AL, Single core AWA Armored, PVC insulated, PVC sheathed

Products

EAYW 1*120

Nexans ref. EAYW 000254 - Country ref. EAYW 1*120

  • Conductor cross-section: 120 mm²
  • Nominal insulation thickness: 1.6 mm
  • Nominal armour wire diameter: 1.7 mm
  • Nominal outer sheath thickness: 1.7 mm
  • Nominal outer diameter: 24.0 mm
  • Approximate weight: 826 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
  • Permissible current rating in open air: 236 A
  • Permissible current rating when buried: 255 A

 

EAYW 1*16

Nexans ref. EAYW 001016 - Country ref. EAYW 1*16

  • Conductor cross-section: 16 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal armour wire diameter: 1.7 mm
  • Nominal outer sheath thickness: 1.4 mm
  • Nominal outer diameter: 14.0 mm
  • Approximate weight: 263 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
  • Permissible current rating in open air: 66 A
  • Permissible current rating when buried: 80 A

 

EAYW 1*25

Nexans ref. EAYW 001017 - Country ref. EAYW 1*25

  • Conductor cross-section: 25 mm²
  • Nominal insulation thickness: 1.2 mm
  • Nominal armour wire diameter: 1.7 mm
  • Nominal outer sheath thickness: 1.4 mm
  • Nominal outer diameter: 16.0 mm
  • Approximate weight: 333 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.2 Ohm/km
  • Permissible current rating in open air: 87 A
  • Permissible current rating when buried: 104 A

 

EAYW 1*300

Nexans ref. EAYW 001019 - Country ref. EAYW 1*300

  • Conductor cross-section: 300 mm²
  • Nominal insulation thickness: 2.4 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer sheath thickness: 2.0 mm
  • Nominal outer diameter: 34.0 mm
  • Approximate weight: 1720 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
  • Permissible current rating in open air: 410 A
  • Permissible current rating when buried: 421 A

 

EAYW 1*35

Nexans ref. EAYW 001018 - Country ref. EAYW 1*35

  • Conductor cross-section: 35 mm²
  • Nominal insulation thickness: 1.2 mm
  • Nominal armour wire diameter: 1.7 mm
  • Nominal outer sheath thickness: 1.5 mm
  • Nominal outer diameter: 17.0 mm
  • Approximate weight: 393 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.868 Ohm/km
  • Permissible current rating in open air: 108 A
  • Permissible current rating when buried: 126 A

 

Description

Description

Standards

  • International
    IEC 60228; IEC 60332-1-2; IEC 60502-1

1. SCOPE

This specification covers PVC insulated, circular, single core armoured cables, rated at 0.6/1 KV according to IEC 60502-1 for use indoors, outdoors, in cable ducts and for direct burial underground, where severe mechanical stresses are present.

 

2. CONSTRUCTION

2.1 Conductor

Aluminum conductors, circular stranded, conforming to the applicable requirements of IEC 60228.

2.2 Insulation

PVC based thermoplastic material,, conforming to the applicable requirements of IEC 60502-1.

2.3 Armour

Aluminum wires armoring complying to the applicable requirements of IEC 60502-1.

2.4 Sheath

PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.

2.5 TESTS

Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products.

Cable identification - LV cables ≤ 1KV

INSULATION COLORS:   

 

Neutral

Cond.1

Cond.2

 Cond.3

Cond.4

1 Conductor

 

BLACK

 

 

 

2 Conductors

GREY

BLACK

 

 

 

3 Conductors

 

BLACK

RED

BLUE

 

4 Conductors

GREY

BLACK

RED

BLUE

 

5 Conductors

GREY

BLACK

RED

BLUE

GREEN

 

All numbered control cables (6 conductors and above), are insulated with white color, and numbered with black digits

 

CABLE MARKING OVER THE OUTER JACKET  (by inkjet printing):

LIBAN CABLES     DESCRIPTION     RATED VOLTAGE     SECTION MM2     Year of manufacture     meter marking

 

Other cable identification requirements are available upon request

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Circular
Number of conductors
1
Insulation
PVC
Armour type
Aluminium Wire
Outer sheath
PVC

Electrical characteristics

Electrical characteristics

Test voltage
3500 V
Rated Voltage Uo/U (Um)
0,6/1 kV
Thermal soil resistivity wet zone
1 °K.m/W

Mechanical characteristics

Mechanical characteristics

Cable flexibility
10xD

Usage characteristics

Usage characteristics

Operating temperature, range
-15 ... 55 °C
Installation temperature, range
-5 ... 50 °C
Ambient air temperature
30 °C
Maximum operating temperature
70 °C
Short-circuit max. conductor temperature
160 °C
Flame retardant
IEC 60332-1-2
Laying depth, center of system
600 mm

Resources

Resources

Find a Distributor

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close