YAKXS 0.6/1 KV

Products

YAKXS 3*185 0.6/1 KV

Nexans ref. EAX 003917 - Country ref. EAX 3*185SM//POL

  • Number of conductors: 3
  • Conductor cross-section: 185 mm²
  • Nominal insulation thickness: 1.6 mm
  • Nominal outer sheath thickness: 2.4 mm
  • Nominal outer diameter: 42.0 mm
  • Approximate weight: 2141 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • Permissible current rating in open air: 353 A
  • Permissible current rating when buried: 339 A

 

YAKXS 3*240 0.6/1 KV

Nexans ref. EAX 003918 - Country ref. EAX 3*240SM//POL

  • Number of conductors: 3
  • Conductor cross-section: 240 mm²
  • Nominal insulation thickness: 1.7 mm
  • Nominal outer sheath thickness: 2.6 mm
  • Nominal outer diameter: 47.0 mm
  • Approximate weight: 2685 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • Permissible current rating in open air: 415 A
  • Permissible current rating when buried: 393 A

 

YAKXS 3*300 0.6/1 KV

Nexans ref. EAX 003922 - Country ref. EAX 3*300SM//POL

  • Number of conductors: 3
  • Conductor cross-section: 300 mm²
  • Nominal insulation thickness: 1.8 mm
  • Nominal outer sheath thickness: 2.8 mm
  • Nominal outer diameter: 52.0 mm
  • Approximate weight: 3333 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
  • Permissible current rating in open air: 472 A
  • Permissible current rating when buried: 495 A

 

YAKXS 4*240 0.6/1 KV

Nexans ref. EAX 000712 - Country ref. EAX 4*240SM//POL

  • Number of conductors: 4
  • Conductor cross-section: 240 mm²
  • Nominal insulation thickness: 1.7 mm
  • Nominal outer sheath thickness: 2.8 mm
  • Nominal outer diameter: 54.0 mm
  • Approximate weight: 3565 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • Permissible current rating in open air: 415 A
  • Permissible current rating when buried: 393 A

 

Description

Description

Standards

  • International
    IEC 60228; IEC 60332-1-2; IEC 60502-1

1. SCOPE/ZAKRES

This specification covers XLPE insulated, circular or shaped, multicore unarmoured cables, rated at 0.6/1 KV according to IEC 60502-1 for use indoors, outdoors, and in cable ducts. / Niniejsza specyfikacja obejmuje kable z izolacją XLPE, o przekroju okrągłym lub kształtowym, wielożyłowe, nieuzbrojone, na napięcie znamionowe 0,6/1 KV zgodnie z normą IEC 60502-1, przeznaczone do pracy w pomieszczeniach zamkniętych, na zewnątrz i w kanałach kablowych.

 

2. CONSTRUCTION/BUDOWA

2.1 Conductor / żyła:

Aluminum conductors, circular stranded, or sectoral stranded, conforming to the applicable requirements of IEC 60228 / Przewody aluminiowe, o splotach okrągłych lub sektorowych, spełniające odpowiednie wymagania normy IEC 60228.

2.2 Insulation / Izolacja :

XLPE material, conforming to the applicable requirements of IEC 60502-1 / Materiał XLPE, zgodny z wymaganiami normy IEC 60502-1.

2.3 Assembly / Układ żył :

Insulated conductors are laid up, filled where necessary with non-hygroscopic material / Izolowane przewody, w razie potrzeby dodane wypełnienie z materiału niehigroskopijnego.

2.4 Sheath / Powłoka kablowa :

PVC LOW TEMPERATURE based thermoplastic material, conforming to the applicable requirements of IEC 60502-1 / Niskotemperaturowy materiał termoplastyczny na bazie PVC, zgodny z wymaganiami normy IEC 60502-1.

2.5 TESTS / TESTY : 

Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products / Zgodność z odpowiednimi wymaganiami normy IEC 60502-1 dotyczącej surowców lub wyrobów gotowych.

TEST AT WORKS YAKXS 0.6/1 KV

Routine Tests / Badania rutynowe:​                                                      

 - Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2 / Maks. rezystancja żyły prądu stałego w temperaturze 20°C zgodnie z IEC 60228 i IEC 60502-1 par. 15.1 & 15.2 

 - Voltage test acc. to IEC 60502-1  parag. 15.1 & 15.3 / Próba napięciowa wg IEC 60502-1 par. 15.1 & 15.3                                                 

                                                                       

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided  / Liban Cables(Grupa Nexans) przeprowadzi niniejsze próby dla wszystkich odcinków, a następnie wyda stosowne świadectwa z badań.

                                                                       

Sample tests / Badania próbek:                                                            

 - Check of the build - up and color coding of the cable / Kontrola struktury i oznaczenia kolorystycznego kabla

 - Check of dimensions / Kontrola wymiarów

                                                

            Insulation / Izolacja      :       according to IEC 60502-1 / zgodnie z IEC 60502-1          Parag./Par.  16.5.2

            Oversheath / Powłoka zewnętrzna   :      according to IEC 60502-1 zgodnie z IEC 60502-1            Parag. /Par. 16.5.3

 

These tests will be carried out on one length of each size during each inspection / Niniejsze próby zostaną przeprowadzane na jednym odcinku każdego rozmiaru podczas prowadzenia każdej kontroli.

Tests certificates will be provided by Liban Cables / Świadectwa z przeprowadzonych prób zostaną dostarczone przez Liban Cables(Grupa Nexans).

                                                                       

Type tests / Próby typu :                                                                 

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-1 / Charakterystyka mechaniczna izolacji i powłoki (wytrzymałość na rozciąganie i wydłużenie przy zerwaniu) zgodnie z normą IEC 60502-1.

These tests will be carried out on one length of the order / Próby zostaną wykonane na jednego odcinka z zamówienia.

Tests certificates will be provided by Liban Cables / Świadectwa z przeprowadzonych prób zostaną dostarczone przez Liban Cables(Grupa Nexans).

 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Shaped
Insulation
XLPE
Outer sheath
PVC
Conductor flexibility
Class 2 IEC 60228

Electrical characteristics

Electrical characteristics

Test voltage
3500 V
Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Operating temperature, range
-35 ... 55 °C
Installation temperature, range
-5 ... 50 °C
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Short-circuit max. conductor temperature
250 °C
Max. conductor temperature in service
90 °C
Flame retardant
IEC 60332-1-2

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close