Hydrocarbon resistant & Fire retardant, Multicore (PN), SWA Armored, XLPE insulated, PVC sheathed
Hydrocarbon resistant & Fire retardant, Multicore (PN), SWA Armored, XLPE insulated, PVC sheathed
0.6 / 1 KV POWER CABLES, Phase and Neutral conductor
Conforming to IEC 60502-1
EXR 3*120+70
Nexans ref. EXR 017772 - Country ref. EXR 3*120+70SM//FMCC
- Conductor cross-section: 120 mm²
- Nominal insulation thickness: 1.2 mm
- Earth conductor cross section: 70 mm²
- Insulation thickness of smaller conductor: 1.1 mm
- Nominal armour wire diameter: 2 mm
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 43.0 mm
- Approximate weight: 5783 kg/km
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.268 Ohm/km
- Permissible current rating in open air: 339 A
- Permissible current rating when buried: 345 A
EXR 3*150+70
Nexans ref. EXR 017773 - Country ref. EXR 3*150+70SM//FMCC
- Conductor cross-section: 150 mm²
- Nominal insulation thickness: 1.4 mm
- Earth conductor cross section: 70 mm²
- Insulation thickness of smaller conductor: 1.1 mm
- Nominal armour wire diameter: 2.5 mm
- Nominal outer sheath thickness: 2.5 mm
- Nominal outer diameter: 48.0 mm
- Approximate weight: 7214 kg/km
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.268 Ohm/km
- Permissible current rating in open air: 390 A
- Permissible current rating when buried: 386 A
EXR 3*185+95
Nexans ref. EXR 017774 - Country ref. EXR 3*185+95SM//FMCC
- Conductor cross-section: 185 mm²
- Nominal insulation thickness: 1.6 mm
- Earth conductor cross section: 95 mm²
- Insulation thickness of smaller conductor: 1.1 mm
- Nominal armour wire diameter: 2.5 mm
- Nominal outer sheath thickness: 2.7 mm
- Nominal outer diameter: 53.0 mm
- Approximate weight: 8806 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.193 Ohm/km
- Permissible current rating in open air: 444 A
- Permissible current rating when buried: 435 A
EXR 3*240+120
Nexans ref. EXR 017775 - Country ref. EXR 3*240+120SM//FMCC
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 1.7 mm
- Earth conductor cross section: 120 mm²
- Insulation thickness of smaller conductor: 1.2 mm
- Nominal armour wire diameter: 2.5 mm
- Nominal outer sheath thickness: 2.9 mm
- Nominal outer diameter: 59.0 mm
- Approximate weight: 10994 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.153 Ohm/km
- Permissible current rating in open air: 522 A
- Permissible current rating when buried: 504 A
EXR 3*25+16
Nexans ref. EXR 017767 - Country ref. EXR 3*25+16//FMCC
- Conductor cross-section: 25 mm²
- Nominal insulation thickness: 0.9 mm
- Earth conductor cross section: 16 mm²
- Insulation thickness of smaller conductor: 0.7 mm
- Nominal armour wire diameter: 1.6 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 26.0 mm
- Approximate weight: 1780 kg/km
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Resistance of neutral conductor at 20ºC: 1.15 Ohm/km
- Permissible current rating in open air: 127 A
- Permissible current rating when buried: 141 A
EXR 3*35+16
Nexans ref. EXR 017768 - Country ref. EXR 3*35+16//FMCC
- Conductor cross-section: 35 mm²
- Nominal insulation thickness: 0.9 mm
- Earth conductor cross section: 16 mm²
- Insulation thickness of smaller conductor: 0.7 mm
- Nominal armour wire diameter: 1.6 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 28.0 mm
- Approximate weight: 2151 kg/km
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Resistance of neutral conductor at 20ºC: 1.15 Ohm/km
- Permissible current rating in open air: 157 A
- Permissible current rating when buried: 170 A
EXR 3*50+25
Nexans ref. EXR 017769 - Country ref. EXR 3*50+25//FMCC
- Conductor cross-section: 50 mm²
- Nominal insulation thickness: 1.0 mm
- Earth conductor cross section: 25 mm²
- Insulation thickness of smaller conductor: 0.9 mm
- Nominal armour wire diameter: 1.6 mm
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 32.0 mm
- Approximate weight: 2807 kg/km
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.727 Ohm/km
- Permissible current rating in open air: 190 A
- Permissible current rating when buried: 204 A
EXR 3*70+35
Nexans ref. EXR 017770 - Country ref. EXR 3*70+35SM/RM//FMCC
- Conductor cross-section: 70 mm²
- Nominal insulation thickness: 1.1 mm
- Earth conductor cross section: 35 mm²
- Insulation thickness of smaller conductor: 0.9 mm
- Nominal armour wire diameter: 2 mm
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 35.0 mm
- Approximate weight: 3632 kg/km
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.524 Ohm/km
- Permissible current rating in open air: 242 A
- Permissible current rating when buried: 252 A
EXR 3*95+50
Nexans ref. EXR 017771 - Country ref. EXR 3*95+50SM/RM//FMCC
- Conductor cross-section: 95 mm²
- Nominal insulation thickness: 1.1 mm
- Earth conductor cross section: 50 mm²
- Insulation thickness of smaller conductor: 1.0 mm
- Nominal armour wire diameter: 2 mm
- Nominal outer sheath thickness: 2.2 mm
- Nominal outer diameter: 39.0 mm
- Approximate weight: 4652 kg/km
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.387 Ohm/km
- Permissible current rating in open air: 293 A
- Permissible current rating when buried: 302 A
EXR 4*120+70
Nexans ref. EXR 017795 - Country ref. EXR 4*120+70//FMCC
- Conductor cross-section: 120 mm²
- Nominal insulation thickness: 1.2 mm
- Earth conductor cross section: 70 mm²
- Insulation thickness of smaller conductor: 1.1 mm
- Nominal armour wire diameter: 2.5 mm
- Nominal outer sheath thickness: 2.5 mm
- Nominal outer diameter: 52.0 mm
- Approximate weight: 8212 kg/km
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.268 Ohm/km
- Permissible current rating in open air: 339 A
- Permissible current rating when buried: 345 A
EXR 4*150+70
Nexans ref. EXR 017796 - Country ref. EXR 4*150+70//FMCC
- Conductor cross-section: 150 mm²
- Nominal insulation thickness: 1.4 mm
- Earth conductor cross section: 70 mm²
- Insulation thickness of smaller conductor: 1.1 mm
- Nominal armour wire diameter: 2.5 mm
- Nominal outer sheath thickness: 2.7 mm
- Nominal outer diameter: 56.0 mm
- Approximate weight: 9606 kg/km
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.268 Ohm/km
- Permissible current rating in open air: 390 A
- Permissible current rating when buried: 386 A
EXR 4*185+95
Nexans ref. EXR 017797 - Country ref. EXR 4*185+95//FMCC
- Conductor cross-section: 185 mm²
- Nominal insulation thickness: 1.6 mm
- Earth conductor cross section: 95 mm²
- Insulation thickness of smaller conductor: 1.1 mm
- Nominal armour wire diameter: 2.5 mm
- Nominal outer sheath thickness: 2.9 mm
- Nominal outer diameter: 62.0 mm
- Approximate weight: 11766 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.193 Ohm/km
- Permissible current rating in open air: 444 A
- Permissible current rating when buried: 435 A
EXR 4*240+120
Nexans ref. EXR 017798 - Country ref. EXR 4*240+120//FMCC
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 1.7 mm
- Earth conductor cross section: 120 mm²
- Insulation thickness of smaller conductor: 1.2 mm
- Nominal armour wire diameter: 2.5 mm
- Nominal outer sheath thickness: 3.1 mm
- Nominal outer diameter: 69.0 mm
- Approximate weight: 14670 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.153 Ohm/km
- Permissible current rating in open air: 522 A
- Permissible current rating when buried: 504 A
EXR 4*35+16
Nexans ref. EXR 017791 - Country ref. EXR 4*35+16//FMCC
- Conductor cross-section: 35 mm²
- Nominal insulation thickness: 0.9 mm
- Earth conductor cross section: 16 mm²
- Insulation thickness of smaller conductor: 0.7 mm
- Nominal armour wire diameter: 1.6 mm
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 31.0 mm
- Approximate weight: 2597 kg/km
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Resistance of neutral conductor at 20ºC: 1.15 Ohm/km
- Permissible current rating in open air: 157 A
- Permissible current rating when buried: 170 A
EXR 4*50+25
Nexans ref. EXR 017792 - Country ref. EXR 4*50+25//FMCC
- Conductor cross-section: 50 mm²
- Nominal insulation thickness: 1.0 mm
- Earth conductor cross section: 25 mm²
- Insulation thickness of smaller conductor: 0.9 mm
- Nominal armour wire diameter: 2 mm
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 37.0 mm
- Approximate weight: 3670 kg/km
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.727 Ohm/km
- Permissible current rating in open air: 190 A
- Permissible current rating when buried: 204 A
EXR 4*70+35
Nexans ref. EXR 017793 - Country ref. EXR 4*70+35//FMCC
- Conductor cross-section: 70 mm²
- Nominal insulation thickness: 1.1 mm
- Earth conductor cross section: 35 mm²
- Insulation thickness of smaller conductor: 0.9 mm
- Nominal armour wire diameter: 2 mm
- Nominal outer sheath thickness: 2.2 mm
- Nominal outer diameter: 41.0 mm
- Approximate weight: 4810 kg/km
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.524 Ohm/km
- Permissible current rating in open air: 242 A
- Permissible current rating when buried: 252 A
EXR 4*95+50
Nexans ref. EXR 017794 - Country ref. EXR 4*95+50//FMCC
- Conductor cross-section: 95 mm²
- Nominal insulation thickness: 1.1 mm
- Earth conductor cross section: 50 mm²
- Insulation thickness of smaller conductor: 1.0 mm
- Nominal armour wire diameter: 2 mm
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 46.0 mm
- Approximate weight: 6218 kg/km
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Resistance of neutral conductor at 20ºC: 0.387 Ohm/km
- Permissible current rating in open air: 293 A
- Permissible current rating when buried: 302 A
Description
Description
Standards
-
ProductIEC 60228; IEC 60502-1
-
TestIEC 60332-1-2; IEC 60332-3
Scope
This specification covers XLPE insulated, circular or shaped, multicore armoured cables, rated at 0.6/1 KV according to IEC 60502-1.
Construction
2.1 Phase Conductor
Plain, annealed electrolytic copper conductors, circular stranded, or sectoral stranded only for 3 Cores+Eath: sizes ≥70 to ≤300, conforming to the applicable requirements of IEC 60228.
2.2 Phase Conductor Insulation
XLPE thermosetting material, conforming to the applicable requirements of IEC 60502-1.
2.3 Neutral Conductor
Plain, annealed electrolytic copper conductors, circular stranded, or sectoral stranded only for 3 Cores+Eath: sizes ≥70 to ≤300, conforming to the applicable requirements of IEC 60228.
2.4 Neutral Conductor Insulation
XLPE thermosetting material, conforming to the applicable requirements of IEC 60502-1.
2.5 Assembly
Insulated conductors are laid up, filled where necessary with non-hygroscopic material and covered with an extruded thickness of thermoplastic material.
2.6 Armour
Galvanized round wires completely covering the assembly of cores complying to the applicable requirements of IEC 60502-1.
2.7 Sheath
Special Hydrocarbon resistant and fire retardant PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.
2.8 TESTS
Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products.
TEST AT WORKS ACCORDING TO IEC 60502-1 & IEC 60332-3
Routine Tests
- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2
- Voltage test acc. to IEC 60502-1 parag.15.1& 15.3
Liban Cables will carry out these tests on all the lengths and tests certificates will be provided.
Sample Tests
- Check of the build - up and color coding of the cable
- Check of dimensions
Insulation : according to IEC 60502-1 Parag. 16.5.2
Armour : according to IEC 60502-1 Parag. 16.7
Oversheath : according to IEC 60502-1 Parag. 16.5.3
Hot Set Test for XLPE insulation: according to IEC 60502-1 Parag. 16.9
These tests will be carried out on one length of each size during each inspection .
Tests certificates will be provided by Liban Cables
Type Tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break ) in accordance with IEC 60502-1.
Fire retardance test according to IEC 60332-3.
These tests will be carried out on one length of the order.
Tests certificates will be provided by Liban Cables.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Find a Distributor
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania