XHAKXS 1*120/16 18/30KV
XHAKXS 1*120/16 18/30KV
XLPE Unarmored cable with Aluminum conductor
Read more- Nexans ref. : M6A4P 100805
- Country ref. : M6A4P 1*120/16(FL)//POL-1
Description
Description
Standards
-
ProductIEC 60228; IEC 60502-2
Application
Power use outdoor application, even wet.
Suitable for fixed installations at open air, in tube or canals and underground.
Max. Operation temperature: 90°
Max. Short circuit temperature : 250° (Max 5 s)
Construction
AL/SC/XLPE/SC/SC TAPE/CU WIRES/PE
1. Conductor: Compacted Round conductor class 2
2. Insulation: Extruded inner semi conductive layer, XLPE insulation and extruded outer semi conductive layer + semi conductive tape
3. Metallic screen layer: Copper wires with open helix copper tape
4. Outer sheath: PE, Black or as per customer requirement
7. Marking: By Inkjet
8. Packing: Drums can be wooden or steel
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Conductor flexibility
Stranded class 2
Conductor shape
Round compacted
Material of the inner semi-conductor
Semi-conducting compound
Insulation
XLPE
Material of the external semi-conductor
Extruded fully bonded
Concentric conductor
Copper wires and helical copper tape
Outer sheath
PE
Sheath colour
Black
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
120 mm²
Conductor diameter
12.8 mm
Nominal insulation thickness
8.0 mm
Screen section
16 mm²
Nominal outer sheath thickness
2.1 mm
Nominal outer diameter
37.0 mm
Approximate net weight
1215 kg/km
Electrical characteristics
Electrical characteristics
Test voltage
63 kV
Rated Voltage Uo/U (Um)
18 / 30 (36) kV
Frequence
50 Hz
Perm current rating in air 30°C
324 A
Permissible current rating when buried
252 A
Max. DC resistance of the conductor at 20°C
0.253 Ohm/km
A.C. Conductor resist. 50Hz and at 90 °C
0.323 Ohm/km
Permissible short circuit current conductor 1s
11.6 kA
Thermal soil resistivity wet zone
1.5 °K.m/W
Mechanical characteristics
Mechanical characteristics
Cable flexibility
10xD
Mechanical resistance to impacts
Good
Usage characteristics
Usage characteristics
Bending factor when laying
20 (xD)
Laying depth, center of system
800 mm
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum operating temperature
-35 °C