3C AL Cond. steel tape armored cables

Products

M3A3B 3*240

Nexans ref. M3A3B 004240 - Country ref. M3A3B 3*240//EDL-SP

  • Material of the external semi-conductor: Extruded strippable
  • Armour type: Steel tapes
  • Colour: Red
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 17.9 mm
  • Nominal insulation thickness: 3.4 mm
  • Nominal outer sheath thickness: 3.3 mm
  • Nominal outer diameter: 68.0 mm
  • Approximate net weight: 5697 kg/km
  • Test voltage: 21 kV
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV
  • Perm current rating in air 30°C: 415 A
  • Permissible current rating when buried: 338 A
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
  • Permissible short circuit current conductor 1s: 23.1 kA

 

M5A2G 3*150

Nexans ref. M5A2G 001552 - Country ref. M5A2G 3*150

  • Material of the external semi-conductor: Extruded fully bonded
  • Armour type: Galvanized steel tapes
  • Colour: Black
  • Conductor cross-section: 150 mm²
  • Conductor diameter: 14.4 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal outer sheath thickness: 3.4 mm
  • Nominal outer diameter: 69.0 mm
  • Approximate net weight: 5296 kg/km
  • Test voltage: 42 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 309 A
  • Permissible current rating when buried: 259 A
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.264 Ohm/km
  • Permissible short circuit current conductor 1s: 14.5 kA

 

M5A2G 3*240

Nexans ref. M5A2G 000552 - Country ref. 3C AL Cond. double black steel tape armored cables 12/20KV

  • Material of the external semi-conductor: Extruded fully bonded
  • Armour type: Galvanized steel tapes
  • Colour: Black
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 17.9 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal outer sheath thickness: 3.7 mm
  • Nominal outer diameter: 78.0 mm
  • Approximate net weight: 7314 kg/km
  • Test voltage: 42 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 415 A
  • Permissible current rating when buried: 338 A
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
  • Permissible short circuit current conductor 1s: 23.1 kA

 

M5A2G 3*240

Nexans ref. M5A2G..000553 - Country ref. M5A2G 3*240//R

  • Material of the external semi-conductor: Extruded fully bonded
  • Armour type: Galvanized steel tapes
  • Colour: Red
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 17.9 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal outer sheath thickness: 3.7 mm
  • Nominal outer diameter: 78.0 mm
  • Approximate net weight: 7314 kg/km
  • Test voltage: 42 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 415 A
  • Permissible current rating when buried: 338 A
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
  • Permissible short circuit current conductor 1s: 23.1 kA

 

M5A2G 3*95

Nexans ref. M5A2G 700112 - Country ref. M5A2G 3*95

  • Material of the external semi-conductor: Extruded fully bonded
  • Armour type: Galvanized steel tapes
  • Colour: Black
  • Conductor cross-section: 95 mm²
  • Conductor diameter: 11.6 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal outer sheath thickness: 3.1 mm
  • Nominal outer diameter: 62.0 mm
  • Approximate net weight: 4063 kg/km
  • Test voltage: 42 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 238 A
  • Permissible current rating when buried: 204 A
  • Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.41 Ohm/km
  • Permissible short circuit current conductor 1s: 9.2 kA

 

M5A3B 3*120 NEW

Nexans ref. M5A3B 002570 - Country ref. M5A3B 3*120//EDL-SP

  • Material of the external semi-conductor: Extruded strippable
  • Armour type: Steel tapes
  • Colour: Red
  • Conductor cross-section: 120 mm²
  • Conductor diameter: 12.8 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal outer sheath thickness: 3.3 mm
  • Nominal outer diameter: 66.0 mm
  • Approximate net weight: 4767 kg/km
  • Test voltage: 42 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 274 A
  • Permissible current rating when buried: 232 A
  • Max. DC resistance of the conductor at 20°C: 0.323 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.253 Ohm/km
  • Permissible short circuit current conductor 1s: 11.6 kA

 

M5A3B 3*120

Nexans ref. M5A3B 102570 - Country ref. M5A3B 3*120//EDL-SP1

  • Packaging: Cut to length (m)
  • Material of the external semi-conductor: Extruded strippable
  • Armour type: Steel tapes
  • Colour: Red
  • Conductor cross-section: 120 mm²
  • Conductor diameter: 12.8 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal outer sheath thickness: 3.3 mm
  • Nominal outer diameter: 65.0 mm
  • Approximate net weight: 4767 kg/km
  • Test voltage: 42 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 274 A
  • Permissible current rating when buried: 232 A
  • Max. DC resistance of the conductor at 20°C: 0.323 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.253 Ohm/km
  • Permissible short circuit current conductor 1s: 11.6 kA

 

M5A3B 3*185

Nexans ref. M5A3B 004385 - Country ref. M5A3B 3*185//EDL-SP

  • Material of the external semi-conductor: Extruded strippable
  • Armour type: Steel tapes
  • Colour: Red
  • Conductor cross-section: 185 mm²
  • Conductor diameter: 16.2 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal outer sheath thickness: 3.5 mm
  • Nominal outer diameter: 73.0 mm
  • Approximate net weight: 6057 kg/km
  • Test voltage: 42 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 354 A
  • Permissible current rating when buried: 293 A
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.21 Ohm/km
  • Permissible short circuit current conductor 1s: 17.9 kA

 

M5A3B 3*185

Nexans ref. M5A3B 104385 - Country ref. M5A3B 3*185//EDL-SP1

  • Packaging: Cut to length (m)
  • Material of the external semi-conductor: Extruded strippable
  • Armour type: Steel tapes
  • Colour: Red
  • Conductor cross-section: 185 mm²
  • Conductor diameter: 16.2 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal outer sheath thickness: 3.5 mm
  • Nominal outer diameter: 73.0 mm
  • Approximate net weight: 6038 kg/km
  • Test voltage: 42 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 354 A
  • Permissible current rating when buried: 293 A
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.21 Ohm/km
  • Permissible short circuit current conductor 1s: 17.9 kA

 

M5A3B 3*240

Nexans ref. M5A3B 004240 - Country ref. M5A3B 3*240//EDL-SP

  • Material of the external semi-conductor: Extruded strippable
  • Armour type: Steel tapes
  • Colour: Red
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 17.9 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal outer sheath thickness: 3.7 mm
  • Nominal outer diameter: 79.0 mm
  • Approximate net weight: 7363 kg/km
  • Test voltage: 42 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 415 A
  • Permissible current rating when buried: 338 A
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
  • Permissible short circuit current conductor 1s: 23.1 kA

 

M5A3B 3*240

Nexans ref. M5A3B 004241 - Country ref. M5A3B 3*240//EDL-SP1

  • Packaging: Cut to length (m)
  • Material of the external semi-conductor: Extruded strippable
  • Armour type: Steel tapes
  • Colour: Red
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 17.9 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal outer sheath thickness: 3.7 mm
  • Nominal outer diameter: 78.0 mm
  • Approximate net weight: 7314 kg/km
  • Test voltage: 42 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 415 A
  • Permissible current rating when buried: 338 A
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
  • Permissible short circuit current conductor 1s: 23.1 kA

 

M5A3B 3*300

Nexans ref. M5A3B 002582 - Country ref. M5A3B 3*300//EDL-SP

  • Material of the external semi-conductor: Extruded strippable
  • Armour type: Steel tapes
  • Colour: Red
  • Conductor cross-section: 300 mm²
  • Conductor diameter: 20.3 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal outer sheath thickness: 3.9 mm
  • Nominal outer diameter: 84.0 mm
  • Approximate net weight: 8493 kg/km
  • Test voltage: 42 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 472 A
  • Permissible current rating when buried: 380 A
  • Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.129 Ohm/km
  • Permissible short circuit current conductor 1s: 28.8 kA

 

M5A3B 3*300

Nexans ref. M5A3B 102582 - Country ref. M5A3B 3*300//EDL-SP1

  • Packaging: Cut to length (m)
  • Material of the external semi-conductor: Extruded strippable
  • Armour type: Steel tapes
  • Colour: Red
  • Conductor cross-section: 300 mm²
  • Conductor diameter: 20.3 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal outer sheath thickness: 3.9 mm
  • Nominal outer diameter: 84.0 mm
  • Approximate net weight: 8492 kg/km
  • Test voltage: 42 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 472 A
  • Permissible current rating when buried: 380 A
  • Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.129 Ohm/km
  • Permissible short circuit current conductor 1s: 28.8 kA

 

M5A3B 3*400

Nexans ref. M5A3B 002583 - Country ref. M5A3B 3*400//EDL-SP

  • Material of the external semi-conductor: Extruded strippable
  • Armour type: Steel tapes
  • Colour: Red
  • Conductor cross-section: 400 mm²
  • Conductor diameter: 23.2 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal outer sheath thickness: 4.1 mm
  • Nominal outer diameter: 93.0 mm
  • Approximate net weight: 10023 kg/km
  • Test voltage: 42 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 545 A
  • Permissible current rating when buried: 432 A
  • Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0997 Ohm/km
  • Permissible short circuit current conductor 1s: 38.3 kA

 

M5A3B 3*400

Nexans ref. M5A3B 102583 - Country ref. M5A3B 3*400//EDL-SP1

  • Packaging: Cut to length (m)
  • Material of the external semi-conductor: Extruded strippable
  • Armour type: Steel tapes
  • Colour: Red
  • Conductor cross-section: 400 mm²
  • Conductor diameter: 23.2 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal outer sheath thickness: 4.1 mm
  • Nominal outer diameter: 92.0 mm
  • Approximate net weight: 10038 kg/km
  • Test voltage: 42 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 545 A
  • Permissible current rating when buried: 432 A
  • Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.0997 Ohm/km
  • Permissible short circuit current conductor 1s: 38.3 kA

 

M5A3B 3*70

Nexans ref. M5A3B 002520 - Country ref. M5A3B 3*70//EDL-SP

  • Material of the external semi-conductor: Extruded strippable
  • Armour type: Steel tapes
  • Colour: Red
  • Conductor cross-section: 70 mm²
  • Conductor diameter: 9.8 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal outer sheath thickness: 3.0 mm
  • Nominal outer diameter: 58.0 mm
  • Approximate net weight: 3697 kg/km
  • Test voltage: 42 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 196 A
  • Permissible current rating when buried: 171 A
  • Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.568 Ohm/km
  • Permissible short circuit current conductor 1s: 6.8 kA

 

M5A3B 3*95 NEW

Nexans ref. M5A3B 002580 - Country ref. M5A3B 3*95//EDL-SP

  • Material of the external semi-conductor: Extruded strippable
  • Armour type: Steel tapes
  • Colour: Red
  • Conductor cross-section: 95 mm²
  • Conductor diameter: 11.7 mm
  • Nominal insulation thickness: 5.5 mm
  • Nominal outer sheath thickness: 3.1 mm
  • Nominal outer diameter: 63.0 mm
  • Approximate net weight: 4249 kg/km
  • Test voltage: 42 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Perm current rating in air 30°C: 238 A
  • Permissible current rating when buried: 204 A
  • Max. DC resistance of the conductor at 20°C: 0.41 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.32 Ohm/km
  • Permissible short circuit current conductor 1s: 9.2 kA

 

M6A2G 3*240

Nexans ref. M6A2G 000242 - Country ref. M6A2G 3*240

  • Material of the external semi-conductor: Extruded fully bonded
  • Armour type: Galvanized steel tapes
  • Colour: Black
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 17.9 mm
  • Nominal insulation thickness: 8.0 mm
  • Nominal outer sheath thickness: 4.1 mm
  • Nominal outer diameter: 88.0 mm
  • Approximate net weight: 8768 kg/km
  • Test voltage: 63 kV
  • Rated Voltage Uo/U (Um): 18 / 30 (36) kV
  • Perm current rating in air 30°C: 415 A
  • Permissible current rating when buried: 338 A
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
  • Permissible short circuit current conductor 1s: 23.1 kA

 

Description

Description

Standards

  • International
    IEC 60332-1-2; IEC 60502-2

1-SCOPE

This specification covers three core armoured cables, rated at 12/20 (24) KV conforming to IEC 60502-2 Specifications.
 

2. CONSTRUCTION

2.1 Conductor

Aluminum conductors, conforming to the applicable requirements of IEC 60228.
 

2.2 Insulation

Extruded inner semi conductive layer, XLPE insulation and  extruded outer semi conductive layer .

 

2.3 Metallic Screen Layer

Copper tape on each core

 

2.4 Separation Sheath

PVC .

 

2.5 Armour

Two layers of steel tape .
 

2.5 Sheath

PVC .
 

3. TESTS

All tests required by IEC 60502-2 either on Raw material or on finished products.

TEST AT WORKS according to IEC 60502-2 for armored cables

Routine Tests

 -          Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-2 parag.16.1 & 16.2

 -          High voltage test acc. to IEC 60502-2  parag. 16.1 & 16.4

 -          Max. partial discharge test  at 1.73 Uo acc. to IEC 60502-2  parag.16.1 & 16.3

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided.

 

Sample Tests

 -          Check of the build - up and color coding of the cable                                                      

 -          Check of dimensions                                                    

            Insulation                      :           according to IEC 60502-2           Parag.  17.5.2

            Separation sheath         :           according to IEC 60502-2           Parag.  17.5.3

            Armouring                     :           according to IEC 60502-2          Parag.  17.7

            Oversheath                   :           according to IEC 60502-2           Parag.  17.5.3

-           Hot Set Test                  :           according to IEC 60502-2           Parag.  17.10

These tests will be carried out on one length of each size during each inspection .

Tests certificates will be provided by Liban Cables

                                                                       

Type Tests

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break  ) in accordance with IEC 60502-2.

These tests will be carried out on one length of the order .

Tests certificates will be provided by Liban Cables

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Number of conductors
3
Conductor shape
Circular
Material of the inner semi-conductor
Extruded
Insulation
XLPE
Screen
Copper tape
Outer sheath
PVC
Conductor flexibility
Class 2 IEC 60228

Electrical characteristics

Electrical characteristics

Thermal soil resistivity wet zone
1.5 °K.m/W

Usage characteristics

Usage characteristics

Laying depth, center of system
800 mm
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Max. conductor temperature in service
90 °C
Operating temperature, range
-15 ... 55 °C
Short-circuit max. conductor temperature
250 °C
Flame retardant
IEC 60332-1-2

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close