XRUHAKXS 18/30KV

Products

XRUHAKXS 1*1000/25 18/30KV

Nexans ref. M6A4DP 000502 - Country ref. M6A4DP 1*1000/25(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Circular non compacted
  • Conductor cross-section: 1000 mm²
  • Conductor diameter: 41.6 mm
  • Screen section: 25 mm²
  • Nominal outer sheath thickness: 3.0 mm
  • Nominal outer diameter: 70.0 mm
  • Approximate net weight: 5173 kg/km
  • Perm current rating in air 30°C: 1251 A
  • Permissible current rating when buried: 781 A
  • Max. DC resistance of the conductor at 20°C: 0.0291 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.04 Ohm/km
  • Permissible short circuit current conductor 1s: 95 kA
  • Permissible short circuit current screen 1s: 3.57 kA

 

XRUHAKXS 1*1000/50 18/30KV

Nexans ref. M6A4DP 000500 - Country ref. M6A4DP 1*1000/50(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Circular non compacted
  • Conductor cross-section: 1000 mm²
  • Conductor diameter: 41.6 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 3.0 mm
  • Nominal outer diameter: 72.0 mm
  • Approximate net weight: 5560 kg/km
  • Perm current rating in air 30°C: 1251 A
  • Permissible current rating when buried: 781 A
  • Max. DC resistance of the conductor at 20°C: 0.0291 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.04 Ohm/km
  • Permissible short circuit current conductor 1s: 95 kA
  • Permissible short circuit current screen 1s: 7.14 kA

 

XRUHAKXS 1*1000/50 18/30KV

Nexans ref. M6A4DP 001103 - Country ref. M6A4DP 1*1000/50(FL)//POL-3

  • Packaging: Cut to length (m)
  • Conductor shape: Circular non compacted
  • Conductor cross-section: 1000 mm²
  • Conductor diameter: 41.6 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 3.0 mm
  • Nominal outer diameter: 72.0 mm
  • Approximate net weight: 5560 kg/km
  • Perm current rating in air 30°C: 1251 A
  • Permissible current rating when buried: 781 A
  • Max. DC resistance of the conductor at 20°C: 0.0291 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.04 Ohm/km
  • Permissible short circuit current conductor 1s: 95 kA
  • Permissible short circuit current screen 1s: 7.14 kA

 

XRUHAKXS 1*1200/50 18/30KV

Nexans ref. M6A4DP 000501 - Country ref. M6A4DP 1*1200/50(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Circular non compacted
  • Conductor cross-section: 1200 mm²
  • Conductor diameter: 46.77 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 3.1 mm
  • Nominal outer diameter: 76.0 mm
  • Approximate net weight: 6435 kg/km
  • Perm current rating in air 30°C: 1375 A
  • Permissible current rating when buried: 841 A
  • Max. DC resistance of the conductor at 20°C: 0.0247 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0368 Ohm/km
  • Permissible short circuit current conductor 1s: 114.4 kA
  • Permissible short circuit current screen 1s: 7.14 kA

 

XRUHAKXS 1*400/16 18/30KV

Nexans ref. M6A4DP 000802 - Country ref. M6A4DP 1*400/16(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 400 mm²
  • Conductor diameter: 23.2 mm
  • Screen section: 16 mm²
  • Nominal outer sheath thickness: 2.5 mm
  • Nominal outer diameter: 49.0 mm
  • Approximate net weight: 2442 kg/km
  • Perm current rating in air 30°C: 673 A
  • Permissible current rating when buried: 470 A
  • Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0997 Ohm/km
  • Permissible short circuit current conductor 1s: 38.3 kA
  • Permissible short circuit current screen 1s: 2.28 kA

 

XRUHAKXS 1*400/25 18/30KV

Nexans ref. M6A4DP 000852 - Country ref. M6A4DP 1*400/25(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 400 mm²
  • Conductor diameter: 23.2 mm
  • Screen section: 25 mm²
  • Nominal outer sheath thickness: 2.5 mm
  • Nominal outer diameter: 49.0 mm
  • Approximate net weight: 2526 kg/km
  • Perm current rating in air 30°C: 673 A
  • Permissible current rating when buried: 470 A
  • Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0997 Ohm/km
  • Permissible short circuit current conductor 1s: 38.3 kA
  • Permissible short circuit current screen 1s: 3.7 kA

 

XRUHAKXS 1*400/35 18/30KV

Nexans ref. M6A4DP 000124 - Country ref. M6A4DP 1*400/35(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 400 mm²
  • Conductor diameter: 23.2 mm
  • Screen section: 35 mm²
  • Nominal outer sheath thickness: 2.5 mm
  • Nominal outer diameter: 49.0 mm
  • Approximate net weight: 2626 kg/km
  • Perm current rating in air 30°C: 673 A
  • Permissible current rating when buried: 470 A
  • Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0997 Ohm/km
  • Permissible short circuit current conductor 1s: 38.3 kA
  • Permissible short circuit current screen 1s: 5.15 kA

 

XRUHAKXS 1*400/50 18/30KV

Nexans ref. M6A4DP 000132 - Country ref. M6A4DP 1*400/50(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 400 mm²
  • Conductor diameter: 23.2 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 2.5 mm
  • Nominal outer diameter: 50.0 mm
  • Approximate net weight: 2765 kg/km
  • Perm current rating in air 30°C: 673 A
  • Permissible current rating when buried: 470 A
  • Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.1 Ohm/km
  • Permissible short circuit current conductor 1s: 38.3 kA
  • Permissible short circuit current screen 1s: 7.15 kA

 

XRUHAKXS 1*120/16 18/30KV

Nexans ref. M6A4DP 000805 - Country ref. XRUHAKXS 1*120/16

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 120 mm²
  • Conductor diameter: 12.8 mm
  • Screen section: 16 mm²
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal outer diameter: 37.0 mm
  • Approximate net weight: 1286 kg/km
  • Perm current rating in air 30°C: 324 A
  • Permissible current rating when buried: 252 A
  • Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.323 Ohm/km
  • Permissible short circuit current conductor 1s: 11.6 kA
  • Permissible short circuit current screen 1s: 2.28 kA

 

XRUHAKXS 1*120/25 18/30KV

Nexans ref. M6A4DP 000122 - Country ref. M6A4DP 1*120/25(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 120 mm²
  • Conductor diameter: 12.8 mm
  • Screen section: 25 mm²
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal outer diameter: 37.0 mm
  • Approximate net weight: 1362 kg/km
  • Perm current rating in air 30°C: 324 A
  • Permissible current rating when buried: 252 A
  • Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.323 Ohm/km
  • Permissible short circuit current conductor 1s: 11.6 kA
  • Permissible short circuit current screen 1s: 3.7 kA

 

XRUHAKXS 1*120/35 18/30KV

Nexans ref. M6A4DP 000863 - Country ref. M6A4DP 1*120/35(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 120 mm²
  • Conductor diameter: 12.8 mm
  • Screen section: 35 mm²
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal outer diameter: 38.0 mm
  • Approximate net weight: 1474 kg/km
  • Perm current rating in air 30°C: 324 A
  • Permissible current rating when buried: 252 A
  • Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.323 Ohm/km
  • Permissible short circuit current conductor 1s: 11.6 kA
  • Permissible short circuit current screen 1s: 5.0 kA

 

XRUHAKXS 1*120/50 18/30KV NEW

Nexans ref. M6A4DP 001742 - Country ref. M6A4DP 1*120/50(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 120 mm²
  • Conductor diameter: 12.8 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal outer diameter: 38.0 mm
  • Approximate net weight: 1614 kg/km
  • Perm current rating in air 30°C: 324 A
  • Permissible current rating when buried: 252 A
  • Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.323 Ohm/km
  • Permissible short circuit current conductor 1s: 11.6 kA
  • Permissible short circuit current screen 1s: 7.15 kA

 

XRUHAKXS 1*120/70 18/30KV

Nexans ref. M6A4DP 001743 - Country ref. M6A4DP 1*120/70(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 120 mm²
  • Conductor diameter: 12.8 mm
  • Screen section: 70 mm²
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal outer diameter: 39.0 mm
  • Approximate net weight: 1800 kg/km
  • Perm current rating in air 30°C: 324 A
  • Permissible current rating when buried: 252 A
  • Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.323 Ohm/km
  • Permissible short circuit current conductor 1s: 11.6 kA
  • Permissible short circuit current screen 1s: 10.3 kA

 

XRUHAKXS 1*150/120 18/30KV

Nexans ref. M6A4DP 001130 - Country ref. M6A4DP 1*150/120(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 150 mm²
  • Conductor diameter: 14.4 mm
  • Screen section: 120 mm²
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal outer diameter: 41.0 mm
  • Approximate net weight: 2437 kg/km
  • Perm current rating in air 30°C: 368 A
  • Permissible current rating when buried: 281 A
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.264 Ohm/km
  • Permissible short circuit current conductor 1s: 14.5 kA
  • Permissible short circuit current screen 1s: 17.8 kA

 

XRUHAKXS 1*150/16 18/30KV

Nexans ref. M6A4DP 000814 - Country ref. M6A4DP 1*150/16(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 150 mm²
  • Conductor diameter: 14.4 mm
  • Screen section: 16 mm²
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal outer diameter: 39.0 mm
  • Approximate net weight: 1414 kg/km
  • Perm current rating in air 30°C: 368 A
  • Permissible current rating when buried: 281 A
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.264 Ohm/km
  • Permissible short circuit current conductor 1s: 14.5 kA
  • Permissible short circuit current screen 1s: 2.28 kA

 

XRUHAKXS 1*150/25 18/30KV

Nexans ref. M6A4DP 021130 - Country ref. M6A4DP 1*150/25(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 150 mm²
  • Conductor diameter: 14.4 mm
  • Screen section: 25 mm²
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal outer diameter: 39.0 mm
  • Approximate net weight: 1500 kg/km
  • Perm current rating in air 30°C: 368 A
  • Permissible current rating when buried: 281 A
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.264 Ohm/km
  • Permissible short circuit current conductor 1s: 14.5 kA
  • Permissible short circuit current screen 1s: 3.7 kA

 

XRUHAKXS 1*150/35 18/30KV

Nexans ref. M6A4DP 000401 - Country ref. M6A4DP 1*150/35(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 150 mm²
  • Conductor diameter: 14.4 mm
  • Screen section: 35 mm²
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal outer diameter: 39.0 mm
  • Approximate net weight: 1598 kg/km
  • Perm current rating in air 30°C: 368 A
  • Permissible current rating when buried: 281 A
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.264 Ohm/km
  • Permissible short circuit current conductor 1s: 14.5 kA
  • Permissible short circuit current screen 1s: 5.0 kA

 

XRUHAKXS 1*150/50 18/30KV NEW

Nexans ref. M6A4DP 000130 - Country ref. M6A4DP 1*150/50(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 150 mm²
  • Conductor diameter: 14.4 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal outer diameter: 40.0 mm
  • Approximate net weight: 1737 kg/km
  • Perm current rating in air 30°C: 368 A
  • Permissible current rating when buried: 281 A
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.264 Ohm/km
  • Permissible short circuit current conductor 1s: 14.5 kA
  • Permissible short circuit current screen 1s: 7.15 kA

 

XRUHAKXS 1*150/70 18/30KV

Nexans ref. M6A4DP 002130 - Country ref. M6A4DP 1*150/70(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 150 mm²
  • Conductor diameter: 14.4 mm
  • Screen section: 70 mm²
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal outer diameter: 40.0 mm
  • Approximate net weight: 1925 kg/km
  • Perm current rating in air 30°C: 368 A
  • Permissible current rating when buried: 281 A
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.264 Ohm/km
  • Permissible short circuit current conductor 1s: 14.5 kA
  • Permissible short circuit current screen 1s: 10.3 kA

 

XRUHAKXS 1*185/100 18/30KV

Nexans ref. M6A4DP 000121 - Country ref. M6A4DP 1*185/100(FL)//POL-1

  • Packaging: Drum (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 185 mm²
  • Conductor diameter: 16.2 mm
  • Screen section: 100 mm²
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal outer diameter: 43.0 mm
  • Approximate net weight: 2411 kg/km
  • Perm current rating in air 30°C: 424 A
  • Permissible current rating when buried: 317 A
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.21 Ohm/km
  • Permissible short circuit current conductor 1s: 17.9 kA
  • Permissible short circuit current screen 1s: 14.85 kA

 

XRUHAKXS 1*185/16 18/30KV

Nexans ref. M6A4DP 000813 - Country ref. M6A4DP 1*185/16(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 185 mm²
  • Conductor diameter: 16.2 mm
  • Screen section: 16 mm²
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal outer diameter: 41.0 mm
  • Approximate net weight: 1589 kg/km
  • Perm current rating in air 30°C: 424 A
  • Permissible current rating when buried: 317 A
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.21 Ohm/km
  • Permissible short circuit current conductor 1s: 17.9 kA
  • Permissible short circuit current screen 1s: 2.28 kA

 

XRUHAKXS 1*185/25 18/30KV

Nexans ref. M6A4DP 021129 - Country ref. M6A4DP 1*185/25(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 185 mm²
  • Conductor diameter: 16.2 mm
  • Screen section: 25 mm²
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal outer diameter: 41.0 mm
  • Approximate net weight: 1686 kg/km
  • Perm current rating in air 30°C: 424 A
  • Permissible current rating when buried: 317 A
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.21 Ohm/km
  • Permissible short circuit current conductor 1s: 17.9 kA
  • Permissible short circuit current screen 1s: 3.7 kA

 

XRUHAKXS 1*185/35 18/30KV

Nexans ref. M6A4DP 000400 - Country ref. M6A4DP 1*185/35(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 185 mm²
  • Conductor diameter: 16.2 mm
  • Screen section: 35 mm²
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal outer diameter: 42.0 mm
  • Approximate net weight: 1785 kg/km
  • Perm current rating in air 30°C: 424 A
  • Permissible current rating when buried: 317 A
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.21 Ohm/km
  • Permissible short circuit current conductor 1s: 17.9 kA
  • Permissible short circuit current screen 1s: - kA

 

XRUHAKXS 1*185/50 18/30KV NEW

Nexans ref. M6A4DP 000129 - Country ref. M6A4DP 1*185/50(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 185 mm²
  • Conductor diameter: 16.2 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal outer diameter: 42.0 mm
  • Approximate net weight: 1924 kg/km
  • Perm current rating in air 30°C: 424 A
  • Permissible current rating when buried: 317 A
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.21 Ohm/km
  • Permissible short circuit current conductor 1s: 17.9 kA
  • Permissible short circuit current screen 1s: 7.15 kA

 

XRUHAKXS 1*185/70 18/30KV

Nexans ref. M6A4DP 002129 - Country ref. M6A4DP 1*185/70(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 185 mm²
  • Conductor diameter: 16.2 mm
  • Screen section: 70 mm²
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal outer diameter: 42.0 mm
  • Approximate net weight: 2112 kg/km
  • Perm current rating in air 30°C: 424 A
  • Permissible current rating when buried: 317 A
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.21 Ohm/km
  • Permissible short circuit current conductor 1s: 17.9 kA
  • Permissible short circuit current screen 1s: 10.3 kA

 

XRUHAKXS 1*240/16 18/30KV

Nexans ref. M6A4DP 000804 - Country ref. M6A4DP 1*240/16(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 17.9 mm
  • Screen section: 16 mm²
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal outer diameter: 43.0 mm
  • Approximate net weight: 1786 kg/km
  • Perm current rating in air 30°C: 502 A
  • Permissible current rating when buried: 367 A
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
  • Permissible short circuit current conductor 1s: 23.1 kA
  • Permissible short circuit current screen 1s: 2.28 kA

 

XRUHAKXS 1*240/25 18/30KV

Nexans ref. M6A4DP 000123 - Country ref. M6A4DP 1*240/25(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 17.9 mm
  • Screen section: 25 mm²
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal outer diameter: 43.0 mm
  • Approximate net weight: 1871 kg/km
  • Perm current rating in air 30°C: 502 A
  • Permissible current rating when buried: 367 A
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
  • Permissible short circuit current conductor 1s: 23.1 kA
  • Permissible short circuit current screen 1s: 3.7 kA

 

XRUHAKXS 1*240/35 18/30KV

Nexans ref. M6A4DP 000141 - Country ref. M6A4DP 1*240/35(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 17.9 mm
  • Screen section: 35 mm²
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal outer diameter: 43.0 mm
  • Approximate net weight: 1970 kg/km
  • Perm current rating in air 30°C: 502 A
  • Permissible current rating when buried: 367 A
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
  • Permissible short circuit current conductor 1s: 23.1 kA
  • Permissible short circuit current screen 1s: 5.0 kA

 

XRUHAKXS 1*240/50 18/30KV NEW

Nexans ref. M6A4DP 000131 - Country ref. M6A4DP 1*240/50(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 17.9 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal outer diameter: 44.0 mm
  • Approximate net weight: 2122 kg/km
  • Perm current rating in air 30°C: 502 A
  • Permissible current rating when buried: 367 A
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
  • Permissible short circuit current conductor 1s: 23.1 kA
  • Permissible short circuit current screen 1s: 7.15 kA

 

XRUHAKXS 1*240/70 18/30KV

Nexans ref. M6A4DP 001131 - Country ref. M6A4DP 1*240/70(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 17.9 mm
  • Screen section: 70 mm²
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal outer diameter: 44.0 mm
  • Approximate net weight: 2295 kg/km
  • Perm current rating in air 30°C: 502 A
  • Permissible current rating when buried: 367 A
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
  • Permissible short circuit current conductor 1s: 23.1 kA
  • Permissible short circuit current screen 1s: 10.3 kA

 

XRUHAKXS 1*300/100 18/30KV

Nexans ref. M6A4DP 000133 - Country ref. M6A4DP 1*300/100(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 300 mm²
  • Conductor diameter: 20.3 mm
  • Screen section: 100 mm²
  • Nominal outer sheath thickness: 2.4 mm
  • Nominal outer diameter: 47.0 mm
  • Approximate net weight: 2860 kg/km
  • Perm current rating in air 30°C: 577 A
  • Permissible current rating when buried: 414 A
  • Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.129 Ohm/km
  • Permissible short circuit current conductor 1s: 28.9 kA
  • Permissible short circuit current screen 1s: 14.85 kA

 

XRUHAKXS 1*300/16 18/30KV

Nexans ref. M6A4DP 000803 - Country ref. M6A4DP 1*300/16(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 300 mm²
  • Conductor diameter: 20.3 mm
  • Screen section: 16 mm²
  • Nominal outer sheath thickness: 2.4 mm
  • Nominal outer diameter: 45.0 mm
  • Approximate net weight: 2050 kg/km
  • Perm current rating in air 30°C: 577 A
  • Permissible current rating when buried: 414 A
  • Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.129 Ohm/km
  • Permissible short circuit current conductor 1s: 28.8 kA
  • Permissible short circuit current screen 1s: 2.28 kA

 

XRUHAKXS 1*300/25 18/30KV

Nexans ref. M6A4DP 021137 - Country ref. M6A4DP 1*300/25(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 300 mm²
  • Conductor diameter: 20.3 mm
  • Screen section: 25 mm²
  • Nominal outer sheath thickness: 2.4 mm
  • Nominal outer diameter: 45.0 mm
  • Approximate net weight: 2134 kg/km
  • Perm current rating in air 30°C: 577 A
  • Permissible current rating when buried: 414 A
  • Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.129 Ohm/km
  • Permissible short circuit current conductor 1s: 28.8 kA
  • Permissible short circuit current screen 1s: 3.7 kA

 

XRUHAKXS 1*300/35 18/30KV

Nexans ref. M6A4DP 000861 - Country ref. M6A4DP 1*300/35(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 300 mm²
  • Conductor diameter: 20.3 mm
  • Screen section: 35 mm²
  • Nominal outer sheath thickness: 2.4 mm
  • Nominal outer diameter: 46.0 mm
  • Approximate net weight: 2234 kg/km
  • Perm current rating in air 30°C: 577 A
  • Permissible current rating when buried: 414 A
  • Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.129 Ohm/km
  • Permissible short circuit current conductor 1s: 28.8 kA
  • Permissible short circuit current screen 1s: 5.0 kA

 

XRUHAKXS 1*300/50 18/30KV NEW

Nexans ref. M6A4DP 000137 - Country ref. M6A4DP 1*300/50(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 300 mm²
  • Conductor diameter: 20.3 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 2.4 mm
  • Nominal outer diameter: 46.0 mm
  • Approximate net weight: 2372 kg/km
  • Perm current rating in air 30°C: 577 A
  • Permissible current rating when buried: 414 A
  • Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.129 Ohm/km
  • Permissible short circuit current conductor 1s: 28.8 kA
  • Permissible short circuit current screen 1s: 7.15 kA

 

XRUHAKXS 1*300/70 18/30KV

Nexans ref. M6A4DP 002131 - Country ref. M6A4DP 1*300/70(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 300 mm²
  • Conductor diameter: 20.3 mm
  • Screen section: 70 mm²
  • Nominal outer sheath thickness: 2.4 mm
  • Nominal outer diameter: 47.0 mm
  • Approximate net weight: 2558 kg/km
  • Perm current rating in air 30°C: 577 A
  • Permissible current rating when buried: 414 A
  • Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.129 Ohm/km
  • Permissible short circuit current conductor 1s: 28.8 kA
  • Permissible short circuit current screen 1s: 10.3 kA

 

XRUHAKXS 1*50/16 18/30KV

Nexans ref. M6A4DP 000808 - Country ref. M6A4DP 1*50/16(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 50 mm²
  • Conductor diameter: 8.1 mm
  • Screen section: 16 mm²
  • Nominal outer sheath thickness: 2.0 mm
  • Nominal outer diameter: 33.0 mm
  • Approximate net weight: 928 kg/km
  • Perm current rating in air 30°C: 184 A
  • Permissible current rating when buried: 152 A
  • Max. DC resistance of the conductor at 20°C: 0.641 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.822 Ohm/km
  • Permissible short circuit current conductor 1s: 4.9 kA
  • Permissible short circuit current screen 1s: 2.3 kA

 

XRUHAKXS 1*500/100 18/30KV

Nexans ref. M6A4DP 002134 - Country ref. M6A4DP 1*500/100(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 500 mm²
  • Conductor diameter: 26.2 mm
  • Screen section: 100 mm²
  • Nominal outer sheath thickness: 2.6 mm
  • Nominal outer diameter: 54.0 mm
  • Approximate net weight: 3658 kg/km
  • Perm current rating in air 30°C: 789 A
  • Permissible current rating when buried: 537 A
  • Max. DC resistance of the conductor at 20°C: 0.0605 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0794 Ohm/km
  • Permissible short circuit current conductor 1s: 47.9 kA
  • Permissible short circuit current screen 1s: 14.85 kA

 

XRUHAKXS 1*500/16 18/30KV

Nexans ref. M6A4DP 000801 - Country ref. M6A4DP 1*500/16(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 500 mm²
  • Conductor diameter: 26.2 mm
  • Screen section: 16 mm²
  • Nominal outer sheath thickness: 2.6 mm
  • Nominal outer diameter: 53.0 mm
  • Approximate net weight: 2855 kg/km
  • Perm current rating in air 30°C: 789 A
  • Permissible current rating when buried: 537 A
  • Max. DC resistance of the conductor at 20°C: 0.0605 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0794 Ohm/km
  • Permissible short circuit current conductor 1s: 47.9 kA
  • Permissible short circuit current screen 1s: 2.28 kA

 

XRUHAKXS 1*500/25 18/30KV

Nexans ref. M6A4DP 000820 - Country ref. M6A4DP 1*500/25(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 500 mm²
  • Conductor diameter: 26.2 mm
  • Screen section: 25 mm²
  • Nominal outer sheath thickness: 2.6 mm
  • Nominal outer diameter: 53.0 mm
  • Approximate net weight: 2940 kg/km
  • Perm current rating in air 30°C: 789 A
  • Permissible current rating when buried: 537 A
  • Max. DC resistance of the conductor at 20°C: 0.0605 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0794 Ohm/km
  • Permissible short circuit current conductor 1s: 47.9 kA
  • Permissible short circuit current screen 1s: 3.57 kA

 

XRUHAKXS 1*500/35 18/30KV

Nexans ref. M6A4DP 000119 - Country ref. M6A4DP 1*500/35(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 500 mm²
  • Conductor diameter: 26.2 mm
  • Screen section: 35 mm²
  • Nominal outer sheath thickness: 2.6 mm
  • Nominal outer diameter: 53.0 mm
  • Approximate net weight: 3040 kg/km
  • Perm current rating in air 30°C: 789 A
  • Permissible current rating when buried: 537 A
  • Max. DC resistance of the conductor at 20°C: 0.0605 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0794 Ohm/km
  • Permissible short circuit current conductor 1s: 47.9 kA
  • Permissible short circuit current screen 1s: 5.15 kA

 

XRUHAKXS 1*500/50 18/30KV

Nexans ref. M6A4DP 000134 - Country ref. M6A4DP 1*500/50(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 500 mm²
  • Conductor diameter: 26.2 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 2.6 mm
  • Nominal outer diameter: 52.0 mm
  • Approximate net weight: 3173 kg/km
  • Perm current rating in air 30°C: 789 A
  • Permissible current rating when buried: 537 A
  • Max. DC resistance of the conductor at 20°C: 0.0605 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0794 Ohm/km
  • Permissible short circuit current conductor 1s: 47.9 kA
  • Permissible short circuit current screen 1s: 7.15 kA

 

XRUHAKXS 1*500/70 18/30KV

Nexans ref. M6A4DP 002133 - Country ref. M6A4DP 1*500/70(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 500 mm²
  • Conductor diameter: 26.2 mm
  • Screen section: 70 mm²
  • Nominal outer sheath thickness: 2.6 mm
  • Nominal outer diameter: 54.0 mm
  • Approximate net weight: 3408 kg/km
  • Perm current rating in air 30°C: 789 A
  • Permissible current rating when buried: 537 A
  • Max. DC resistance of the conductor at 20°C: 0.0605 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0794 Ohm/km
  • Permissible short circuit current conductor 1s: 47.9 kA
  • Permissible short circuit current screen 1s: 7.4 kA

 

XRUHAKXS 1*630/100 18/30KV

Nexans ref. M6A4DP 000145 - Country ref. M6A4DP 1*630/100(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 630 mm²
  • Conductor diameter: 29.6 mm
  • Screen section: 100 mm²
  • Nominal outer sheath thickness: 2.8 mm
  • Nominal outer diameter: 58.0 mm
  • Approximate net weight: 4241 kg/km
  • Perm current rating in air 30°C: 916 A
  • Permissible current rating when buried: 611 A
  • Max. DC resistance of the conductor at 20°C: 0.0469 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0626 Ohm/km
  • Permissible short circuit current conductor 1s: 60.2 kA
  • Permissible short circuit current screen 1s: 14.85 kA

 

XRUHAKXS 1*630/16 18/30KV

Nexans ref. M6A4DP 000800 - Country ref. M6A4DP 1*630/16(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 630 mm²
  • Conductor diameter: 29.6 mm
  • Screen section: 16 mm²
  • Nominal outer sheath thickness: 2.7 mm
  • Nominal outer diameter: 57.0 mm
  • Approximate net weight: 3416 kg/km
  • Perm current rating in air 30°C: 916 A
  • Permissible current rating when buried: 611 A
  • Max. DC resistance of the conductor at 20°C: 0.0469 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0626 Ohm/km
  • Permissible short circuit current conductor 1s: 60.2 kA
  • Permissible short circuit current screen 1s: 2.28 kA

 

XRUHAKXS 1*630/25 18/30KV

Nexans ref. M6A4DP 021138 - Country ref. M6A4DP 1*630/25(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 630 mm²
  • Conductor diameter: 29.6 mm
  • Screen section: 25 mm²
  • Nominal outer sheath thickness: 2.7 mm
  • Nominal outer diameter: 57.0 mm
  • Approximate net weight: 3506 kg/km
  • Perm current rating in air 30°C: 916 A
  • Permissible current rating when buried: 611 A
  • Max. DC resistance of the conductor at 20°C: 0.0469 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0626 Ohm/km
  • Permissible short circuit current conductor 1s: 60.2 kA
  • Permissible short circuit current screen 1s: 3.57 kA

 

XRUHAKXS 1*630/35 18/30KV

Nexans ref. M6A4DP 000120 - Country ref. XRUHAKXS 1*630/35

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 630 mm²
  • Conductor diameter: 29.6 mm
  • Screen section: 35 mm²
  • Nominal outer sheath thickness: 2.7 mm
  • Nominal outer diameter: 57.0 mm
  • Approximate net weight: 3604 kg/km
  • Perm current rating in air 30°C: 916 A
  • Permissible current rating when buried: 611 A
  • Max. DC resistance of the conductor at 20°C: 0.0469 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0626 Ohm/km
  • Permissible short circuit current conductor 1s: 60.2 kA
  • Permissible short circuit current screen 1s: 5.0 kA

 

XRUHAKXS 1*630/50 18/30KV NEW

Nexans ref. M6A4DP 000138 - Country ref. M6A4DP 1*630/50(FL)//POL-1

  • Packaging: Drum (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 630 mm²
  • Conductor diameter: 29.6 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 2.7 mm
  • Nominal outer diameter: 57.0 mm
  • Approximate net weight: 3725 kg/km
  • Perm current rating in air 30°C: 916 A
  • Permissible current rating when buried: 611 A
  • Max. DC resistance of the conductor at 20°C: 0.0469 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0626 Ohm/km
  • Permissible short circuit current conductor 1s: 60.2 kA
  • Permissible short circuit current screen 1s: 7.15 kA

 

XRUHAKXS 1*630/70 18/30KV

Nexans ref. M6A4DP 001138 - Country ref. M6A4DP 1*630/70(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 630 mm²
  • Conductor diameter: 29.6 mm
  • Screen section: 70 mm²
  • Nominal outer sheath thickness: 2.8 mm
  • Nominal outer diameter: 58.0 mm
  • Approximate net weight: 3923 kg/km
  • Perm current rating in air 30°C: 916 A
  • Permissible current rating when buried: 611 A
  • Max. DC resistance of the conductor at 20°C: 0.0469 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0626 Ohm/km
  • Permissible short circuit current conductor 1s: 60.2 kA
  • Permissible short circuit current screen 1s: 10.3 kA

 

XRUHAKXS 1*70/25 18/30KV NEW

Nexans ref. M6A4DP 001114 - Country ref. M6A4DP 1*70/25(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 70 mm²
  • Conductor diameter: 9.8 mm
  • Screen section: 25 mm²
  • Nominal outer sheath thickness: 2.0 mm
  • Nominal outer diameter: 34.0 mm
  • Approximate net weight: 1130 kg/km
  • Perm current rating in air 30°C: 230 A
  • Permissible current rating when buried: 186 A
  • Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.568 Ohm/km
  • Permissible short circuit current conductor 1s: 6.8 kA
  • Permissible short circuit current screen 1s: 3.7 kA

 

XRUHAKXS 1*70/35 18/30KV

Nexans ref. M6A4DP 000136 - Country ref. M6A4DP 1*70/35

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 70 mm²
  • Conductor diameter: 9.8 mm
  • Screen section: 35 mm²
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal outer diameter: 35.0 mm
  • Approximate net weight: 1231 kg/km
  • Perm current rating in air 30°C: 230 A
  • Permissible current rating when buried: 186 A
  • Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.568 Ohm/km
  • Permissible short circuit current conductor 1s: 6.8 kA
  • Permissible short circuit current screen 1s: 5.19 kA

 

XRUHAKXS 1*70/50 18/30KV

Nexans ref. M6A4DP 100136 - Country ref. M6A4DP 1*70/50(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 70 mm²
  • Conductor diameter: 9.8 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal outer diameter: 35.0 mm
  • Approximate net weight: 1372 kg/km
  • Perm current rating in air 30°C: 230 A
  • Permissible current rating when buried: 186 A
  • Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.568 Ohm/km
  • Permissible short circuit current conductor 1s: 6.8 kA
  • Permissible short circuit current screen 1s: 7.42 kA

 

XRUHAKXS 1*800/16 18/30KV

Nexans ref. M6A4DP 000864 - Country ref. M6A4DP 1*800/16(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 800 mm²
  • Conductor diameter: 35.2 mm
  • Screen section: 16 mm²
  • Nominal outer sheath thickness: 2.8 mm
  • Nominal outer diameter: 62.5 mm
  • Approximate net weight: 4227 kg/km
  • Perm current rating in air 30°C: 1086 A
  • Permissible current rating when buried: 700 A
  • Max. DC resistance of the conductor at 20°C: 0.0367 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0504 Ohm/km
  • Permissible short circuit current conductor 1s: 76.4 kA
  • Permissible short circuit current screen 1s: 2.28 kA

 

XRUHAKXS 1*800/25 18/30KV

Nexans ref. M6A4DP 000853 - Country ref. M6A4DP 1*800/25(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 800 mm²
  • Conductor diameter: 35.2 mm
  • Screen section: 25 mm²
  • Nominal outer sheath thickness: 2.8 mm
  • Nominal outer diameter: 62.5 mm
  • Approximate net weight: 4312 kg/km
  • Perm current rating in air 30°C: 1086 A
  • Permissible current rating when buried: 700 A
  • Max. DC resistance of the conductor at 20°C: 0.0367 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0504 Ohm/km
  • Permissible short circuit current conductor 1s: 76.4 kA
  • Permissible short circuit current screen 1s: 3.57 kA

 

XRUHAKXS 1*800/35 18/30KV

Nexans ref. M6A4DP 000854 - Country ref. M6A4DP 1*800/35(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 800 mm²
  • Conductor diameter: 35.2 mm
  • Screen section: 35 mm²
  • Nominal outer sheath thickness: 2.8 mm
  • Nominal outer diameter: 62.5 mm
  • Approximate net weight: 4405 kg/km
  • Perm current rating in air 30°C: 1086 A
  • Permissible current rating when buried: 700 A
  • Max. DC resistance of the conductor at 20°C: 0.0367 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0504 Ohm/km
  • Permissible short circuit current conductor 1s: 76.4 kA
  • Permissible short circuit current screen 1s: 5.0 kA

 

XRUHAKXS 1*800/50 18/30KV

Nexans ref. M6A4DP 000855 - Country ref. M6A4DP 1*800/50(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 800 mm²
  • Conductor diameter: 35.2 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 2.8 mm
  • Nominal outer diameter: 62.5 mm
  • Approximate net weight: 4565 kg/km
  • Perm current rating in air 30°C: 1086 A
  • Permissible current rating when buried: 700 A
  • Max. DC resistance of the conductor at 20°C: 0.0367 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0504 Ohm/km
  • Permissible short circuit current conductor 1s: 76.4 kA
  • Permissible short circuit current screen 1s: 7.15 kA

 

XRUHAKXS 1*800/70 18/30KV

Nexans ref. M6A4DP 002132 - Country ref. M6A4DP 1*800/70(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 800 mm²
  • Conductor diameter: 35.2 mm
  • Screen section: 70 mm²
  • Nominal outer sheath thickness: 2.9 mm
  • Nominal outer diameter: 64.0 mm
  • Approximate net weight: 4723 kg/km
  • Perm current rating in air 30°C: 1086 A
  • Permissible current rating when buried: 700 A
  • Max. DC resistance of the conductor at 20°C: 0.0367 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0504 Ohm/km
  • Permissible short circuit current conductor 1s: 76.4 kA
  • Permissible short circuit current screen 1s: 10.3 kA

 

XRUHAKXS 1*95/16 18/30KV

Nexans ref. M6A4DP 000806 - Country ref. M6A4DP 1*95/16(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 95 mm²
  • Conductor diameter: 11.65 mm
  • Screen section: 16 mm²
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal outer diameter: 36.0 mm
  • Approximate net weight: 1186 kg/km
  • Perm current rating in air 30°C: 280 A
  • Permissible current rating when buried: 221 A
  • Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.41 Ohm/km
  • Permissible short circuit current conductor 1s: 9.2 kA
  • Permissible short circuit current screen 1s: 2.28 kA

 

XRUHAKXS 1*95/25 18/30KV

Nexans ref. M6A4DP 000402 - Country ref. M6A4DP 1*95/25(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 95 mm²
  • Conductor diameter: 11.65 mm
  • Screen section: 25 mm²
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal outer diameter: 36.0 mm
  • Approximate net weight: 1263 kg/km
  • Perm current rating in air 30°C: 280 A
  • Permissible current rating when buried: 221 A
  • Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.41 Ohm/km
  • Permissible short circuit current conductor 1s: 9.2 kA
  • Permissible short circuit current screen 1s: 3.57 kA

 

XRUHAKXS 1*95/35 18/30KV

Nexans ref. M6A4DP 000135 - Country ref. M6A4DP 1*95/35(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 95 mm²
  • Conductor diameter: 11.65 mm
  • Screen section: 35 mm²
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal outer diameter: 36.0 mm
  • Approximate net weight: 1362 kg/km
  • Perm current rating in air 30°C: 280 A
  • Permissible current rating when buried: 221 A
  • Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.41 Ohm/km
  • Permissible short circuit current conductor 1s: 9.2 kA
  • Permissible short circuit current screen 1s: 5.0 kA

 

XRUHAKXS 1*95/50 18/30KV NEW

Nexans ref. M6A4DP 001129 - Country ref. M6A4DP 1*95/50(FL)//POL-1

  • Packaging: Cut to length (m)
  • Conductor shape: Round compacted
  • Conductor cross-section: 95 mm²
  • Conductor diameter: 11.65 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal outer diameter: 37.0 mm
  • Approximate net weight: 1501 kg/km
  • Perm current rating in air 30°C: 280 A
  • Permissible current rating when buried: 221 A
  • Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.41 Ohm/km
  • Permissible short circuit current conductor 1s: 9.2 kA
  • Permissible short circuit current screen 1s: 7.15 kA

 

Description

Description

Standards

  • Product
    IEC 60502-2

DESCRIPTION: AL/SC/XLPE/SC/SC SWEL/CU WIRES/SWEL/ALLUPE/PE

OPIS: AL/S.C/XLPE/S.C/S.C. Włóknina. pęczn./druty CU/Włóknina.pęczn./ALUCOPO/PE

1. Conductor / żyła:

Aluminium stranded class 2 acc. To IEC 60228 / aluminiowa wielodrutowa klasa 2 zgodnie z IEC 60228

2. Conductor screen / ekran żyły:

Extruded semi-conductor bonded to the XLPE insulation / wytłoczony półprzewodzący zespojony z izolacją z XLPE

3. Insulation / izolacja:

XLPE / XLPE

4. Insulation screen / ekran izolacji:

Extruded semi-conductor bonded to the XLPE insulation / wytłoczony półprzewodzący zespojony z izolacją z XLPE

5. Water proof tape / taśma zapewniająca wodoszczelność:

Semi-conductor swelling tape / półprzewodząca włóknina pęczniejąca

6. Screen / ekran:

Copper wires / druty miedziane

7. Water proof tape / taśma zapewniająca wodoszczelność:

Swelling tape / włóknina pęczniejąca

8. Radial water proof barrier / poprzeczna bariera wodoszczelna:

Longitudinal aluminium PE coated tape / wzdłużna taśma powlekana AL/PE

9. Oversheath / powłoka zewnętrzna:

PE / PE

TEST AT WORKS / PRÓBY FABRYCZNE

Routine Tests / Badania rutynowe:

• Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-2 parag.16.2 / Maks. rezystancja DC żył w temperaturze 20°C zgodnie z IEC 60228 i IEC 60502-2 pkt 16.2

• High voltage test acc. to IEC 60502-2 parag. 16.4 / Próba wysokim napięciem zgodnie z IEC 60502-2 pkt 16.4

• Max. partial discharge test at 1.73 Uo acc. to IEC 60502-2 parag. 16.3 / Badanie maksymalnych wyładowań niezupełnych przy 1,73 Uo zgodnie z IEC 60502-2 pkt 16.3

 

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided  / Firma Liban Cables przeprowadzi te badania dla wszystkich odcinków kabli i dostarczy świadectwa z badań

 

Sample tests / Badania próbek:

• Check of the build - up and color coding of the cable / Sprawdzenie rozwijania i kolorowych oznaczeń kabla

• Check of dimensions / Sprawdzenie wymiarów

Insulation / Izolacja        :           according to IEC 60502-2 / zgodnie z IEC 60502-2          Parag. / pkt.      17.5.2

Metallic screen / Ekran metaliczny          :           according to IEC 60502-2 / zgodnie z IEC 60502-2          Parag. / pkt.            17.7

Oversheath / Powłoka zewnętrzna           :           according to IEC 60502-2 / zgodnie z IEC 60502-2          Parag. / pkt.            17.5.3

- Hot Set Test for XLPE insulation according to IEC 60502-2 parag. 17.10 /-Badanie stopnia usieciowania izolacji z XLPE zgodnie z IEC 60502-2 pkt 17.10

 

These tests will be carried out on one length of each size during each inspection . / Badania te – podczas każdej kontroli – zostaną przeprowadzone na jednym odcinku dla każdego rozmiaru kabla.

Tests certificates will be provided by Liban Cables / Świadectwa z badań dostarczy firma Liban Cables

 

Type tests / Próby typu

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break ) in accordance with IEC 60502-2. / Charakterystyki mechaniczne materiałów izolacji i powłoki zewnętrznej (wytrzymałość na rozciąganie i wydłużenie przy zerwaniu) zgodnie z IEC 60502-2.

These tests will be carried out on one length of the order / Badania te zostaną przeprowadzone na jednym odcinku z zamówienia

Tests certificates will be provided by Liban Cables / Świadectwa z badań dostarczy firma Liban Cables

DRAWING XRUHAKXS

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor flexibility
Stranded class 2
Material of the inner semi-conductor
Semi-conducting compound
Insulation
XLPE
Material of the external semi-conductor
Extruded fully bonded
Material used for longitudinal water tightness
Swellable tape
Concentric conductor
Copper wires and helical copper tape
Protection
Aluminium tape
Outer sheath
PE
Sheath colour
Black
Number of conductors
1

Dimensional characteristics

Dimensional characteristics

Nominal insulation thickness
8.0 mm

Electrical characteristics

Electrical characteristics

Test voltage
63 kV
Rated Voltage Uo/U (Um)
18 / 30 (36) kV
Frequence
50 Hz
Thermal soil resistivity wet zone
1.5 °K.m/W

Usage characteristics

Usage characteristics

Laying depth, center of system
800 mm
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Max. conductor temperature in service
90 °C
Minimum operating temperature
-35 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close