Single core Cu Cond. CWS, AWA and LSZH sheath

Products

M3N5UWU 1*185/25

Nexans ref. M3N5UWU020170 - Country ref. M3N5UWU 1*185/25//KEL

 

Description

Description

Standards

  • International
    IEC 60332-1-2
  • National
    BS 7835

1-SCOPE

This specification covers single core armoured cables.
 

2. CONSTRUCTION

2.1 Conductor

Plain, annealed electrolytic copper conductors, circular stranded,conforming to the applicable requirements of BS EN 60228.

2.2 Insulation

Extruded inner semi conductive layer, XLPE insulation and  extruded outer semi conductive layer .

2.3 Metallic Screen Layer

Copper wires + Open Helix Copper Tape

2.4 Separation Sheath

Low Smoke Zero Halogen Compound .

2.5 Armour

ALUMINUM WIRES .

2.5 Sheath

Low Smoke Zero Halogen Compound .

TEST AT WORKS GENERALLY TO BS 7835

Routine Tests

- Max. DC conductors resistance at 20°C acc. to BS EN 60228

- High voltage test acc. to BS 7835  parag. 18.6

- Max. partial discharge test  acc. To BS 7835  parag. 18.5

 

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided.

 

Sample Tests

- Check of the build - up and color coding of the cable                                                    

- Check of dimensions                                                  

            Insulation                      :           according to BS 7835     Parag.  19.7

            Separation sheath         :           according to BS 7835     Parag.  19.12

            Armouring                     :           according to BS 7835     Parag.  19.14

            Oversheath                   :           according to BS 7835     Parag.  19.15

 

These tests will be carried out on one length of each size during each inspection .

Tests certificates will be provided by Liban Cables

 

Type Tests

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break  ) in accordance with BS 7835

These tests will be carried out on one length of the order .

Tests certificates will be provided by Liban Cables

DRAWING 1C CSW and AWA

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Circular
Material of the inner semi-conductor
Extruded
Insulation
XLPE
Screen
Copper wires + copper tape
Armour type
Aluminium Wire
Outer sheath
LSZH compound
Colour
Red
Conductor flexibility
Class 2 IEC 60228

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
185 mm²
Conductor diameter
15.9 mm
Nominal insulation thickness
3.4 mm
Screen section
25 mm²
Nominal armour wire diameter
2 mm
Nominal outer sheath thickness
2.2 mm
Nominal outer diameter
37.0 mm
Approximate net weight
2930 kg/km

Electrical characteristics

Electrical characteristics

Perm current rating in air 30°C
543 A
Permissible current rating when buried
406 A
Max. DC resistance of the conductor at 20°C
0.0991 Ohm/km
A.C. Conductor resist. 50Hz and at 90 °C
0.128 Ohm/km
Thermal soil resistivity wet zone
1.5 °K.m/W

Usage characteristics

Usage characteristics

Laying depth, center of system
800 mm
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Max. conductor temperature in service
90 °C
Operating temperature, range
-25 ... 55 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close