M3A3B 3*240
Nexans ref. M3A3B 004240 - Country ref. M3A3B 3*240//EDL-SP
- Material of the external semi-conductor: Extruded strippable
- Armour type: Steel tapes
- Colour: Red
- Conductor cross-section: 240 mm²
- Conductor diameter: 17.9 mm
- Nominal insulation thickness: 3.4 mm
- Nominal outer sheath thickness: 3.3 mm
- Nominal outer diameter: 68.0 mm
- Approximate net weight: 5697 kg/km
- Test voltage: 21 kV
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Perm current rating in air 30°C: 415 A
- Permissible current rating when buried: 338 A
- Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
- Permissible short circuit current conductor 1s: 23.1 kA
M5A2G 3*150
Nexans ref. M5A2G 001552 - Country ref. M5A2G 3*150
- Material of the external semi-conductor: Extruded fully bonded
- Armour type: Galvanized steel tapes
- Colour: Black
- Conductor cross-section: 150 mm²
- Conductor diameter: 14.4 mm
- Nominal insulation thickness: 5.5 mm
- Nominal outer sheath thickness: 3.4 mm
- Nominal outer diameter: 69.0 mm
- Approximate net weight: 5296 kg/km
- Test voltage: 42 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Perm current rating in air 30°C: 309 A
- Permissible current rating when buried: 259 A
- Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.264 Ohm/km
- Permissible short circuit current conductor 1s: 14.5 kA
M5A2G 3*240
Nexans ref. M5A2G 000552 - Country ref. 3C AL Cond. double black steel tape armored cables 12/20KV
- Material of the external semi-conductor: Extruded fully bonded
- Armour type: Galvanized steel tapes
- Colour: Black
- Conductor cross-section: 240 mm²
- Conductor diameter: 17.9 mm
- Nominal insulation thickness: 5.5 mm
- Nominal outer sheath thickness: 3.7 mm
- Nominal outer diameter: 78.0 mm
- Approximate net weight: 7314 kg/km
- Test voltage: 42 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Perm current rating in air 30°C: 415 A
- Permissible current rating when buried: 338 A
- Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
- Permissible short circuit current conductor 1s: 23.1 kA
M5A2G 3*240
Nexans ref. M5A2G..000553 - Country ref. M5A2G 3*240//R
- Material of the external semi-conductor: Extruded fully bonded
- Armour type: Galvanized steel tapes
- Colour: Red
- Conductor cross-section: 240 mm²
- Conductor diameter: 17.9 mm
- Nominal insulation thickness: 5.5 mm
- Nominal outer sheath thickness: 3.7 mm
- Nominal outer diameter: 78.0 mm
- Approximate net weight: 7314 kg/km
- Test voltage: 42 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Perm current rating in air 30°C: 415 A
- Permissible current rating when buried: 338 A
- Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
- Permissible short circuit current conductor 1s: 23.1 kA
M5A2G 3*95
Nexans ref. M5A2G 700112 - Country ref. M5A2G 3*95
- Material of the external semi-conductor: Extruded fully bonded
- Armour type: Galvanized steel tapes
- Colour: Black
- Conductor cross-section: 95 mm²
- Conductor diameter: 11.6 mm
- Nominal insulation thickness: 5.5 mm
- Nominal outer sheath thickness: 3.1 mm
- Nominal outer diameter: 62.0 mm
- Approximate net weight: 4063 kg/km
- Test voltage: 42 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Perm current rating in air 30°C: 238 A
- Permissible current rating when buried: 204 A
- Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.41 Ohm/km
- Permissible short circuit current conductor 1s: 9.2 kA
M5A3B 3*120 NEW
Nexans ref. M5A3B 002570 - Country ref. M5A3B 3*120//EDL-SP
- Material of the external semi-conductor: Extruded strippable
- Armour type: Steel tapes
- Colour: Red
- Conductor cross-section: 120 mm²
- Conductor diameter: 12.8 mm
- Nominal insulation thickness: 5.5 mm
- Nominal outer sheath thickness: 3.3 mm
- Nominal outer diameter: 66.0 mm
- Approximate net weight: 4767 kg/km
- Test voltage: 42 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Perm current rating in air 30°C: 274 A
- Permissible current rating when buried: 232 A
- Max. DC resistance of the conductor at 20°C: 0.323 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.253 Ohm/km
- Permissible short circuit current conductor 1s: 11.6 kA
M5A3B 3*120
Nexans ref. M5A3B 102570 - Country ref. M5A3B 3*120//EDL-SP1
- Packaging: Cut to length (m)
- Material of the external semi-conductor: Extruded strippable
- Armour type: Steel tapes
- Colour: Red
- Conductor cross-section: 120 mm²
- Conductor diameter: 12.8 mm
- Nominal insulation thickness: 5.5 mm
- Nominal outer sheath thickness: 3.3 mm
- Nominal outer diameter: 65.0 mm
- Approximate net weight: 4767 kg/km
- Test voltage: 42 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Perm current rating in air 30°C: 274 A
- Permissible current rating when buried: 232 A
- Max. DC resistance of the conductor at 20°C: 0.323 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.253 Ohm/km
- Permissible short circuit current conductor 1s: 11.6 kA
M5A3B 3*185
Nexans ref. M5A3B 004385 - Country ref. M5A3B 3*185//EDL-SP
- Material of the external semi-conductor: Extruded strippable
- Armour type: Steel tapes
- Colour: Red
- Conductor cross-section: 185 mm²
- Conductor diameter: 16.2 mm
- Nominal insulation thickness: 5.5 mm
- Nominal outer sheath thickness: 3.5 mm
- Nominal outer diameter: 73.0 mm
- Approximate net weight: 6057 kg/km
- Test voltage: 42 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Perm current rating in air 30°C: 354 A
- Permissible current rating when buried: 293 A
- Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.21 Ohm/km
- Permissible short circuit current conductor 1s: 17.9 kA
M5A3B 3*185
Nexans ref. M5A3B 104385 - Country ref. M5A3B 3*185//EDL-SP1
- Packaging: Cut to length (m)
- Material of the external semi-conductor: Extruded strippable
- Armour type: Steel tapes
- Colour: Red
- Conductor cross-section: 185 mm²
- Conductor diameter: 16.2 mm
- Nominal insulation thickness: 5.5 mm
- Nominal outer sheath thickness: 3.5 mm
- Nominal outer diameter: 73.0 mm
- Approximate net weight: 6038 kg/km
- Test voltage: 42 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Perm current rating in air 30°C: 354 A
- Permissible current rating when buried: 293 A
- Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.21 Ohm/km
- Permissible short circuit current conductor 1s: 17.9 kA
M5A3B 3*240
Nexans ref. M5A3B 004240 - Country ref. M5A3B 3*240//EDL-SP
- Material of the external semi-conductor: Extruded strippable
- Armour type: Steel tapes
- Colour: Red
- Conductor cross-section: 240 mm²
- Conductor diameter: 17.9 mm
- Nominal insulation thickness: 5.5 mm
- Nominal outer sheath thickness: 3.7 mm
- Nominal outer diameter: 79.0 mm
- Approximate net weight: 7363 kg/km
- Test voltage: 42 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Perm current rating in air 30°C: 415 A
- Permissible current rating when buried: 338 A
- Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
- Permissible short circuit current conductor 1s: 23.1 kA
M5A3B 3*240
Nexans ref. M5A3B 004241 - Country ref. M5A3B 3*240//EDL-SP1
- Packaging: Cut to length (m)
- Material of the external semi-conductor: Extruded strippable
- Armour type: Steel tapes
- Colour: Red
- Conductor cross-section: 240 mm²
- Conductor diameter: 17.9 mm
- Nominal insulation thickness: 5.5 mm
- Nominal outer sheath thickness: 3.7 mm
- Nominal outer diameter: 78.0 mm
- Approximate net weight: 7314 kg/km
- Test voltage: 42 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Perm current rating in air 30°C: 415 A
- Permissible current rating when buried: 338 A
- Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
- Permissible short circuit current conductor 1s: 23.1 kA
M5A3B 3*300
Nexans ref. M5A3B 002582 - Country ref. M5A3B 3*300//EDL-SP
- Material of the external semi-conductor: Extruded strippable
- Armour type: Steel tapes
- Colour: Red
- Conductor cross-section: 300 mm²
- Conductor diameter: 20.3 mm
- Nominal insulation thickness: 5.5 mm
- Nominal outer sheath thickness: 3.9 mm
- Nominal outer diameter: 84.0 mm
- Approximate net weight: 8493 kg/km
- Test voltage: 42 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Perm current rating in air 30°C: 472 A
- Permissible current rating when buried: 380 A
- Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.129 Ohm/km
- Permissible short circuit current conductor 1s: 28.8 kA
M5A3B 3*300
Nexans ref. M5A3B 102582 - Country ref. M5A3B 3*300//EDL-SP1
- Packaging: Cut to length (m)
- Material of the external semi-conductor: Extruded strippable
- Armour type: Steel tapes
- Colour: Red
- Conductor cross-section: 300 mm²
- Conductor diameter: 20.3 mm
- Nominal insulation thickness: 5.5 mm
- Nominal outer sheath thickness: 3.9 mm
- Nominal outer diameter: 84.0 mm
- Approximate net weight: 8492 kg/km
- Test voltage: 42 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Perm current rating in air 30°C: 472 A
- Permissible current rating when buried: 380 A
- Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.129 Ohm/km
- Permissible short circuit current conductor 1s: 28.8 kA
M5A3B 3*400
Nexans ref. M5A3B 002583 - Country ref. M5A3B 3*400//EDL-SP
- Material of the external semi-conductor: Extruded strippable
- Armour type: Steel tapes
- Colour: Red
- Conductor cross-section: 400 mm²
- Conductor diameter: 23.2 mm
- Nominal insulation thickness: 5.5 mm
- Nominal outer sheath thickness: 4.1 mm
- Nominal outer diameter: 93.0 mm
- Approximate net weight: 10023 kg/km
- Test voltage: 42 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Perm current rating in air 30°C: 545 A
- Permissible current rating when buried: 432 A
- Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.0997 Ohm/km
- Permissible short circuit current conductor 1s: 38.3 kA
M5A3B 3*400
Nexans ref. M5A3B 102583 - Country ref. M5A3B 3*400//EDL-SP1
- Packaging: Cut to length (m)
- Material of the external semi-conductor: Extruded strippable
- Armour type: Steel tapes
- Colour: Red
- Conductor cross-section: 400 mm²
- Conductor diameter: 23.2 mm
- Nominal insulation thickness: 5.5 mm
- Nominal outer sheath thickness: 4.1 mm
- Nominal outer diameter: 92.0 mm
- Approximate net weight: 10038 kg/km
- Test voltage: 42 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Perm current rating in air 30°C: 545 A
- Permissible current rating when buried: 432 A
- Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.0997 Ohm/km
- Permissible short circuit current conductor 1s: 38.3 kA
M5A3B 3*70
Nexans ref. M5A3B 002520 - Country ref. M5A3B 3*70//EDL-SP
- Material of the external semi-conductor: Extruded strippable
- Armour type: Steel tapes
- Colour: Red
- Conductor cross-section: 70 mm²
- Conductor diameter: 9.8 mm
- Nominal insulation thickness: 5.5 mm
- Nominal outer sheath thickness: 3.0 mm
- Nominal outer diameter: 58.0 mm
- Approximate net weight: 3697 kg/km
- Test voltage: 42 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Perm current rating in air 30°C: 196 A
- Permissible current rating when buried: 171 A
- Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.568 Ohm/km
- Permissible short circuit current conductor 1s: 6.8 kA
M5A3B 3*95 NEW
Nexans ref. M5A3B 002580 - Country ref. M5A3B 3*95//EDL-SP
- Material of the external semi-conductor: Extruded strippable
- Armour type: Steel tapes
- Colour: Red
- Conductor cross-section: 95 mm²
- Conductor diameter: 11.7 mm
- Nominal insulation thickness: 5.5 mm
- Nominal outer sheath thickness: 3.1 mm
- Nominal outer diameter: 63.0 mm
- Approximate net weight: 4249 kg/km
- Test voltage: 42 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Perm current rating in air 30°C: 238 A
- Permissible current rating when buried: 204 A
- Max. DC resistance of the conductor at 20°C: 0.41 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.32 Ohm/km
- Permissible short circuit current conductor 1s: 9.2 kA
M6A2G 3*240
Nexans ref. M6A2G 000242 - Country ref. M6A2G 3*240
- Material of the external semi-conductor: Extruded fully bonded
- Armour type: Galvanized steel tapes
- Colour: Black
- Conductor cross-section: 240 mm²
- Conductor diameter: 17.9 mm
- Nominal insulation thickness: 8.0 mm
- Nominal outer sheath thickness: 4.1 mm
- Nominal outer diameter: 88.0 mm
- Approximate net weight: 8768 kg/km
- Test voltage: 63 kV
- Rated Voltage Uo/U (Um): 18 / 30 (36) kV
- Perm current rating in air 30°C: 415 A
- Permissible current rating when buried: 338 A
- Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
- Permissible short circuit current conductor 1s: 23.1 kA
Description
Description
Standards
-
InternationalIEC 60332-1-2; IEC 60502-2
1-SCOPE
This specification covers three core armoured cables, rated at 12/20 (24) KV conforming to IEC 60502-2 Specifications.
2. CONSTRUCTION
2.1 Conductor
Aluminum conductors, conforming to the applicable requirements of IEC 60228.
2.2 Insulation
Extruded inner semi conductive layer, XLPE insulation and extruded outer semi conductive layer .
2.3 Metallic Screen Layer
Copper tape on each core
2.4 Separation Sheath
PVC .
2.5 Armour
Two layers of steel tape .
2.5 Sheath
PVC .
3. TESTS
All tests required by IEC 60502-2 either on Raw material or on finished products.
TEST AT WORKS according to IEC 60502-2 for armored cables
Routine Tests
- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-2 parag.16.1 & 16.2
- High voltage test acc. to IEC 60502-2 parag. 16.1 & 16.4
- Max. partial discharge test at 1.73 Uo acc. to IEC 60502-2 parag.16.1 & 16.3
Liban Cables will carry out these tests on all the lengths and tests certificates will be provided.
Sample Tests
- Check of the build - up and color coding of the cable
- Check of dimensions
Insulation : according to IEC 60502-2 Parag. 17.5.2
Separation sheath : according to IEC 60502-2 Parag. 17.5.3
Armouring : according to IEC 60502-2 Parag. 17.7
Oversheath : according to IEC 60502-2 Parag. 17.5.3
- Hot Set Test : according to IEC 60502-2 Parag. 17.10
These tests will be carried out on one length of each size during each inspection .
Tests certificates will be provided by Liban Cables
Type Tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break ) in accordance with IEC 60502-2.
These tests will be carried out on one length of the order .
Tests certificates will be provided by Liban Cables
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania