XHAKXS Single Core 6/10KV

Products

XHAKXS 1*120/50 6/10KV

Nexans ref. M3A4P 008034 - Country ref. M3A4P 1*120/50//POL-1

 

Description

Description

Standards

  • International
    IEC 60228; IEC 60502-2

AL/SC/XLPE/SC/SC TAPE/CU WIRES/PE

APPLICATION

Power use outdoor application, even wet.

Suitable for fixed installations at open air, in tube or canals and underground.

Max. Operation temperature: 90°

Max. Short circuit temperature : 250° (Max 5 s)

 

CONSTRUCTION

1. Conductor:

Compacted Round conductor class 2

2. Insulation:

Extruded inner semi conductive layer, XLPE insulation and  extruded outer semi conductive layer + semi conductive tape

3. Metallic screen layer:

Copper wires with open helix copper tape

4. Outer sheath:

PE, Black or as per customer requirement

7. Marking:

By Inkjet

8. Packing:

Drums can be wooden or steel

TEST AT WORKS according to IEC 60502-2

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided                                                                 

                                                                       

Sample tests

 -          Check of the build - up and color coding of the cable                                                      

 -          Check of dimensions                                                    

            Insulation          :           according to IEC 60502-2                       Parag.  17.5.2

            Metallic screen  :           according to IEC 60502-2                       Parag.  17.7

            Oversheath       :           according to IEC 60502-2                       Parag.  17.5.3

- Hot Set Test for XLPE insulation according to IEC 60502-2 parag. 17.10

                                                                       

These tests will be carried out on one length of each size during each inspection .                                                                       

Tests certificates will be provided by Liban Cables                                                                      

                                                                       

Type tests

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-2.                                                                     

These tests will be carried out on one length of the order.

Tests certificates will be provided by Liban Cables

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Round compacted
Material of the inner semi-conductor
Semi-conducting compound
Insulation
XLPE
Material of the external semi-conductor
Extruded fully bonded
Concentric conductor
Copper wires and helical copper tape
Sheath colour
Black

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
120 mm²
Nominal insulation thickness
3.4 mm
Screen section
50 mm²
Nominal outer sheath thickness
1.8 mm
Nominal outer diameter
27.0 mm

Mechanical characteristics

Mechanical characteristics

Cable flexibility
10xD
Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Bending factor when laying
20 (xD)
Laying depth, center of system
800 mm
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close