E(NYY) 1*120
0.6 / 1 KV POWER CABLES Conforming to IEC 60502-1
Read more- Nexans ref. : E(NYY) 000565
- Country ref. : E(NYY) 1*120
Description
Description
Standards
-
ProductIEC 60228; IEC 60502-1
-
TestIEC 60332-1-2
Scope
This specification covers PVC insulated, circular, single core unarmoured cables, rated at 0.6/1 KV according to IEC 60502-1 for use indoors, outdoors, and in cable ducts.
Construction
2.1 Conductor
Plain, annealed electrolytic copper conductors, circular stranded, conforming to the applicable requirements of IEC 60228.
2.2 Insulation
PVC material, conforming to the applicable requirements of IEC 60502-1.
2.3 Sheath
PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.
2.4 TESTS
Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products.
TEST AT WORKS unarmored single core
Routine Tests
- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2
- Spark test during insulation
Liban Cables will carry out these tests on all the length and tests certificates will be provided.
Sample Tests
- Check of the build - up and color coding of the cable
- Check of dimensions
Insulation : according to IEC 60502-1 Parag. 16.5.2
Oversheath : according to IEC 60502-1 Parag. 16.5.3
These tests will be carried out on one length during of each size during each inspection .
Tests certificates will be provided by Liban Cables
Type Tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-1.
These tests will be carried out on one length of the order.
Tests certificates will be provided by Liban Cables
Cable identification - LV cables ≤ 1KV
INSULATION COLORS:
|
Neutral |
Cond.1 |
Cond.2 |
Cond.3 |
Cond.4 |
1 Conductor |
|
BLACK |
|
|
|
2 Conductors |
GREY |
BLACK |
|
|
|
3 Conductors |
|
BLACK |
RED |
BLUE |
|
4 Conductors |
GREY |
BLACK |
RED |
BLUE |
|
5 Conductors |
GREY |
BLACK |
RED |
BLUE |
GREEN |
All numbered control cables (6 conductors and above), are insulated with white color, and numbered with black digits
CABLE MARKING OVER THE OUTER JACKET (by inkjet printing):
LIBAN CABLES DESCRIPTION RATED VOLTAGE SECTION MM2 Year of manufacture meter marking
Other cable identification requirements are available upon request
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Dealer locator
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania