Multicore (PN) STA Armored, PVC insulated, PVC sheathed
Multicore (PN) STA Armored, PVC insulated, PVC sheathed
0.6 / 1 KV POWER CABLES Conforming to IEC 60502-1
Read moreEYG 3*120+2*70
Nexans ref. EYG 005004 - Country ref. EYG 3*120+2*70
- Conductor cross-section: 120 mm²
- Nominal insulation thickness: 1.6 mm
- Earth conductor cross section: 70 mm²
- Insulation thickness of smaller conductor: 1.4 mm
- Nominal outer sheath thickness: 2.4 mm
- Tape thickness: 0.5 mm
- Nominal outer diameter: 51.0 mm
- Approximate weight: 6334 kg/km
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.268 Ohm/km
- Permissible current rating in open air: 269 A
- Permissible current rating when buried: 311 A
EYG 3*120+70SM
Nexans ref. EYG 004531 - Country ref. EYG 3*120+70SM
- Conductor cross-section: 120 mm²
- Nominal insulation thickness: 1.6 mm
- Earth conductor cross section: 70 mm²
- Insulation thickness of smaller conductor: 1.4 mm
- Nominal outer sheath thickness: 2.3 mm
- Tape thickness: 0.5 mm
- Nominal outer diameter: 43.0 mm
- Approximate weight: 5395 kg/km
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.268 Ohm/km
- Permissible current rating in open air: 269 A
- Permissible current rating when buried: 311 A
EYG 3*150+2*70
Nexans ref. EYG 005005 - Country ref. EYG 3*150+2*70
- Conductor cross-section: 150 mm²
- Nominal insulation thickness: 1.8 mm
- Earth conductor cross section: 70 mm²
- Insulation thickness of smaller conductor: 1.4 mm
- Nominal outer sheath thickness: 2.6 mm
- Tape thickness: 0.5 mm
- Nominal outer diameter: 55.0 mm
- Approximate weight: 7330 kg/km
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.268 Ohm/km
- Permissible current rating in open air: 309 A
- Permissible current rating when buried: 348 A
EYG 3*150+70SM
Nexans ref. EYG 004551 - Country ref. EYG 3*150+70SM
- Conductor cross-section: 150 mm²
- Nominal insulation thickness: 1.8 mm
- Earth conductor cross section: 70 mm²
- Insulation thickness of smaller conductor: 1.4 mm
- Nominal outer sheath thickness: 2.5 mm
- Tape thickness: 0.5 mm
- Nominal outer diameter: 47.0 mm
- Approximate weight: 6364 kg/km
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.268 Ohm/km
- Permissible current rating in open air: 309 A
- Permissible current rating when buried: 348 A
EYG 3*185+2*95
Nexans ref. EYG 005006 - Country ref. EYG 3*185+2*95
- Conductor cross-section: 185 mm²
- Nominal insulation thickness: 2.0 mm
- Earth conductor cross section: 95 mm²
- Insulation thickness of smaller conductor: 1.6 mm
- Nominal outer sheath thickness: 2.7 mm
- Tape thickness: 0.5 mm
- Nominal outer diameter: 61.0 mm
- Approximate weight: 9121 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.193 Ohm/km
- Permissible current rating in open air: 353 A
- Permissible current rating when buried: 392 A
EYG 3*185+95SM
Nexans ref. EYG 004566 - Country ref. EYG 3*185+95SM
- Conductor cross-section: 185 mm²
- Nominal insulation thickness: 2.0 mm
- Earth conductor cross section: 95 mm²
- Insulation thickness of smaller conductor: 1.6 mm
- Nominal outer sheath thickness: 2.6 mm
- Tape thickness: 0.5 mm
- Nominal outer diameter: 52.0 mm
- Approximate weight: 7870 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.193 Ohm/km
- Permissible current rating in open air: 353 A
- Permissible current rating when buried: 392 A
EYG 3*240+120SM
Nexans ref. EYG 004571 - Country ref. EYG 3*240+120SM
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 2.2 mm
- Earth conductor cross section: 120 mm²
- Insulation thickness of smaller conductor: 1.6 mm
- Nominal outer sheath thickness: 2.8 mm
- Tape thickness: 0.5 mm
- Nominal outer diameter: 58.0 mm
- Approximate weight: 9984 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.153 Ohm/km
- Permissible current rating in open air: 414 A
- Permissible current rating when buried: 454 A
EYG 3*240+2*120
Nexans ref. EYG 005007 - Country ref. EYG 3*240+2*120
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 2.2 mm
- Earth conductor cross section: 120 mm²
- Insulation thickness of smaller conductor: 1.6 mm
- Nominal outer sheath thickness: 2.9 mm
- Tape thickness: 0.5 mm
- Nominal outer diameter: 68.0 mm
- Approximate weight: 11540 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.153 Ohm/km
- Permissible current rating in open air: 414 A
- Permissible current rating when buried: 454 A
EYG 3*25+16
Nexans ref. EYG 004229 - Country ref. EYG 3*25+16
- Conductor cross-section: 25 mm²
- Nominal insulation thickness: 1.2 mm
- Earth conductor cross section: 16 mm²
- Insulation thickness of smaller conductor: 1.0 mm
- Nominal outer sheath thickness: 1.8 mm
- Tape thickness: 0.2 mm
- Nominal outer diameter: 25.0 mm
- Approximate weight: 1494 kg/km
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Resistance of neutral conductor at 20ºC: 1.15 Ohm/km
- Permissible current rating in open air: 101 A
- Permissible current rating when buried: 127 A
EYG 3*25+2*16
Nexans ref. EYG 005000 - Country ref. EYG 3*25+2*16
- Conductor cross-section: 25 mm²
- Nominal insulation thickness: 1.2 mm
- Earth conductor cross section: 16 mm²
- Insulation thickness of smaller conductor: 1.0 mm
- Nominal outer sheath thickness: 1.8 mm
- Tape thickness: 0.2 mm
- Nominal outer diameter: 28.0 mm
- Approximate weight: 1711 kg/km
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Resistance of neutral conductor at 20ºC: 1.15 Ohm/km
- Permissible current rating in open air: 101 A
- Permissible current rating when buried: 127 A
EYG 3*400+240
Nexans ref. EYG 004300 - Country ref. EYG 3*400+240
- Conductor cross-section: 400 mm²
- Nominal insulation thickness: 2.6 mm
- Earth conductor cross section: 240 mm²
- Insulation thickness of smaller conductor: 2.2 mm
- Nominal outer sheath thickness: 3.3 mm
- Tape thickness: 0.5 mm
- Nominal outer diameter: 77.0 mm
- Approximate weight: 16383 kg/km
- Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.0754 Ohm/km
- Permissible current rating in open air: 551 A
- Permissible current rating when buried: 592 A
EYG 3*50+2*25
Nexans ref. EYG 005001 - Country ref. EYG 3*50+2*25
- Conductor cross-section: 50 mm²
- Nominal insulation thickness: 1.4 mm
- Earth conductor cross section: 25 mm²
- Insulation thickness of smaller conductor: 1.2 mm
- Nominal outer sheath thickness: 2.0 mm
- Tape thickness: 0.2 mm
- Nominal outer diameter: 35.0 mm
- Approximate weight: 2640 kg/km
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.727 Ohm/km
- Permissible current rating in open air: 151 A
- Permissible current rating when buried: 184 A
EYG 3*70+2*35
Nexans ref. EYG 005002 - Country ref. EYG 3*70+2*35
- Conductor cross-section: 70 mm²
- Nominal insulation thickness: 1.4 mm
- Earth conductor cross section: 35 mm²
- Insulation thickness of smaller conductor: 1.2 mm
- Nominal outer sheath thickness: 2.1 mm
- Tape thickness: 0.5 mm
- Nominal outer diameter: 40.0 mm
- Approximate weight: 3821 kg/km
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.524 Ohm/km
- Permissible current rating in open air: 192 A
- Permissible current rating when buried: 227 A
EYG 3*70+35SM/RM
Nexans ref. EYG 003735 - Country ref. EYG 3*70+35SM/RM
- Conductor cross-section: 70 mm²
- Nominal insulation thickness: 1.4 mm
- Earth conductor cross section: 35 mm²
- Insulation thickness of smaller conductor: 1.2 mm
- Nominal outer sheath thickness: 2.0 mm
- Tape thickness: 0.5 mm
- Nominal outer diameter: 34.0 mm
- Approximate weight: 2994 kg/km
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.524 Ohm/km
- Permissible current rating in open air: 192 A
- Permissible current rating when buried: 227 A
EYG 3*95+2*50
Nexans ref. EYG 005003 - Country ref. EYG 3*95+2*50
- Conductor cross-section: 95 mm²
- Nominal insulation thickness: 1.6 mm
- Earth conductor cross section: 50 mm²
- Insulation thickness of smaller conductor: 1.4 mm
- Nominal outer sheath thickness: 2.3 mm
- Tape thickness: 0.5 mm
- Nominal outer diameter: 46.0 mm
- Approximate weight: 5063 kg/km
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.387 Ohm/km
- Permissible current rating in open air: 232 A
- Permissible current rating when buried: 272 A
Description
Description
Standards
-
InternationalIEC 60228; IEC 60332-1-2; IEC 60502-1
1. SCOPE
This specification covers PVC insulated, circular or shaped, multicore armoured cables, rated at 0.6/1 KV according to IEC 60502-1 for use indoors, outdoors, in cable ducts and for direct burial underground, where severe mechanical stresses are present.
2. CONSTRUCTION
2.1 Phase Conductor
Plain, annealed electrolytic copper conductors, circular stranded, or sectoral stranded only for 3 Cores+Eath: sizes ≥70 to ≤300, conforming to the applicable requirements of IEC 60228.
2.2 Phase Conductor Insulation
PVC thermosetting material, conforming to the applicable requirements of IEC 60502-1.
2.3 Neutral Conductor
Plain, annealed electrolytic copper conductors, circular stranded, or sectoral stranded only for 3 Cores+Eath: sizes ≥70 to ≤300, conforming to the applicable requirements of IEC 60228.
2.4 Neutral Conductor Insulation
PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.
2.5 Assembly
Insulated conductors are laid up, filled where necessary with non-hygroscopic material and covered with an extruded thickness of thermoplastic material.
2.6 Armour
Galvanized Steel Tape Armor complying to the applicable requirements of IEC 60502-1.
2.7 Sheath
PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.
2.8 TESTS
Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products.
TEST AT WORKS according to IEC 60502-1 armored
Routine Tests
- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2
- Voltage test acc. to IEC 60502-1 parag. 15.1 & 15.3
Liban Cables will carry out these tests on all the lengths and tests certificates will be provided.
Sample Tests
- Check of the build - up and color coding of the cable
- Check of dimensions
Insulation: according to IEC 60502-1 Parag. 16.5.2
Armour: according to IEC 60502-1 Parag. 16.7
Oversheath: according to IEC 60502-1 Parag. 16.5.3
These tests will be carried out on one length of each size during each inspection .
Tests certificates will be provided by Liban Cables
Type Tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-1.
These tests will be carried out on one length of the order .
Tests certificates will be provided by Liban Cables
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics