XnRUHKXS armored 3*120/50 12/20kV
XnRUHKXS armored 3*120/50 12/20kV
XLPE Armored cable with copper conductor (water tight at the screen area only)
Read more- Nexans ref. : M5N4DRP000200
- Country ref. : M5N4DRP 3*120/50(FL)//POL-2
Description
Description
Standards
-
ProductIEC 60228; IEC 60502-2
-
TestIEC 60332-1-2
CU/SC/XLPE/SC/SC SWEL/CU WIRES/SWEL/ALLUPE/PE/ARMOUR/PE
CONSTRUCTION
1. Conductor:
Compacted Round conductor class 2
2. Insulation:
Extruded inner semi conductive layer, XLPE insulation and extruded outer semi conductive layer
3. Water proof tape:
Semi-conductive swelling tape
4. Metallic screen layer:
Copper wires with open helix copper tape
5. Water proof tape:
Swelling tape
6. Radial water tightness:
Longitudinal PE coated Aluminum Tape
7. Separation sheath:
PE FR
8. Armour:
Galvanized steel wires armoring
9. Outer sheath:
PE FR
10. Marking:
By Inkjet printing on one line over the outer jacket
9. Packing:
Drums can be wooden or steel
TEST AT WORKS FOR XnRUHKXS armored
Routine Tests
-Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-2 parag. 16.1 & 16.2
-High voltage test acc. to IEC 60502-2 parag. 16.1 & 16.4
-Max. partial discharge test at 1.73 Uo acc. to IEC 60502-2 parag. 16.1 & 16.3
Liban Cables will carry out these tests on all the lengths and tests certificates will be provided
Sample tests
- Check of the build - up and color coding of the cable
- Check of dimensions
Insulation : according to IEC 60502-2 Parag. 17.5.2
Metallic screen : according to IEC 60502-2 Parag. 17.7
Separation sheath: according to IEC 60502-2 Parag.17.5.3
Armouring: according to IEC 60502-2 Parag.17.7
Oversheath : according to IEC 60502-2 Parag. 17.5.3
- Hot Set Test for XLPE insulation according to IEC 60502-2 parag. 17.10
These tests will be carried out on one length of each size during each inspection .
Tests certificates will be provided by Liban Cables
Type tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-2.
These tests will be carried out on one length of the order.
Tests certificates will be provided by Liban Cables
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania