexans ref. EXR 001569 - Country ref. EXR 4*240+120

  • Conductor shape: Circular
  • Number of conductors: 5
  • Conductor cross-section: 240 mm²
  • Nominal insulation thickness: 1.7 mm
  • Earth conductor cross section: 120 mm²
  • Insulation thickness of smaller conductor: 1.2 mm
  • Nominal outer sheath thickness: 3.1 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer diameter: 69.0 mm
  • Approximate weight: 13883 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.153 Ohm/km
  • Permissible current rating in open air: 522 A
  • Permissible current rating when buried: 504 A

 

EXR 4*25+16

Nexans ref. EXR 000971 - Country ref. EXR 4*25+16

  • Conductor shape: Circular
  • Number of conductors: 5
  • Conductor cross-section: 25 mm²
  • Nominal insulation thickness: 0.9 mm
  • Earth conductor cross section: 16 mm²
  • Insulation thickness of smaller conductor: 0.7 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer diameter: 28.0 mm
  • Approximate weight: 2056 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
  • Resistance of neutral conductor at 20ºC: 1.15 Ohm/km
  • Permissible current rating in open air: 127 A
  • Permissible current rating when buried: 141 A

 

EXR 4*35+16

Nexans ref. EXR 001838 - Country ref. EXR 4*35+16

  • Conductor shape: Circular
  • Number of conductors: 5
  • Conductor cross-section: 35 mm²
  • Nominal insulation thickness: 0.9 mm
  • Earth conductor cross section: 16 mm²
  • Insulation thickness of smaller conductor: 0.7 mm
  • Nominal outer sheath thickness: 1.9 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer diameter: 31.0 mm
  • Approximate weight: 2470 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Resistance of neutral conductor at 20ºC: 1.15 Ohm/km
  • Permissible current rating in open air: 157 A
  • Permissible current rating when buried: 170 A

 

EXR 4*35+25

Nexans ref. EXR 001839 - Country ref. EXR 4*35+25

  • Conductor shape: Circular
  • Number of conductors: 5
  • Conductor cross-section: 35 mm²
  • Nominal insulation thickness: 0.9 mm
  • Earth conductor cross section: 25 mm²
  • Insulation thickness of smaller conductor: 0.9 mm
  • Nominal outer sheath thickness: 1.9 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer diameter: 32.0 mm
  • Approximate weight: 2622 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.727 Ohm/km
  • Permissible current rating in open air: 157 A
  • Permissible current rating when buried: 170 A

 

EXR 4*50+25

Nexans ref. EXR 001840 - Country ref. EXR 4*50+25

  • Conductor shape: Circular
  • Number of conductors: 5
  • Conductor cross-section: 50 mm²
  • Nominal insulation thickness: 1.0 mm
  • Earth conductor cross section: 25 mm²
  • Insulation thickness of smaller conductor: 0.9 mm
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer diameter: 36.0 mm
  • Approximate weight: 3513 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.727 Ohm/km
  • Permissible current rating in open air: 190 A
  • Permissible current rating when buried: 204 A

 

EXR 4*50+35

Nexans ref. EXR 060102 - Country ref. EXR 4*50+35

  • Conductor shape: Circular
  • Number of conductors: 5
  • Conductor cross-section: 50 mm²
  • Nominal insulation thickness: 1.0 mm
  • Earth conductor cross section: 35 mm²
  • Insulation thickness of smaller conductor: 0.9 mm
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer diameter: 36.5 mm
  • Approximate weight: 3630 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.524 Ohm/km
  • Permissible current rating in open air: 190 A
  • Permissible current rating when buried: 204 A

 

EXR 4*70+35 NEW

Nexans ref. EXR 001842 - Country ref. EXR 4*70+35

  • Conductor shape: Circular
  • Number of conductors: 5
  • Conductor cross-section: 70 mm²
  • Nominal insulation thickness: 1.1 mm
  • Earth conductor cross section: 35 mm²
  • Insulation thickness of smaller conductor: 0.9 mm
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer diameter: 41.0 mm
  • Approximate weight: 4565 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.524 Ohm/km
  • Permissible current rating in open air: 242 A
  • Permissible current rating when buried: 252 A

 

EXR 4*70+50

Nexans ref. EXR 060103 - Country ref. EXR 4*70+50

  • Conductor shape: Circular
  • Number of conductors: 5
  • Conductor cross-section: 70 mm²
  • Nominal insulation thickness: 1.1 mm
  • Earth conductor cross section: 50 mm²
  • Insulation thickness of smaller conductor: 1.0 mm
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer diameter: 41.0 mm
  • Approximate weight: 4772 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.387 Ohm/km
  • Permissible current rating in open air: 242 A
  • Permissible current rating when buried: 252 A

 

EXR 4*95+50 NEW

Nexans ref. EXR 000967 - Country ref. EXR 4*95+50

  • Conductor shape: Circular
  • Number of conductors: 5
  • Conductor cross-section: 95 mm²
  • Nominal insulation thickness: 1.1 mm
  • Earth conductor cross section: 50 mm²
  • Insulation thickness of smaller conductor: 1.0 mm
  • Nominal outer sheath thickness: 2.4 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer diameter: 46.0 mm
  • Approximate weight: 5897 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
  • Resistance of neutral conductor at 20ºC: 0.387 Ohm/km
  • Permissible current rating in open air: 293 A
  • Permissible current rating when buried: 302 A

 

Description

Description

Standards

  • International
    IEC 60228; IEC 60332-1-2; IEC 60502-1

1. SCOPE

This specification covers XLPE insulated, circular or shaped, multicore armoured cables, rated at 0.6/1 KV according to IEC 60502-1 for use indoors, outdoors, in cable ducts and for direct burial underground, where severe mechanical stresses are present.

 

2. CONSTRUCTION

2.1 Phase Conductor

Plain, annealed electrolytic copper conductors, circular stranded, or sectoral stranded only for 3 Cores+Eath: sizes ≥70 to ≤300, conforming to the applicable requirements of IEC 60228.

2.2 Phase Conductor Insulation

XLPE thermosetting material, conforming to the applicable requirements of IEC 60502-1.

2.3 Neutral Conductor

Plain, annealed electrolytic copper conductors, circular stranded, or sectoral stranded only for 3 Cores+Eath: sizes ≥70 to ≤300, conforming to the applicable requirements of IEC 60228.

2.4 Neutral Conductor Insulation

XLPE thermosetting material, conforming to the applicable requirements of IEC 60502-1.

2.5 Assembly

Insulated conductors are laid up, filled where necessary with non-hygroscopic material and covered with an extruded thickness of thermoplastic material.

2.6 Armour

Galvanized Steel Wires Armor complying to the applicable requirements of IEC 60502-1.

2.7 Sheath

PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.

2.8 TESTS

Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products.

TEST AT WORKS according to IEC 60502-1 armored

 Routine Tests                                                              

- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2  

- Voltage test acc. to IEC 60502-1  parag. 15.1 & 15.3 

                                                                       

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided. 

                                                                       

Sample Tests                                                              

            - Check of the build - up and color coding of the cable 

            - Check of dimensions 

                        Insulation:         according to IEC 60502-1                       Parag.  16.5.2

                        Armour:             according to IEC 60502-1                       Parag.  16.7

                        Oversheath:      according to IEC 60502-1                       Parag.  16.5.3

                                                                       

These tests will be carried out on one length of each size during each inspection . 

Tests certificates will be provided by Liban Cables 

                                                                       

Type Tests                                                                  

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-1.  

These tests will be carried out on one length of the order . 

Tests certificates will be provided by Liban Cables

Cable identification - LV cables ≤ 1KV

INSULATION COLORS:   

 

Neutral

Cond.1

Cond.2

 Cond.3

Cond.4

1 Conductor

 

BLACK

 

 

 

2 Conductors

GREY

BLACK

 

 

 

3 Conductors

 

BLACK

RED

BLUE

 

4 Conductors

GREY

BLACK

RED

BLUE

 

5 Conductors

GREY

BLACK

RED

BLUE

GREEN

 

All numbered control cables (6 conductors and above), are insulated with white color, and numbered with black digits

 

CABLE MARKING OVER THE OUTER JACKET  (by inkjet printing):

LIBAN CABLES     DESCRIPTION     RATED VOLTAGE     SECTION MM2     Year of manufacture     meter marking

 

Other cable identification requirements are available upon request

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Class 2 IEC 60228
Conductor material
Copper
Insulation
XLPE
Armour type
Galvanized steel wires
Outer sheath
PVC

Electrical characteristics

Electrical characteristics

Thermal soil resistivity wet zone
1 °K.m/W
Test voltage
3500 V
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
10xD

Usage characteristics

Usage characteristics

Laying depth, center of system
600 mm
Operating temperature, range
-15 ... 55 °C
Installation temperature, range
-5 ... 50 °C
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Flame retardant
IEC 60332-1-2

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close