Multicore SWA Armored, XLPE insulated, PVC sheathed UV resistant

Products

EXR 12*1.5 NEW

Nexans ref. EXR 005938 - Country ref. EXR 12*1.5//UV

  • Conductor shape: Circular
  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 0.8 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 15.0 mm
  • Approximate weight: 419 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 24 A
  • Permissible current rating when buried: 34 A

 

EXR 2*16 NEW

Nexans ref. EXR 010502 - Country ref. EXR 2*16//UV

  • Conductor shape: Circular
  • Conductor cross-section: 16 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 1.25 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 20.0 mm
  • Approximate weight: 882 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Permissible current rating in open air: 107 A
  • Permissible current rating when buried: 128 A

 

EXR 2*35 NEW

Nexans ref. EXR 010503 - Country ref. EXR 2*35//UV

  • Conductor shape: Circular
  • Conductor cross-section: 35 mm²
  • Nominal insulation thickness: 0.9 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 26.0 mm
  • Approximate weight: 1614 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Permissible current rating in open air: 175 A
  • Permissible current rating when buried: 195 A

 

EXR 2*4 NEW

Nexans ref. EXR 002187 - Country ref. EXR 2*4//UV

  • Conductor shape: Circular
  • Conductor cross-section: 4 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 0.8 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 14.0 mm
  • Approximate weight: 382 kg/km
  • Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
  • Permissible current rating in open air: 45 A
  • Permissible current rating when buried: 59 A

 

EXR 2*50 NEW

Nexans ref. EXR 010513 - Country ref. EXR 2*50//UV

  • Conductor shape: Circular
  • Conductor cross-section: 50 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 29.0 mm
  • Approximate weight: 2023 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Permissible current rating in open air: 212 A
  • Permissible current rating when buried: 235 A

 

EXR 2*6 NEW

Nexans ref. EXR 010501 - Country ref. EXR 2*6//UV

  • Conductor shape: Circular
  • Conductor cross-section: 6 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 0.8 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 15.5 mm
  • Approximate weight: 456 kg/km
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Permissible current rating in open air: 58 A
  • Permissible current rating when buried: 74 A

 

EXR 2*70 NEW

Nexans ref. EXR 010504 - Country ref. EXR 2*70//UV

  • Conductor shape: Circular
  • Conductor cross-section: 70 mm²
  • Nominal insulation thickness: 1.1 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer sheath thickness: 2.0 mm
  • Nominal outer diameter: 33.0 mm
  • Approximate weight: 2645 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Permissible current rating in open air: 270 A
  • Permissible current rating when buried: 290 A

 

EXR 2*95 NEW

Nexans ref. EXR 010505 - Country ref. EXR 2*95//UV

  • Conductor shape: Circular
  • Conductor cross-section: 95 mm²
  • Nominal insulation thickness: 1.1 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal outer diameter: 37.0 mm
  • Approximate weight: 3624 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
  • Permissible current rating in open air: 327 A
  • Permissible current rating when buried: 347 A

 

EXR 3*10 NEW

Nexans ref. EXR 010507 - Country ref. EXR 3*10//UV

  • Conductor shape: Circular
  • Conductor cross-section: 10 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 1.25 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 19.0 mm
  • Approximate weight: 805 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
  • Permissible current rating in open air: 71 A
  • Permissible current rating when buried: 88 A

 

EXR 3*120SM NEW

Nexans ref. EXR 010511 - Country ref. EXR 3*120SM//UV

  • Conductor shape: Shaped
  • Conductor cross-section: 120 mm²
  • Nominal insulation thickness: 1.2 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal outer diameter: 40.0 mm
  • Approximate weight: 4964 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
  • Permissible current rating in open air: 339 A
  • Permissible current rating when buried: 345 A

 

EXR 3*16 NEW

Nexans ref. EXR 005939 - Country ref. EXR 3*16//UV

  • Conductor shape: Circular
  • Conductor cross-section: 16 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 1.25 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 21.0 mm
  • Approximate weight: 1036 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Permissible current rating in open air: 96 A
  • Permissible current rating when buried: 111 A

 

EXR 3*2.5 NEW

Nexans ref. EXR 002188 - Country ref. EXR 3*2.5//UV

  • Conductor shape: Circular
  • Conductor cross-section: 2.5 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 0.8 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 14.0 mm
  • Approximate weight: 355 kg/km
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 30 A
  • Permissible current rating when buried: 40 A

 

EXR 3*25 NEW

Nexans ref. EXR 010508 - Country ref. EXR 3*25//UV

  • Conductor shape: Circular
  • Conductor cross-section: 25 mm²
  • Nominal insulation thickness: 0.9 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 25.0 mm
  • Approximate weight: 1578 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
  • Permissible current rating in open air: 127 A
  • Permissible current rating when buried: 141 A

 

EXR 3*35 NEW

Nexans ref.

  • Conductor shape: Circular
  • Conductor cross-section: 35 mm²
  • Nominal insulation thickness: 0.9 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 27.0 mm
  • Approximate weight: 1846 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Permissible current rating in open air: 157 A
  • Permissible current rating when buried: 170 A

 

EXR 3*4 NEW

Nexans ref. EXR 010506 - Country ref. EXR 3*4//UV

  • Conductor shape: Circular
  • Conductor cross-section: 4 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 0.8 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 15.0 mm
  • Approximate weight: 432 kg/km
  • Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
  • Permissible current rating in open air: 40 A
  • Permissible current rating when buried: 51 A

 

EXR 3*50 NEW

Nexans ref. EXR 010510 - Country ref. EXR 3*50//UV

  • Conductor shape: Circular
  • Conductor cross-section: 50 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer sheath thickness: 1.9 mm
  • Nominal outer diameter: 30.0 mm
  • Approximate weight: 2357 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Permissible current rating in open air: 190 A
  • Permissible current rating when buried: 204 A

 

EXR 3*6 NEW

Nexans ref. EXR 005930 - Country ref. EXR 3*6//UV

  • Conductor shape: Circular
  • Conductor cross-section: 6 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 0.8 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 16.0 mm
  • Approximate weight: 524 kg/km
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Permissible current rating in open air: 52 A
  • Permissible current rating when buried: 64 A

 

EXR 4*1.5 NEW

Nexans ref. EXR 005931 - Country ref. EXR 4*1.5//UV

  • Conductor shape: Circular
  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 0.8 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 13.5 mm
  • Approximate weight: 335 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 22 A
  • Permissible current rating when buried: 29 A

 

EXR 4*10 NEW

Nexans ref. EXR 002192 - Country ref. EXR 4*10//UV

  • Conductor shape: Circular
  • Conductor cross-section: 10 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 1.25 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 20.0 mm
  • Approximate weight: 946 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
  • Permissible current rating in open air: 71 A
  • Permissible current rating when buried: 88 A

 

EXR 4*120SM NEW

Nexans ref. EXR 001692 - Country ref. EXR 4*120SM//UV

  • Conductor shape: Shaped
  • Conductor cross-section: 120 mm²
  • Nominal insulation thickness: 1.2 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer sheath thickness: 2.5 mm
  • Nominal outer diameter: 47.0 mm
  • Approximate weight: 6795 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
  • Permissible current rating in open air: 339 A
  • Permissible current rating when buried: 345 A

 

EXR 4*150SM NEW

Nexans ref. EXR 005933 - Country ref. EXR 4*150SM//UV

  • Conductor shape: Shaped
  • Conductor cross-section: 150 mm²
  • Nominal insulation thickness: 1.4 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer sheath thickness: 2.6 mm
  • Nominal outer diameter: 51.0 mm
  • Approximate weight: 8085 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
  • Permissible current rating in open air: 390 A
  • Permissible current rating when buried: 386 A

 

EXR 4*16 NEW

Nexans ref. EXR 002193 - Country ref. EXR 4*16//UV

  • Conductor shape: Circular
  • Conductor cross-section: 16 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 23.0 mm
  • Approximate weight: 1346 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Permissible current rating in open air: 96 A
  • Permissible current rating when buried: 111 A

 

EXR 4*185SM

Nexans ref. EXR 003921 - Country ref. EXR 4*185SM

  • Conductor shape: Shaped
  • Conductor cross-section: 150 mm²
  • Nominal insulation thickness: 1.4 mm
  • Nominal armour wire diameter: 2.5 mm
  • Nominal outer sheath thickness: 2.6 mm
  • Nominal outer diameter: 51.0 mm
  • Approximate weight: 8085 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
  • Permissible current rating in open air: 390 A
  • Permissible current rating when buried: 386 A

 

EXR 4*2.5 NEW

Nexans ref. EXR 002189 - Country ref. EXR 4*2.5//UV

  • Conductor shape: Circular
  • Conductor cross-section: 2.5 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 0.8 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 15.0 mm
  • Approximate weight: 404 kg/km
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 30 A
  • Permissible current rating when buried: 40 A

 

EXR 4*25 NEW

Nexans ref. EXR 005932 - Country ref. EXR 4*25//UV

  • Conductor shape: Circular
  • Conductor cross-section: 25 mm²
  • Nominal insulation thickness: 0.9 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 27.0 mm
  • Approximate weight: 1880 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
  • Permissible current rating in open air: 127 A
  • Permissible current rating when buried: 141 A

 

EXR 4*35 NEW

Nexans ref.

  • Conductor shape: Circular
  • Conductor cross-section: 35 mm²
  • Nominal insulation thickness: 0.9 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer sheath thickness: 1.9 mm
  • Nominal outer diameter: 29.0 mm
  • Approximate weight: 2274 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Permissible current rating in open air: 157 A
  • Permissible current rating when buried: 170 A

 

EXR 4*4 NEW

Nexans ref. EXR 002190 - Country ref. EXR 4*4//UV

  • Conductor shape: Circular
  • Conductor cross-section: 4 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 0.8 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 16.0 mm
  • Approximate weight: 498 kg/km
  • Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
  • Permissible current rating in open air: 40 A
  • Permissible current rating when buried: 51 A

 

EXR 4*50 NEW

Nexans ref. EXR 010512 - Country ref. EXR 4*50//UV

  • Conductor shape: Circular
  • Conductor cross-section: 50 mm²
  • Nominal insulation thickness: 1.0 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer sheath thickness: 2.0 mm
  • Nominal outer diameter: 33.0 mm
  • Approximate weight: 2921 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Permissible current rating in open air: 190 A
  • Permissible current rating when buried: 204 A

 

EXR 4*6 NEW

Nexans ref. EXR 002191 - Country ref. EXR 4*6//UV

  • Conductor shape: Circular
  • Conductor cross-section: 6 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 1.25 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 18.0 mm
  • Approximate weight: 721 kg/km
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Permissible current rating in open air: 52 A
  • Permissible current rating when buried: 64 A

 

EXR 4*70SM NEW

Nexans ref. EXR 002181 - Country ref. EXR 4*70SM//UV

  • Conductor shape: Shaped
  • Conductor cross-section: 70 mm²
  • Nominal insulation thickness: 1.1 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal outer diameter: 37.0 mm
  • Approximate weight: 4021 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Permissible current rating in open air: 242 A
  • Permissible current rating when buried: 252 A

 

EXR 4*95SM NEW

Nexans ref. EXR 002194 - Country ref. EXR 4*95SM//UV

  • Conductor shape: Shaped
  • Conductor cross-section: 95 mm²
  • Nominal insulation thickness: 1.1 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal outer diameter: 41.0 mm
  • Approximate weight: 5159 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
  • Permissible current rating in open air: 293 A
  • Permissible current rating when buried: 302 A

 

EXR 5*25 NEW

Nexans ref. EXR 005935 - Country ref. EXR 5*25//UV

  • Conductor shape: Circular
  • Conductor cross-section: 25 mm²
  • Nominal insulation thickness: 0.9 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 29.0 mm
  • Approximate weight: 2130 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
  • Permissible current rating in open air: 127 A
  • Permissible current rating when buried: 141 A

 

EXR 5*35 NEW

Nexans ref. EXR 005936 - Country ref. EXR 5*35//UV

  • Conductor shape: Circular
  • Conductor cross-section: 35 mm²
  • Nominal insulation thickness: 0.9 mm
  • Nominal armour wire diameter: 1.6 mm
  • Nominal outer sheath thickness: 1.9 mm
  • Nominal outer diameter: 32.0 mm
  • Approximate weight: 2681 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Permissible current rating in open air: 157 A
  • Permissible current rating when buried: 170 A

 

EXR 5*4 NEW

Nexans ref. EXR 005934 - Country ref. EXR 5*4//UV

  • Conductor shape: Circular
  • Conductor cross-section: 4 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 1.25 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 18.0 mm
  • Approximate weight: 672 kg/km
  • Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
  • Permissible current rating in open air: 40 A
  • Permissible current rating when buried: 51 A

 

EXR 5*6 NEW

Nexans ref. EXR 005928 - Country ref. EXR 5*6//UV

  • Conductor shape: Circular
  • Conductor cross-section: 6 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 1.25 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 19.0 mm
  • Approximate weight: 819 kg/km
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Permissible current rating in open air: 52 A
  • Permissible current rating when buried: 64 A

 

EXR 7*1.5 NEW

Nexans ref. EXR 005937 - Country ref. EXR 7*1.5//UV

  • Conductor shape: Circular
  • Conductor cross-section: 1.5 mm²
  • Nominal insulation thickness: 0.7 mm
  • Nominal armour wire diameter: 0.8 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 15.0 mm
  • Approximate weight: 419 kg/km
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 24 A
  • Permissible current rating when buried: 34 A

 

Description

Description

Standards

  • International
    IEC 60228; IEC 60332-1-2; IEC 60502-1

1. SCOPE

This specification covers XLPE insulated, circular or shaped, multicore armoured cables, rated at 0.6/1 KV according to IEC 60502-1 for use indoors, outdoors, in cable ducts and for direct burial underground, where severe mechanical stresses are present.

 

2. CONSTRUCTION

2.1 Conductor

Plain, annealed electrolytic copper conductors, circular stranded, or sectoral stranded, conforming to the applicable requirements of IEC 60228.

2.2 Insulation

XLPE thermosetting material, conforming to the applicable requirements of IEC 60502-1.

2.3 Assembly

Insulated conductors are laid up, filled where necessary with non-hygroscopic material and covered with an extruded thickness of thermoplastic material.

2.4 Armour

Galvanized round wires completely covering the assembly of cores complying to the applicable requirements of IEC 60502-1.

2.5 Sheath

PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.

2.6 TESTS

Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products.

TEST AT WORKS according to IEC 60502-1 armored

 Routine Tests                                                              

- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2  

- Voltage test acc. to IEC 60502-1  parag. 15.1 & 15.3 

                                                                       

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided. 

                                                                       

Sample Tests                                                              

            - Check of the build - up and color coding of the cable 

            - Check of dimensions 

                        Insulation:         according to IEC 60502-1                       Parag.  16.5.2

                        Armour:             according to IEC 60502-1                       Parag.  16.7

                        Oversheath:      according to IEC 60502-1                       Parag.  16.5.3

                                                                       

These tests will be carried out on one length of each size during each inspection . 

Tests certificates will be provided by Liban Cables 

                                                                       

Type Tests                                                                  

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-1.  

These tests will be carried out on one length of the order . 

Tests certificates will be provided by Liban Cables

Drawing Circular Conductor

Drawing Shaped Conductors

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Class 2 IEC 60228
Conductor material
Copper
Insulation
XLPE
Armour type
Galvanized steel wires
Outer sheath
PVC

Electrical characteristics

Electrical characteristics

Test voltage
3500 V
Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Operating temperature, range
-15 ... 55 °C
Installation temperature, range
-5 ... 50 °C
Ambient air temperature
30 °C
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Flame retardant
IEC 60332-1-2
U.V resistance
Yes

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close