Fire retardant, Single core AWA Armored, XLPE insulated, PVC sheathed

Products

EXW 1*120

Nexans ref. EXW 000633 - Country ref. EXW 1*120//FR

  • Conductor cross-section: 120 mm²
  • Nominal insulation thickness: 1.2 mm
  • Nominal armour wire diameter: 1.7 mm
  • Nominal outer sheath thickness: 1.7 mm
  • Nominal outer diameter: 24.0 mm
  • Approximate weight: 1475 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
  • Permissible current rating in open air: 379 A
  • Permissible current rating when buried: 363 A

 

EXW 1*150

Nexans ref. EXW 000751 - Country ref. EXW 1*150//FR

  • Conductor cross-section: 150 mm²
  • Nominal insulation thickness: 1.4 mm
  • Nominal armour wire diameter: 1.7 mm
  • Nominal outer sheath thickness: 1.7 mm
  • Nominal outer diameter: 25.0 mm
  • Approximate weight: 1767 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
  • Permissible current rating in open air: 435 A
  • Permissible current rating when buried: 405 A

 

EXW 1*185

Nexans ref. EXW 000757 - Country ref. EXW 1*185//FR

  • Conductor cross-section: 185 mm²
  • Nominal insulation thickness: 1.6 mm
  • Nominal armour wire diameter: 1.7 mm
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 28.0 mm
  • Approximate weight: 2145 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
  • Permissible current rating in open air: 496 A
  • Permissible current rating when buried: 457 A

 

EXW 1*240

Nexans ref. EXW 000124 - Country ref. EXW 1*240//FR

  • Conductor cross-section: 240 mm²
  • Nominal insulation thickness: 1.7 mm
  • Nominal armour wire diameter: 1.7 mm
  • Nominal outer sheath thickness: 1.9 mm
  • Nominal outer diameter: 30.0 mm
  • Approximate weight: 2715 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
  • Permissible current rating in open air: 584 A
  • Permissible current rating when buried: 529 A

 

EXW 1*35

Nexans ref. EXW 000513 - Country ref. EXW 1*35//FR

  • Conductor cross-section: 35 mm²
  • Nominal insulation thickness: 0.9 mm
  • Nominal armour wire diameter: 1.7 mm
  • Nominal outer sheath thickness: 1.4 mm
  • Nominal outer diameter: 16.0 mm
  • Approximate weight: 554 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Permissible current rating in open air: 175 A
  • Permissible current rating when buried: 179 A

 

EXW 1*400

Nexans ref. EXW 000269 - Country ref. EXW 1*400//FR

  • Conductor cross-section: 400 mm²
  • Nominal insulation thickness: 2.0 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal outer diameter: 37.0 mm
  • Approximate weight: 4266 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
  • Permissible current rating in open air: 779 A
  • Permissible current rating when buried: 690 A

 

EXW 1*630

Nexans ref. EXW 000695 - Country ref. EXW 1*630//FR

  • Conductor cross-section: 630 mm²
  • Nominal insulation thickness: 2.4 mm
  • Nominal armour wire diameter: 2 mm
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal outer diameter: 45.0 mm
  • Approximate weight: 6826 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0283 Ohm/km
  • Permissible current rating in open air: 995 A
  • Permissible current rating when buried: 880 A

 

EXW 1*70

Nexans ref. EXW 000613 - Country ref. EXW 1*70//FR

  • Conductor cross-section: 70 mm²
  • Nominal insulation thickness: 1.1 mm
  • Nominal armour wire diameter: 1.7 mm
  • Nominal outer sheath thickness: 1.6 mm
  • Nominal outer diameter: 19.5 mm
  • Approximate weight: 933 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Permissible current rating in open air: 270 A
  • Permissible current rating when buried: 264 A

 

EXW 1*95

Nexans ref. EXW 000617 - Country ref. EXW 1*95//FR

  • Conductor cross-section: 95 mm²
  • Nominal insulation thickness: 1.1 mm
  • Nominal armour wire diameter: 1.7 mm
  • Nominal outer sheath thickness: 1.6 mm
  • Nominal outer diameter: 21.0 mm
  • Approximate weight: 1200 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
  • Permissible current rating in open air: 327 A
  • Permissible current rating when buried: 317 A

 

Description

Description

Standards

  • International
    IEC 60228; IEC 60332-1-2; IEC 60332-3; IEC 60502-1

1. SCOPE

This specification covers XLPE insulated, circular, single core armoured cables, rated at 0.6/1 KV according to IEC 60502-1 for use indoors, outdoors, in cable ducts and for direct burial underground, where severe mechanical stresses are present.

 

2. CONSTRUCTION

2.1 Conductor

Plain, annealed electrolytic copper conductors, circular stranded, conforming to the applicable requirements of IEC 60228.

2.2 Insulation

XLPE thermosetting material, conforming to the applicable requirements of IEC 60502-1.

2.3 Inner Sheath

Special fire retardant PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.

2.4 Armour

Aluminum wires completely covering the assembly of cores complying to the applicable requirements of IEC 60502-1.

2.5 Sheath

Special fire retardant PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.

2.6 TESTS

Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products.

TEST AT WORKS ACCORDING TO IEC 60502-1 & IEC 60332-3

Routine Tests

 -          Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2

 -          Voltage test acc. to IEC 60502-1  parag.15.1& 15.3

 

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided.                                                                

 

Sample Tests

 -          Check of the build - up and color coding of the cable

 -          Check of dimensions

            Insulation          :           according to IEC 60502-1                      Parag.  16.5.2

            Armour             :           according to IEC 60502-1                       Parag.  16.7

            Oversheath       :           according to IEC 60502-1                      Parag.  16.5.3

 Hot Set Test for XLPE insulation: according to IEC 60502-1                 Parag.  16.9

 

These tests will be carried out on one length of each size during each inspection .

Tests certificates will be provided by Liban Cables

 

Type Tests

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break ) in accordance with IEC 60502-1.

Fire retardance test according to IEC 60332-3.

These tests will be carried out on one length of the order.

Tests certificates will be provided by Liban Cables.

DRAWING SINGLE CORE, AWA ARMORED CABLE

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Circular
Insulation
XLPE
Armour type
Aluminium Wire
Outer sheath
PVC

Electrical characteristics

Electrical characteristics

Test voltage
3500 V
Rated Voltage Uo/U (Um)
0,6/1 kV
Thermal soil resistivity wet zone
1 °K.m/W

Mechanical characteristics

Mechanical characteristics

Cable flexibility
10xD

Usage characteristics

Usage characteristics

Laying depth, center of system
600 mm
Operating temperature, range
-15 ... 55 °C
Installation temperature, range
-5 ... 50 °C
Ambient air temperature
30 °C
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Flame retardant
IEC 60332-1-2
Fire retardant
IEC 60332-3

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close