AL, Unarmored, multicore PVC insulation, PVC sheathed
AL, Unarmored, multicore PVC insulation, PVC sheathed
0.6 / 1 KV POWER CABLES Conforming to IEC 60502-1
Read moreEAYY 2*16
Nexans ref. EAYY 001112 - Country ref. EAYY 2*16
- Conductor shape: Circular
- Number of conductors: 2
- Conductor cross-section: 16 mm²
- Conductor diameter: 4.7 mm
- Nominal insulation thickness: 1.0 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 16.5 mm
- Maximum outer diameter: 17.66 mm
- Approximate weight: 344 kg/km
- Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
- Permissible current rating in open air: 59 A
- Permissible current rating when buried: 78 A
EAYY 2*25
Nexans ref. EAYY 001116 - Country ref. EAYY 2*25
- Conductor shape: Circular
- Number of conductors: 2
- Conductor cross-section: 25 mm²
- Conductor diameter: 5.9 mm
- Nominal insulation thickness: 1.2 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 20.0 mm
- Maximum outer diameter: 21.4 mm
- Approximate weight: 495 kg/km
- Max. DC resistance of the conductor at 20°C: 1.2 Ohm/km
- Permissible current rating in open air: 87 A
- Permissible current rating when buried: 114 A
EAYY 2*35
Nexans ref. EAYY 001117 - Country ref. EAYY 2*35
- Conductor shape: Circular
- Number of conductors: 2
- Conductor cross-section: 35 mm²
- Conductor diameter: 6.9 mm
- Nominal insulation thickness: 1.2 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 23.0 mm
- Maximum outer diameter: 24.61 mm
- Approximate weight: 620 kg/km
- Max. DC resistance of the conductor at 20°C: 0.868 Ohm/km
- Permissible current rating in open air: 108 A
- Permissible current rating when buried: 137 A
EAYY 3*120SM
Nexans ref. EAYY 003256 - Country ref. EAYY 3*120SM
- Conductor shape: Shaped
- Number of conductors: 3
- Conductor cross-section: 120 mm²
- Conductor diameter: 14.2 mm
- Nominal insulation thickness: 1.6 mm
- Nominal outer sheath thickness: 2.2 mm
- Nominal outer diameter: 36.0 mm
- Maximum outer diameter: 38.52 mm
- Approximate weight: 1625 kg/km
- Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
- Permissible current rating in open air: 210 A
- Permissible current rating when buried: 243 A
EAYY 3*16
Nexans ref. EAYY 003285 - Country ref. EAYY 3*16
- Conductor shape: Circular
- Number of conductors: 3
- Conductor cross-section: 16 mm²
- Conductor diameter: 4.7 mm
- Nominal insulation thickness: 1.0 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 18.0 mm
- Maximum outer diameter: 19.26 mm
- Approximate weight: 397 kg/km
- Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
- Permissible current rating in open air: 59 A
- Permissible current rating when buried: 78 A
EAYY 3*185SM
Nexans ref. EAYY 003261 - Country ref. EAYY 3*185SM
- Conductor shape: Shaped
- Number of conductors: 3
- Conductor cross-section: 185 mm²
- Conductor diameter: 17.7 mm
- Nominal insulation thickness: 2.0 mm
- Nominal outer sheath thickness: 2.5 mm
- Nominal outer diameter: 44.0 mm
- Maximum outer diameter: 47.08 mm
- Approximate weight: 2506 kg/km
- Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
- Permissible current rating in open air: 275 A
- Permissible current rating when buried: 306 A
EAYY 3*240SM
Nexans ref. EAYY 001443 - Country ref. EAYY 3*240SM
- Conductor shape: Shaped
- Number of conductors: 3
- Conductor cross-section: 240 mm²
- Conductor diameter: 20.0 mm
- Nominal insulation thickness: 2.2 mm
- Nominal outer sheath thickness: 2.7 mm
- Nominal outer diameter: 50.0 mm
- Maximum outer diameter: 60.99 mm
- Approximate weight: 3147 kg/km
- Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
