Single Core Cu Cond. CTS Unarmored LSZH Sheath
Single Core Cu Cond. CTS Unarmored LSZH Sheath
M3N2U 1*400
Nexans ref. M3N2U 001256 - Country ref. M3N2U 1*400
- Conductor diameter: 23.2 mm
- Nominal insulation thickness: 3.4 mm
- Nominal outer sheath thickness: 2.2 mm
- Nominal outer diameter: 37.0 mm
- Approximate net weight: 4137 kg/km
- Perm current rating in air 30°C: 845 A
- Permissible current rating when buried: 590 A
- Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.646 Ohm/km
- Resistant to termites: No
M3N2U 1*95 NEW
Nexans ref. M3N2U 001459 - Country ref. M3N2U 1*95//UV
- Conductor diameter: 11.4 mm
- Nominal insulation thickness: 3.4 mm
- Nominal outer sheath thickness: 2.7 mm
- Nominal outer diameter: 29.0 mm
- Approximate net weight: 1656 kg/km
- Perm current rating in air 30°C: 361 A
- Permissible current rating when buried: 285 A
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.247 Ohm/km
- Resistant to termites: No
M4N2U 1*240(AT)//UV NEW
Nexans ref. M4N2U 000261 - Country ref. M4N2U 1*240(AT)//UV
- Conductor diameter: 18.1 mm
- Nominal insulation thickness: 4.5 mm
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 33.0 mm
- Approximate net weight: 2527 kg/km
- Perm current rating in air 30°C: 641 A
- Permissible current rating when buried: 469 A
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.0981 Ohm/km
- Resistant to termites: Yes
M4N2U 1*630(AT)//UV NEW
Nexans ref. M4N2U 000262 - Country ref. M4N2U 1*630(AT)//UV
- Conductor diameter: 30.2 mm
- Nominal insulation thickness: 4.5 mm
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 47.0 mm
- Approximate net weight: 2527 kg/km
- Perm current rating in air 30°C: 1154 A
- Permissible current rating when buried: 749 A
- Max. DC resistance of the conductor at 20°C: 0.0283 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.0407 Ohm/km
- Resistant to termites: Yes
Description
Description
Standards
-
InternationalIEC 60228; IEC 60332-1-2; IEC 60502-2
1-SCOPE
This specification covers Single core unarmoured cables, conforming to IEC 60502-2 Specifications.
2. CONSTRUCTION
2.1 Conductor
Plain, annealed electrolytic copper conductors, circular stranded,conforming to the applicable requirements of IEC 60228.
2.2 Insulation
Extruded inner semi conductive layer, XLPE insulation and extruded outer semi conductive layer .
2.3 Metallic Screen Layer
Copper tape
2.4 Sheath
LSZH
3. TESTS
All tests required by IEC 60502-2 either on Raw material or on finished products.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania