Standards

  • Product
    IEC 60228; IEC 60502-1
  • Test
    IEC 60332-1-2

Scope

This specification covers XLPE insulated, circular, single core unarmoured cables, rated at 0.6/1 KV according to IEC 60502-1 for use indoors, outdoors, and in cable ducts.

Construction

2.1 Conductor

Plain, annealed electrolytic copper conductors, circular stranded, conforming to the applicable requirements of IEC 60228.

2.2 Insulation

XLPE material, conforming to the applicable requirements of IEC 60502-1.

2.3 Sheath

Special PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.

2.4 TESTS

Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products.

TEST AT WORKS unarmored single core

Routine Tests

 -  Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2

 -  Spark test during insulation                                                       

 Liban Cables will carry out these tests on all the length and tests certificates will be provided.                                                                  

                                                                       

Sample Tests                                                              

 -          Check of the build - up and color coding of the cable                                                      

 -          Check of dimensions                                                    

            Insulation          :           according to IEC 60502-1                       Parag.  16.5.2

            Oversheath       :           according to IEC 60502-1                       Parag.  16.5.3

                                                                       

These tests will be carried out on one length during  of each size during each inspection . 

Tests certificates will be provided by Liban Cables 

                                                                       

Type Tests                                                                  

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-1.

These tests will be carried out on one length of the order.

Tests certificates will be provided by Liban Cables

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Circular
Number of conductors
1
Insulation
XLPE
Outer sheath
Special PVC compound
Colour
Black

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
240 mm²
Nominal insulation thickness
1.7 mm
Nominal outer sheath thickness
1.7 mm
Nominal outer diameter
25.0 mm
Approximate weight
2304 kg/km

Electrical characteristics

Electrical characteristics

Thermal soil resistivity wet zone
1 °K.m/W
Max. DC resistance of the conductor at 20°C
0.0754 Ohm/km
Permissible current rating in open air
584 A
Permissible current rating when buried
529 A
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
6xD

Usage characteristics

Usage characteristics

Operating temperature, range
-35 ... 55 °C
Installation temperature, range
-5 ... 50 °C
Ambient air temperature
30 °C
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Flame retardant
IEC 60332-1-2
Laying depth, center of system
600 mm

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close