- Permissible current rating in open air: 325 A
- Permissible current rating when buried: 354 A
EAYY 3*25 NEW
Nexans ref. EAYY 003248 - Country ref. EAYY 3*25
- Conductor shape: Circular
- Number of conductors: 3
- Conductor cross-section: 25 mm²
- Conductor diameter: 5.9 mm
- Nominal insulation thickness: 1.2 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 22.0 mm
- Maximum outer diameter: 23.54 mm
- Approximate weight: 577 kg/km
- Max. DC resistance of the conductor at 20°C: 1.2 Ohm/km
- Permissible current rating in open air: 79 A
- Permissible current rating when buried: 99 A
EAYY 3*35
Nexans ref. EAYY 003249 - Country ref. EAYY 3*35
- Conductor shape: Circular
- Number of conductors: 3
- Conductor cross-section: 35 mm²
- Conductor diameter: 6.9 mm
- Nominal insulation thickness: 1.2 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 24.0 mm
- Maximum outer diameter: 25.68 mm
- Approximate weight: 610 kg/km
- Max. DC resistance of the conductor at 20°C: 0.868 Ohm/km
- Permissible current rating in open air: 97 A
- Permissible current rating when buried: 119 A
EAYY 3*35//F
Nexans ref. EAYY 103248 - Country ref. EAYY 3*35//F
- Conductor shape: Circular
- Number of conductors: 3
- Conductor cross-section: 35 mm²
- Conductor diameter: 6.9 mm
- Nominal insulation thickness: 1.2 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 24.0 mm
- Maximum outer diameter: 25.68 mm
- Approximate weight: 744 kg/km
- Max. DC resistance of the conductor at 20°C: 0.868 Ohm/km
- Permissible current rating in open air: 97 A
- Permissible current rating when buried: 119 A
EAYY 3*50
Nexans ref. EAYY 013263 - Country ref. EAYY 3*50
- Conductor shape: Circular
- Number of conductors: 3
- Conductor cross-section: 50 mm²
- Conductor diameter: 8.1 mm
- Nominal insulation thickness: 1.4 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 27.0 mm
- Maximum outer diameter: 28.89 mm
- Approximate weight: 818 kg/km
- Max. DC resistance of the conductor at 20°C: 0.641 Ohm/km
- Permissible current rating in open air: 118 A
- Permissible current rating when buried: 144 A
EAYY 3*50//F
Nexans ref. EAYY 203248 - Country ref. EAYY 3*50//F
- Conductor shape: Circular
- Number of conductors: 3
- Conductor cross-section: 50 mm²
- Conductor diameter: 8.1 mm
- Nominal insulation thickness: 1.4 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 27.0 mm
- Maximum outer diameter: 28.89 mm
- Approximate weight: 986 kg/km
- Max. DC resistance of the conductor at 20°C: 0.641 Ohm/km
- Permissible current rating in open air: 118 A
- Permissible current rating when buried: 144 A
EAYY 3*70SM
Nexans ref. EAYY 003252 - Country ref. EAYY 3*70SM
- Conductor shape: Shaped
- Number of conductors: 3
- Conductor cross-section: 70 mm²
- Conductor diameter: 10.7 mm
- Nominal insulation thickness: 1.4 mm
- Nominal outer sheath thickness: 2.0 mm
- Nominal outer diameter: 29.0 mm
- Maximum outer diameter: 31.03 mm
- Approximate weight: 1005 kg/km
- Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
- Permissible current rating in open air: 150 A
- Permissible current rating when buried: 177 A
EAYY 3*95SM
Nexans ref. EAYY 003254 - Country ref. EAYY 3*95SM
- Conductor shape: Shaped
- Number of conductors: 3
- Conductor cross-section: 95 mm²
- Conductor diameter: 12.6 mm
- Nominal insulation thickness: 1.6 mm
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 33.0 mm
- Maximum outer diameter: 35.31 mm
- Approximate weight: 1351 kg/km
- Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
- Permissible current rating in open air: 181 A
- Permissible current rating when buried: 212 A
EAYY 4*120SM
