NHAKXS single core IEC 60332-3

Products

NA2XSH 1*300/50 6/10kV

Nexans ref. M3A4U 009106 - Country ref. M3A4U 1*300/50//POL-2

  • Conductor cross-section: 300 mm²
  • Nominal insulation thickness: 3.4 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal outer diameter: 38.0 mm
  • Test voltage: 21 kV
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV

 

NHAKXS 1*120/50 6/10kV

Nexans ref. M3A4U 009034 - Country ref. M3A4U 1*120/50//POL-2

  • Conductor cross-section: 120 mm²
  • Nominal insulation thickness: 3.4 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal outer diameter: 30.0 mm
  • Test voltage: 21 kV
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV

 

NHAKXS 1*150/50 6/10kV

Nexans ref. M3A4U 009067 - Country ref. M3A4U 1*150/50//POL-2

  • Conductor cross-section: 150 mm²
  • Nominal insulation thickness: 3.4 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 1.9 mm
  • Nominal outer diameter: 32.0 mm
  • Test voltage: 21 kV
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV

 

NHAKXS 1*240/50 6/10kV

Nexans ref. M3A4U 009105 - Country ref. M3A4U 1*240/50//POL-2

  • Conductor cross-section: 240 mm²
  • Nominal insulation thickness: 3.4 mm
  • Screen section: 50 mm²
  • Nominal outer sheath thickness: 2.0 mm
  • Nominal outer diameter: 35.0 mm
  • Test voltage: 21 kV
  • Rated Voltage Uo/U (Um): 6 / 10 (12) kV

 

NHAKXS 1*240/95 8.7/15kV

Nexans ref. M4A4U 000601 - Country ref. M4A4U 1*240/95//POL-2

  • Conductor cross-section: 240 mm²
  • Nominal insulation thickness: 4.5 mm
  • Screen section: 95 mm²
  • Nominal outer sheath thickness: 2.1 mm
  • Nominal outer diameter: 39.0 mm
  • Test voltage: 30 kV
  • Rated Voltage Uo/U (Um): 8.7 / 15 (17.5) kV

 

Description

Description

Standards

  • International
    IEC 60332-1-2; IEC 60332-3; IEC 60502-2

AL/SC/XLPE/SC/SC TAPE/CU WIRES/LSZH

APPLICATION

Power use outdoor application, even wet.

Suitable for fixed installations at open air, in tube or canals and underground.

Max. Operation temperature: 90°

Max. Short circuit temperature : 250° (Max 5 s)

 

CONSTRUCTION

1. Conductor:

Compacted Round conductor class 2

2. Insulation:

Extruded inner semi conductive layer, XLPE insulation and  extruded outer semi conductive layer + Semi-conductive tape

3. Metallic screen layer:

Copper wires with open helix copper tape

4. Outer sheath:

Low Smoke Zero Halogen compound, Red or as per customer requirement

5. Marking:

By Inkjet

6. Packing:

Drums can be wooden or steel

TEST AT WORKS according to IEC 60502-2 & IEC 60332-3

Routine Tests
-Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-2 parag. 16.1 & 16.2
-High voltage test acc. to IEC 60502-2 parag. 16.1 & 16.4
-Max. partial discharge test at 1.73 Uo acc. to IEC 60502-2 parag. 16.1 & 16.3

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided 

                                                                       

Sample tests

 -          Check of the build - up and color coding of the cable                                                      

 -          Check of dimensions                                                    

            Insulation          :           according to IEC 60502-2                       Parag.  17.5.2

            Metallic screen  :           according to IEC 60502-2                       Parag.  17.7

            Oversheath       :           according to IEC 60502-2                       Parag.  17.5.3

- Hot Set Test for XLPE insulation according to IEC 60502-2 parag. 17.10

                                                                       

These tests will be carried out on one length of each size during each inspection . 

Tests certificates will be provided by Liban Cables                                                                      

                                                                       

Type tests

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-2. 

Fire retardance test according to IEC 60332-3

These tests will be carried out on one length of the order.

Tests certificates will be provided by Liban Cables

DRAWING HFFR

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Round compacted
Material of the inner semi-conductor
Semi-conducting compound
Insulation
XLPE
Material of the external semi-conductor
Extruded fully bonded
Concentric conductor
Copper wires and helical copper tape
Sheath colour
Red

Electrical characteristics

Electrical characteristics

Frequence
50 Hz

Mechanical characteristics

Mechanical characteristics

Cable flexibility
12 x D
Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

U.V resistance
Yes
Flame retardant
IEC 60332-1-2
Fire retardant
IEC 60332-3

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error