Bare Copper conductors CNUR

Products

CNUR 10

Nexans ref. CNUR 000114 - Country ref. CNUR 10//M

  • Conductor cross-section: 10 mm²
  • Nominal overall diameter: 3.8 mm
  • Approximate weight: 86 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km

CNUR 120

Nexans ref. CNUR 001002 - Country ref. CNUR 120//M

  • Conductor cross-section: 120 mm²
  • Nominal overall diameter: 12.86 mm
  • Approximate weight: 1031 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km

CNUR 16

Nexans ref. CNUR 000127 - Country ref. CNUR 16//M

  • Conductor cross-section: 16 mm²
  • Nominal overall diameter: 4.7 mm
  • Approximate weight: 137 kg/km
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km

CNUR 185

Nexans ref. CNUR 001113 - Country ref. CNUR 185//M

  • Conductor cross-section: 185 mm²
  • Nominal overall diameter: 15.85 mm
  • Approximate weight: 1590 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km

CNUR 25

Nexans ref. CNUR 000137 - Country ref. CNUR 25//M

  • Conductor cross-section: 25 mm²
  • Nominal overall diameter: 5.87 mm
  • Approximate weight: 215 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km

CNUR 300

Nexans ref. CNUR 001228 - Country ref. CNUR 300//M

  • Conductor cross-section: 300 mm²
  • Nominal overall diameter: 20.3 mm
  • Approximate weight: 2595 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km

CNUR 35

Nexans ref. CNUR 000157 - Country ref. CNUR 35//M

  • Conductor cross-section: 35 mm²
  • Nominal overall diameter: 6.9 mm
  • Approximate weight: 296 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km

CNUR 50

Nexans ref. CNUR 000177 - Country ref. CNUR 50//M

  • Conductor cross-section: 50 mm²
  • Nominal overall diameter: 8.1 mm
  • Approximate weight: 407 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km

CNUR 6

Nexans ref. CNUR 000038 - Country ref. CNUR 6//M

  • Conductor cross-section: 6 mm²
  • Nominal overall diameter: 3.0 mm
  • Approximate weight: 51 kg/km
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km

CNUR 70

Nexans ref. CNUR 000252 - Country ref. CNUR 70//M

  • Conductor cross-section: 70 mm²
  • Nominal overall diameter: 9.71 mm
  • Approximate weight: 586 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km

CNUR 95

Nexans ref. CNUR 000960 - Country ref. CNUR 95//M

  • Conductor cross-section: 95 mm²
  • Nominal overall diameter: 11.4 mm
  • Approximate weight: 813 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km

Description

Description

Standards

  • International
    IEC 60228

DESCRIPTION:    CU   

           

CONDUCTOR:   STRANDED ANNEALED COPPER Class 2 acc. to IEC 60228

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Type of conductor
Stranded copper
Conductor shape
Circular

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close