XnRUHKXS 1*300/50 18/30KV

Products

XnRUHKXS 1*300/50 18/30KV

Nexans ref. M6N4DP 001500 - Country ref. M6N4DP 1*300/50(S)//POL-FO

  • Packaging: Cut to length (m)

 

XnRUHKXS 1*300/50 18/30KV

Nexans ref. M6N4DP 990537 - Country ref. M6N4DP 1*300/50(S)//POL-FO,

  • Packaging: Cut to length (m)

 

XnRUHKXS 1*300/50 18/30KV

Nexans ref. M6N4DP 990542 - Country ref. M6N4DP 1*300/50(S)//POL-FO.,

  • Packaging: Cut to length (m)

 

Description

Description

Standards

  • Product
    IEC 60502-2
  • Test
    IEC 60332-1-2

CU+SWELLING TAPES/SC/XLPE/SC/SC SWELLING TAPE/CU WIRES+FO/SWELLING TAPE/PE


APPLICATION

  • Power use outdoor application, even wet.
  • Suitable for fixed installations at open air, in tube or canals and underground.
  • Max. Operation temperature: 90°
  • Max. Short circuit temperature : 250° (Max 5 s)

 

CONSTRUCTION

  1. Conductor: :Compacted Round conductor class 2 + Swelling tapes.
  2. Insulation: Extruded inner semi conductive layer, XLPE insulation and  extruded outer semi conductive layer 
  3. Water proof tape :: Semi-conductor swelling tape
  4. Metallic screen layer:: Copper wires + ONE FIBER METAL TUBES + OPEN HELIX COPPER TAPE.
  5. Water proof tape :: Swelling tape
  6. Outer sheath: PE FR

 

MARKING

Marking: By Inkjet or customer requirement.

 

PACKING

Packing: Drums can be wooden or steel

TEST AT WORKS ACCORDING TO IEC 60502-2 / PRÓBY FABRYCZNE XnRUHAKXS, XnRUHKXS

Routine Tests / Badania rutynowe:

• Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-2 parag.16.2 / Maks. rezystancja DC żył w temperaturze 20°C zgodnie z IEC 60228 i IEC 60502-2 pkt 16.2

• High voltage test acc. to IEC 60502-2 parag. 16.4 / Próba wysokim napięciem zgodnie z IEC 60502-2 pkt 16.4

• Max. partial discharge test at 1.73 Uo acc. to IEC 60502-2 parag. 16.3 / Badanie maksymalnych wyładowań niezupełnych przy 1,73 Uo zgodnie z IEC 60502-2 pkt 16.3

 

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided  / Firma Liban Cables przeprowadzi te badania dla wszystkich odcinków kabli i dostarczy świadectwa z badań

 

Sample tests / Badania próbek:

• Check of the build - up and color coding of the cable / Sprawdzenie rozwijania i kolorowych oznaczeń kabla

• Check of dimensions / Sprawdzenie wymiarów

Insulation / Izolacja        :           according to IEC 60502-2 / zgodnie z IEC 60502-2          Parag. / pkt.      17.5.2

Metallic screen / Ekran metaliczny          :           according to IEC 60502-2 / zgodnie z IEC 60502-2          Parag. / pkt.            17.7

Oversheath / Powłoka zewnętrzna           :           according to IEC 60502-2 / zgodnie z IEC 60502-2          Parag. / pkt.            17.5.3

- Hot Set Test for XLPE insulation according to IEC 60502-2 parag. 17.10 /-Badanie stopnia usieciowania izolacji z XLPE zgodnie z IEC 60502-2 pkt 17.10

 

These tests will be carried out on one length of each size during each inspection . / Badania te – podczas każdej kontroli – zostaną przeprowadzone na jednym odcinku dla każdego rozmiaru kabla.

Tests certificates will be provided by Liban Cables / Świadectwa z badań dostarczy firma Liban Cables

 

Type tests / Próby typu

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break ) in accordance with IEC 60502-2. / Charakterystyki mechaniczne materiałów izolacji i powłoki zewnętrznej (wytrzymałość na rozciąganie i wydłużenie przy zerwaniu) zgodnie z IEC 60502-2.

These tests will be carried out on one length of the order / Badania te zostaną przeprowadzone na jednym odcinku z zamówienia

Tests certificates will be provided by Liban Cables / Świadectwa z badań dostarczy firma Liban Cables

Characteristics

Characteristics

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
300 mm²
Nominal insulation thickness
8.0 mm
Screen section
50 mm²
Nominal outer sheath thickness
2.4 mm
Nominal outer diameter
48.0 mm

Electrical characteristics

Electrical characteristics

Test voltage
63 kV
Rated Voltage Uo/U (Um)
18 / 30 (36) kV
Frequence
50 Hz

Mechanical characteristics

Mechanical characteristics

Cable flexibility
10xD
Mechanical resistance to impacts
Good

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close