Nexans ref. EAYY 003901 - Country ref. EAYY 4*120SM
- Conductor shape: Shaped
- Number of conductors: 4
- Conductor cross-section: 120 mm²
- Conductor diameter: 14.2 mm
- Nominal insulation thickness: 1.6 mm
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 41.0 mm
- Maximum outer diameter: 43.87 mm
- Approximate weight: 2163 kg/km
- Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
- Permissible current rating in open air: 210 A
- Permissible current rating when buried: 243 A
EAYY 4*120SM
Nexans ref. EAYY 003905 - Country ref. EAYY 4*120SM//EDL-SP
- Conductor shape: Shaped
- Number of conductors: 4
- Conductor cross-section: 120 mm²
- Conductor diameter: 14.2 mm
- Nominal insulation thickness: 1.6 mm
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 41.0 mm
- Maximum outer diameter: 43.87 mm
- Approximate weight: 2163 kg/km
- Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
- Permissible current rating in open air: 210 A
- Permissible current rating when buried: 243 A
EAYY 4*150SM
Nexans ref. EAYY 000010 - Country ref. EAYY 4*150SM
- Conductor shape: Shaped
- Number of conductors: 4
- Conductor cross-section: 150 mm²
- Conductor diameter: 15.8 mm
- Nominal insulation thickness: 1.8 mm
- Nominal outer sheath thickness: 2.5 mm
- Nominal outer diameter: 45.0 mm
- Maximum outer diameter: 48.15 mm
- Approximate weight: 2635 kg/km
- Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
- Permissible current rating in open air: 240 A
- Permissible current rating when buried: 271 A
EAYY 4*16
Nexans ref. EAYY 003301 - Country ref. EAYY 4*16
- Conductor shape: Circular
- Number of conductors: 4
- Conductor cross-section: 16 mm²
- Conductor diameter: 4.7 mm
- Nominal insulation thickness: 1.0 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 19.5 mm
- Maximum outer diameter: 20.86 mm
- Approximate weight: 476 kg/km
- Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
- Permissible current rating in open air: 59 A
- Permissible current rating when buried: 78 A
EAYY 4*185SM NEW
Nexans ref. EAYY 003272 - Country ref. EAYY 4*185SM
- Conductor shape: Shaped
- Number of conductors: 4
- Conductor cross-section: 185 mm²
- Conductor diameter: 17.7 mm
- Nominal insulation thickness: 2.0 mm
- Nominal outer sheath thickness: 2.7 mm
- Nominal outer diameter: 50.0 mm
- Maximum outer diameter: 53.5 mm
- Approximate weight: 3300 kg/km
- Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
- Permissible current rating in open air: 275 A
- Permissible current rating when buried: 306 A
EAYY 4*240SM
Nexans ref. EAYY 004201 - Country ref. EAYY 4*240SM
- Conductor shape: Shaped
- Number of conductors: 4
- Conductor cross-section: 240 mm²
- Conductor diameter: 20.0 mm
- Nominal insulation thickness: 2.2 mm
- Nominal outer sheath thickness: 2.9 mm
- Nominal outer diameter: 57.0 mm
- Maximum outer diameter: 60.99 mm
- Approximate weight: 4177 kg/km
- Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
- Permissible current rating in open air: 325 A
- Permissible current rating when buried: 354 A
EAYY 4*240SM
Nexans ref. EAYY 000505 - Country ref. EAYY 4*240SM//EDL-SP
- Conductor shape: Shaped
- Number of conductors: 4
- Conductor cross-section: 240 mm²
- Conductor diameter: 20.0 mm
- Nominal insulation thickness: 2.2 mm
- Nominal outer sheath thickness: 2.9 mm
- Nominal outer diameter: 57.0 mm
- Maximum outer diameter: 60.99 mm
- Approximate weight: 4177 kg/km
- Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
- Permissible current rating in open air: 325 A
- Permissible current rating when buried: 354 A
EAYY 4*25
Nexans ref. EAYY 003260 - Country ref. EAYY 4*25
- Conductor shape: Circular
- Number of conductors: 4
- Conductor cross-section: 25 mm²
- Conductor diameter: 5.9 mm
- Nominal insulation thickness: 1.2 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 24.0 mm
- Maximum outer diameter: 25.68 mm
- Approximate weight: 696 kg/km
- Max. DC resistance of the conductor at 20°C: 1.2 Ohm/km
- Permissible current rating in open air: 79 A
- Permissible current rating when buried: 99 A
EAYY 4*300SM
Nexans ref. EAYY...004301 - Country ref. EAYY 4*300SM
- Conductor shape: Shaped
- Number of conductors: 4
- Conductor cross-section: 300 mm²
- Conductor diameter: 22.4 mm
- Nominal insulation thickness: 2.4 mm
- Nominal outer sheath thickness: 3.1 mm
- Nominal outer diameter: 63.0 mm
- Maximum outer diameter: 67.41 mm
- Approximate weight: 5179 kg/km
- Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
- Permissible current rating in open air: 370 A
- Permissible current rating when buried: 401 A
EAYY 4*35
Nexans ref. EAYY 003263 - Country ref. EAYY 4*35
- Conductor shape: Circular
- Number of conductors: 4
- Conductor cross-section: 35 mm²
- Conductor diameter: 6.9 mm
- Nominal insulation thickness: 1.2 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 26.0 mm
- Maximum outer diameter: 27.82 mm
- Approximate weight: 779 kg/km
- Max. DC resistance of the conductor at 20°C: 0.868 Ohm/km
- Permissible current rating in open air: 97 A
- Permissible current rating when buried: 119 A
EAYY 4*400
Nexans ref. EAYY 003440 - Country ref. EAYY 4*400
- Conductor shape: Circular
- Number of conductors: 4
- Conductor cross-section: 400 mm²
- Conductor diameter: 23.2 mm
- Nominal insulation thickness: 2.6 mm
- Nominal outer sheath thickness: 3.4 mm
- Nominal outer diameter: 75.0 mm
- Maximum outer diameter: 32.1 mm
- Approximate weight: 6882 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
- Permissible current rating in open air: 432 A
- Permissible current rating when buried: 460 A
EAYY 4*50 NEW
Nexans ref. EAYY 003264 - Country ref. EAYY 4*50
- Conductor shape: Circular
- Number of conductors: 4
- Conductor cross-section: 50 mm²
- Conductor diameter: 8.1 mm
- Nominal insulation thickness: 1.4 mm
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 30.0 mm
- Maximum outer diameter: 32.1 mm
- Approximate weight: 1055 kg/km
- Max. DC resistance of the conductor at 20°C: 0.641 Ohm/km
- Permissible current rating in open air: 118 A
- Permissible current rating when buried: 144 A
EAYY 4*70SM
Nexans ref. EAYY 003701 - Country ref. EAYY 4*70SM
- Conductor shape: Shaped
- Number of conductors: 4
- Conductor cross-section: 70 mm²
- Conductor diameter: 10.7 mm
- Nominal insulation thickness: 1.4 mm
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 33.0 mm
- Maximum outer diameter: 35.31 mm
- Approximate weight: 1320 kg/km
- Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
- Permissible current rating in open air: 150 A
- Permissible current rating when buried: 177 A
EAYY 4*95SM
Nexans ref. EAYY 003801 - Country ref. EAYY 4*95SM
- Conductor shape: Shaped
- Number of conductors: 4
- Conductor cross-section: 95 mm²
- Conductor diameter: 12.6 mm
- Nominal insulation thickness: 1.6 mm
- Nominal outer sheath thickness: 2.2 mm
- Nominal outer diameter: 37.0 mm
- Maximum outer diameter: 39.59 mm
- Approximate weight: 1777 kg/km
- Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
- Permissible current rating in open air: 181 A
- Permissible current rating when buried: 212 A
EAYY 5*16
Nexans ref. EAYY 000547 - Country ref. EAYY 5*16
- Conductor shape: Circular
- Number of conductors: 5
- Conductor cross-section: 16 mm²
- Conductor diameter: 4.7 mm
- Nominal insulation thickness: 1.0 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 22.0 mm
- Maximum outer diameter: 23.54 mm
- Approximate weight: 515 kg/km
- Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
- Permissible current rating in open air: 59 A
- Permissible current rating when buried: 78 A
EAYY 5*25
Nexans ref. EAYY 000511 - Country ref. EAYY 5*25
- Conductor shape: Circular
- Number of conductors: 5
- Conductor cross-section: 25 mm²
- Conductor diameter: 5.9 mm
- Nominal insulation thickness: 1.2 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 26.0 mm
- Maximum outer diameter: 27.82 mm
- Approximate weight: 742 kg/km
- Max. DC resistance of the conductor at 20°C: 1.2 Ohm/km
- Permissible current rating in open air: 79 A
- Permissible current rating when buried: 99 A
EAYY 5*35
Nexans ref. EAYY 000560 - Country ref. EAYY 5*35
- Conductor shape: Circular
- Number of conductors: 5
- Conductor cross-section: 35 mm²
- Conductor diameter: 6.9 mm
- Nominal insulation thickness: 1.2 mm
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 29.0 mm
- Maximum outer diameter: 31.03 mm
- Approximate weight: 956 kg/km
- Max. DC resistance of the conductor at 20°C: 0.868 Ohm/km
- Permissible current rating in open air: 97 A
- Permissible current rating when buried: 119 A
Description
Description
Standards
-
InternationalIEC 60228; IEC 60332-1-2; IEC 60502-1
1. SCOPE
This specification covers PVC insulated, circular or shaped, multicore unarmoured cables, rated at 0.6/1 KV according to IEC 60502-1 for use indoors, outdoors, and in cable ducts.
2. CONSTRUCTION
2.1 Conductor
Aluminum conductors, circular stranded, or sectoral stranded, conforming to the applicable requirements of IEC 60228.
2.2 Insulation
PVC material, conforming to the applicable requirements of IEC 60502-1.
2.3 Assembly
Insulated conductors are laid up, filled where necessary with non-hygroscopic material.
2.4 Sheath
PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.
2.5 TESTS
Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products.
TEST AT WORKS unarmored multicore
Routine Tests
- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2
- Voltage test acc. to IEC 60502-1 parag. 15.1 & 15.3
Liban Cables will carry out these tests on all the lengths and tests certificates will be provided .
Sample Tests
- Check of the build - up and color coding of the cable
- Check of dimensions
Insulation : according to IEC 60502-1 Parag. 16.5.2
Oversheath : according to IEC 60502-1 Parag. 16.5.3
These tests will be carried out on one length of each size during each inspection .
Tests certificates will be provided by Liban Cables
Type Tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-1.
These tests will be carried out on one length of the order .
Tests certificates will be provided by Liban Cables
AL power LV cables PVC insulated PVC sheathed
Cable identification - LV cables ≤ 1KV
INSULATION COLORS:
|
Neutral |
Cond.1 |
Cond.2 |
Cond.3 |
Cond.4 |
1 Conductor |
|
BLACK |
|
|
|
2 Conductors |
GREY |
BLACK |
|
|
|
3 Conductors |
|
BLACK |
RED |
BLUE |
|
4 Conductors |
GREY |
BLACK |
RED |
BLUE |
|
5 Conductors |
GREY |
BLACK |
RED |
BLUE |
GREEN |
All numbered control cables (6 conductors and above), are insulated with white color, and numbered with black digits
CABLE MARKING OVER THE OUTER JACKET (by inkjet printing):
LIBAN CABLES DESCRIPTION RATED VOLTAGE SECTION MM2 Year of manufacture meter marking
Other cable identification requirements are available upon request
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania