Flat Cable, PVC insulated PVC sheathed

Products

DYY 2*0.5 FLAT

Nexans ref. DYY 002005 - Country ref. DYY 2*0.5//FLAT-BS

  • Conductor cross-section: 0.5 mm²
  • Nominal insulation thickness: 0.6 mm
  • Nominal outer sheath thickness: 0.9 mm
  • Approximate weight: 40 kg/km
  • Max. DC resistance of the conductor at 20°C: 36 Ohm/km

 

DYY 2*1.5 FLAT

Nexans ref. DYY 000038 - Country ref. DYY 2*1.5//FLAT-BS

  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal outer sheath thickness: 0.9 mm
  • Approximate weight: 70 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km

 

DYY 2*2.5 FLAT

Nexans ref. DYY 000048 - Country ref. DYY 2*2.5//FLAT-BS

  • Conductor cross-section: 2.5 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer sheath thickness: 1.0 mm
  • Approximate weight: 102 kg/km
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km

 

DYY 2*4 FLAT

Nexans ref. DYY 000057 - Country ref. DYY 2*4//FLAT-BS

  • Conductor cross-section: 4 mm²
  • Nominal insulation thickness: 0.8 mm
  • Nominal outer sheath thickness: 1.0 mm
  • Approximate weight: 138 kg/km
  • Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km

 

Description

Description

Standards

  • International
    IEC 60332-1-2
  • National
    BS 6004

1 - CONSTRUCTION

2.1 - Conductor

Stranded annealed copper Class 2 acc. to IEC 60228.

2.2 - Insulation

PVC based thermoplastic material.

2.3 - Outer sheath

PVC based thermoplastic material.

TEST AT WORKS FOR DYY

Routine Tests

 -          Max. DC conductors resistance at 20°C acc. to BS 6004  parag.7.2

 -          Voltage test on insulation acc. to BS 6004 parag. 7.5

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided

                                                                       

Sample tests

            Check of the build - up and color coding of the cable                                                      

            Check of dimensions                                                    

            Insulation          :           according to BS 6004                 Parag.  6.2.3

            Oversheath       :           according to BS 6004                 Parag.  6.6.3

            Voltage test acc. To BS  6004  parag. 7.3                                                          

These tests will be carried out on one length of each size during each inspection .

Tests certificates will be provided by Liban Cables

                                                                       

Type tests

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break  ) in accordance with BS 6004                                                                

These tests will be carried out on one length of the order .

Tests certificates will be provided by Liban Cables

DRAWING DYY

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Class 2 IEC 60228
Conductor material
Copper
Conductor shape
Circular
Number of conductors
2
Core lay-up
Conductor flat laying
Insulation
PVC
Outer sheath
PVC

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
300/500 V
Test voltage
2 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
6xD

Usage characteristics

Usage characteristics

Max. conductor temperature in service
70 °C
Short-circuit max. conductor temperature
160 °C
Operating temperature, range
-15 ... 55 °C
Installation temperature, range
-5 ... 50 °C
Flame retardant
IEC 60332-1-2

Resources

Resources

Find a Distributor

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.