Fire retardant, Unarmored, single core XLPE insulation, PVC sheathed
Fire retardant, Unarmored, single core XLPE insulation, PVC sheathed
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
EX 1*10
Nexans ref. EX 000158 - Country ref. EX 1*10//FR
- Conductor cross-section: 10 mm²
- Nominal insulation thickness: 0.7 mm
- Nominal outer sheath thickness: 1.4 mm
- Nominal outer diameter: 9.5 mm
- Approximate weight: 170 kg/km
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Permissible current rating in open air: 80 A
- Permissible current rating when buried: 91 A
EX 1*120
Nexans ref. EX 000231 - Country ref. EX 1*120//FR
- Conductor cross-section: 120 mm²
- Nominal insulation thickness: 1.5 mm
- Nominal outer sheath thickness: 1.5 mm
- Nominal outer diameter: 20.0 mm
- Approximate weight: 1275 kg/km
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Permissible current rating in open air: 379 A
- Permissible current rating when buried: 363 A
EX 1*150
Nexans ref. EX 000247 - Country ref. EX 1*150//FR
- Conductor cross-section: 150 mm²
- Nominal insulation thickness: 1.4 mm
- Nominal outer sheath thickness: 1.6 mm
- Nominal outer diameter: 20.0 mm
- Approximate weight: 1450 kg/km
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Permissible current rating in open air: 435 A
- Permissible current rating when buried: 405 A
EX 1*16
Nexans ref. EX 000117 - Country ref. EX 1*16//FR
- Conductor cross-section: 16 mm²
- Nominal insulation thickness: 0.7 mm
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 10.3 mm
- Approximate weight: 231 kg/km
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Permissible current rating in open air: 107 A
- Permissible current rating when buried: 112 A
EX 1*185
Nexans ref. EX 000249 - Country ref. EX 1*185//FR
- Conductor cross-section: 185 mm²
- Nominal insulation thickness: 1.6 mm
- Nominal outer sheath thickness: 1.6 mm
- Nominal outer diameter: 22.0 mm
- Approximate weight: 1810 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Permissible current rating in open air: 496 A
- Permissible current rating when buried: 457 A
EX 1*240
Nexans ref. EX 000255 - Country ref. EX 1*240//FR
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 1.7 mm
- Nominal outer sheath thickness: 1.7 mm
- Nominal outer diameter: 26.7 mm
- Approximate weight: 2463 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Permissible current rating in open air: 584 A
- Permissible current rating when buried: 529 A
EX 1*25
Nexans ref. EX 000185 - Country ref. EX 1*25//FR
- Conductor cross-section: 25 mm²
- Nominal insulation thickness: 0.9 mm
- Nominal outer sheath thickness: 1.4 mm
- Nominal outer diameter: 12.0 mm
- Approximate weight: 332 kg/km
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Permissible current rating in open air: 142 A
- Permissible current rating when buried: 148 A
EX 1*300
Nexans ref. EX 000272 - Country ref. EX 1*300//FR
- Conductor cross-section: 300 mm²
- Nominal insulation thickness: 1.8 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 29.0 mm
- Approximate weight: 3060 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
- Permissible current rating in open air: 665 A
- Permissible current rating when buried: 600 A
EX 1*35
Nexans ref. EX 000191 - Country ref. EX 1*35//FR
- Conductor cross-section: 35 mm²
- Nominal insulation thickness: 0.9 mm
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 12.9 mm
- Approximate weight: 427 kg/km
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Permissible current rating in open air: 175 A
- Permissible current rating when buried: 179 A
EX 1*4
Nexans ref. EX 000154 - Country ref. EX 1*4//FR
- Conductor cross-section: 4 mm²
- Nominal insulation thickness: 0.7 mm
- Nominal outer sheath thickness: 1.4 mm
- Nominal outer diameter: 8.0 mm
- Approximate weight: 102 kg/km
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Permissible current rating in open air: 45 A
- Permissible current rating when buried: 51 A
EX 1*400
Nexans ref. EX 000279 - Country ref. EX 1*400//FR
- Conductor cross-section: 400 mm²
- Nominal insulation thickness: 2.0 mm
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 31.0 mm
- Approximate weight: 3740 kg/km
- Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
- Permissible current rating in open air: 779 A
- Permissible current rating when buried: 690 A
EX 1*500
Nexans ref. EX 000288 - Country ref. EX 1*500//FR
- Conductor cross-section: 500 mm²
- Nominal insulation thickness: 2.0 mm
- Nominal outer sheath thickness: 2.0 mm
- Nominal outer diameter: 36.6 mm
- Approximate weight: 4953.3 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0366 Ohm/km
- Permissible current rating in open air: 870 A
- Permissible current rating when buried: 780 A
EX 1*95
Nexans ref. EX 000214 - Country ref. EX 1*95//FR
- Conductor cross-section: 95 mm²
- Nominal insulation thickness: 1.1 mm
- Nominal outer sheath thickness: 1.5 mm
- Nominal outer diameter: 18.2 mm
- Approximate weight: 1030 kg/km
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Permissible current rating in open air: 327 A
- Permissible current rating when buried: 317 A
Description
Description
Standards
-
ProductIEC 60228; IEC 60502-1
-
TestIEC 60332-1-2; IEC 60332-3
Scope
This specification covers XLPE insulated, circular, single core unarmoured cables, rated at 0.6/1 KV according to IEC 60502-1 for use indoors, outdoors, and in cable ducts.
Construction
2.1 Conductor
Plain, annealed electrolytic copper conductors, circular stranded, conforming to the applicable requirements of IEC 60228.
2.2 Insulation
XLPE material, conforming to the applicable requirements of IEC 60502-1.
2.3 Sheath
Special PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.
2.4 TESTS
Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products.
TEST AT WORKS LV UNARMORED 1C FR
Routine Tests
- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag.15.1&15.2
- Spark test during insulation
Liban Cables will carry out these tests on all the length and tests certificates will be provided
Sample Tests
- Check of the build - up and color coding of the cable
- Check of dimensions
Insulation : according to IEC 60502-1 Parag. 16.5.2
Oversheath : according to IEC 60502-1 Parag. 16.5.3
These tests will be carried out on one length during each inspection .
Tests certificates will be provided by Liban Cables
Type Tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-1.
Fire retardance according to IEC 60332-3.
These tests will be carried out on one length of the order .
Tests certificates will be provided by Liban Cables
Drawing XLPE insulated 1C unarmored FR
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Find a Distributor
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania