3C Cu Cond. CWS, GSWA and LSZH sheath

Products

M3N5URU 3*240/35

Nexans ref. M3N5URU000185 - Country ref. M3N5R 3*240/35//KEL

 

Description

Description

Standards

  • International
    IEC 60332-1-2
  • National
    BS 7835

1-SCOPE

This specification covers three cores armoured cables.
 

2. CONSTRUCTION

2.1 Conductor

Plain, annealed electrolytic copper conductors, circular stranded,conforming to the applicable requirements of BS EN 60228.

2.2 Insulation

Extruded inner semi conductive layer, XLPE insulation and  extruded outer semi conductive layer .

2.3 Metallic Screen Layer

Copper wires + Open Helix Copper Tape on each core

2.4 Separation Sheath

Low Smoke Zero Halogen Compound .

2.5 Armour

GALVANIZED STEEL WIRES .

2.5 Sheath

Low Smoke Zero Halogen Compound .

TEST AT WORKS GENERALLY TO BS 7835

Routine Tests

- Max. DC conductors resistance at 20°C acc. to BS EN 60228

- High voltage test acc. to BS 7835  parag. 18.6

- Max. partial discharge test  acc. To BS 7835  parag. 18.5

 

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided.

 

Sample Tests

- Check of the build - up and color coding of the cable                                                    

- Check of dimensions                                                  

            Insulation                      :           according to BS 7835     Parag.  19.7

            Separation sheath         :           according to BS 7835     Parag.  19.12

            Armouring                     :           according to BS 7835     Parag.  19.14

            Oversheath                   :           according to BS 7835     Parag.  19.15

 

These tests will be carried out on one length of each size during each inspection .

Tests certificates will be provided by Liban Cables

 

Type Tests

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break  ) in accordance with BS 7835

These tests will be carried out on one length of the order .

Tests certificates will be provided by Liban Cables

DRAWING 3C MV CABLE CWS and GSWA

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Circular
Material of the inner semi-conductor
Extruded
Insulation
XLPE
Screen
Copper wires + copper tape
Armour type
Galvanized steel wires
Outer sheath
LSZH compound
Colour
Red
Conductor flexibility
Stranded class 2

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
240 mm²
Conductor diameter
18.1 mm
Nominal insulation thickness
3.4 mm
Screen section
35 mm²
Nominal armour wire diameter
3.15 mm
Nominal outer sheath thickness
3.5 mm
Nominal outer diameter
79.0 mm
Approximate net weight
14475 kg/km

Electrical characteristics

Electrical characteristics

Perm current rating in air 30°C
529 A
Permissible current rating when buried
431 A
Max. DC resistance of the conductor at 20°C
0.0754 Ohm/km
A.C. Conductor resist. 50Hz and at 90 °C
0.0981 Ohm/km
Thermal soil resistivity wet zone
1.5 °K.m/W

Usage characteristics

Usage characteristics

Laying depth, center of system
800 mm
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Max. conductor temperature in service
90 °C
Operating temperature, range
-25 ... 55 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*