Single core Cu Cond. CWS, Lead, AWA and fire retardant PVC Sheath+AT
Single core Cu Cond. CWS, Lead, AWA and fire retardant PVC Sheath+AT
Description
Description
Standards
-
InternationalIEC 60228; IEC 60332-1-2; IEC 60332-3; IEC 60502-2
1-SCOPE
This specification covers single core armoured cables.
2. CONSTRUCTION
2.1 Conductor
Plain, annealed electrolytic copper conductors, circular stranded,conforming to the applicable requirements of IEC 60228.
2.2 Insulation
Extruded inner semi conductive layer, XLPE insulation and extruded outer semi conductive layer .
2.3 Metallic Screen Layer
Copper wires + Open Helix Copper Tape
2.4 Separation Sheath
Special PVC .
2.5 Metal Sheath
Polyester Tape + Lead
2.6 Armour
ALUMINUM WIRES .
2.7 Sheath
Special PVC with Anti-termites .
TEST AT WORKS FIRE RETARDANT MV CABLE ARMORED WITH LEAD SHEATH
Routine Tests
- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-2 parag.16.1& 16.2
- High voltage test acc. to IEC 60502-2 parag. 16.1& 16.4
- Max. partial discharge test at 1.73 Uo acc. to IEC 60502-2 parag.16.1& 16.3
( The test voltage shall be raised gradually to and held at 2U0 for 10s and than slowly reduced to 1.73U0).
Liban Cables will carry out these tests on all the lengths and tests certificates will be provided
Sample Tests
- Check of the build - up and color coding of the cable
- Check of dimensions
Insulation : according to IEC 60502-2 Parag. 17.5.2
Metal sheath : according to EEMUA 133 Table 1
Separation sheath : according to IEC 60502-2 Parag. 17.5.3
Armouring : according to IEC 60502-2 Parag. 17.7
Oversheath : according to IEC 60502-2 Parag. 17.5.3
- Hot Set Test for XLPE insulation according to IEC 60502-2 Parag. 17.10
- Voltage test for 4 hours.
These tests will be carried out on one length of each size during each inspection .
Tests certificates will be provided by Liban Cables
Type Tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break ) in accordance with IEC 60502-2.
Fire retardance test according to IEC 60332-3.
These tests will be carried out on one length of the order .
Tests certificates will be provided by Liban Cables
drawing AWA+LEAD MV CABLE
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania